RA Indoor Unit Functions
SiUS121827E
68
Part 4 Functions and Control
Reference
CTXS, FTXS Series
FDXS, CDXS, FVXS Series
Refer to Temperature Control on page 59 for details.
2.6 NIGHT SET Mode
Outline
When the OFF TIMER is set, NIGHT SET mode is automatically activated. NIGHT SET mode
keeps the airflow rate setting.
Details
NIGHT SET mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers the target
temperature slightly in the case of heating. This prevents excessive cooling in summer and
excessive heating in winter to ensure comfortable sleeping conditions, and also conserves
electricity.
Cooling
Heating
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
2.0°C (3.6°F)
1.0°C (1.8°F)
0.5°C (0.9°F)
1.5°C (2.7°F)
2.0°C (3.6°F)
Room thermistor temperature – target temperature
(R24033)
Room thermistor temperature – target temperature
(R24034)
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
1.5°C (2.7°F)
0°C (0°F)
1.0°C (1.8°F)
(R23917)
Target temperature
+0.5°C (+0.9°F)
temperature shift
Operation stops
at the set hour
0.5°C (0.9°F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2°C (–3.6°F)
temperature shift
1 hour
2°C (3.6°F)
(R23918)
TIMER operation
NIGHT SET Mode ON