
6
|
Unit installation
Installer reference guide
28
2(A)MXM40+50 + 2(A)MXF40+50
R32 Split series
4P600463-3D – 2021.03
Example:
Behind the building.
b
c
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
▪
Height of windbreaker≥1.5×height of outdoor unit
▪
Mind the service space requirements when installing the windbreaker.
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient
temperatures within the following ranges (unless otherwise specified in the
operation manual of the connected indoor unit):
Cooling mode
Heating mode
–10~46°C DB
–15~24°C DB
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction