ED15117
59
BACnet
No BACnet equivalent
L
ON
W
ORKS
LonWorks Name
Profile
Uses Heartbeat
SNVT Type
SNVT Number
nviRequest Node
Object
No
SNVT_obj_status
93
Enumeration Definitions (object_request_t)
Value
Identifier
Notes
0
RQ_NORMAL
Enable object and remove override
1
RQ_DISABLED
Disable object (not supported)
2
RQ_UPDATE_STATUS
Report object status
3
RQ_SELF_TEST
Perform object self-test (not supported)
4
RQ_UPDATE_ALARM
Update alarm status (not supported)
5
RQ_REPORT_MASK
Report status bit mask
6
RQ_OVERRIDE
Override object (not supported)
7
RQ_ENABLE
Enable object (not supported)
8
RQ_RMV_OVERRIDE
Remove object override (not supported)
9
RQ_CLEAR_STATUS
Clear object status (not supported)
10
RQ_CLEAR_ALARM
Clear object alarm (not supported)
11
RQ_ALARM_NOTIFY_ENABLED
Enable alarm notification (not supported)
12
RQ_ALARM_NOTIFY_DISABLED
Disable alarm notification (not supported)
13
RQ_MANUAL_CTRL
Enable object for manual control (not supported)
14
RQ_REMOTE_CTRL
Enable object for remote control (not supported)
15
RQ_PROGRAM
Enable programming of special configuration properties (not supported)
16
RQ_CLEAR_RESET
Clear reset-complete flag (reset_complete) (not supported)
17
RQ_RESET
Execute reset-sequence of object (not supported)
-1(0xFF) OC_NUL
Invalid
Value
Outdoor Air Temperature
This read only network variable indicates the current outdoor air temperature.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
signed long
-40° to 212°F
-40° to 100°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
5
Present Value
85
Object Name
OutdoorAirTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoOutdoorTemp McQuayChiller SNVT_temp_p
105
two
bytes
Pump Select
This L
ON
W
ORKS
-only read/write network variable selects which pump (#1 or # 2) supplies the data.
The unit controller returns the information for the appropriate Condenser or Evaporator pump. You
must first select a pump and then interrogate the selected pump. See Condenser Pump Run Hours and
Evaporator Pump Run Hours.