FSDEL-218-161
INSTRUCTION MANUAL
PLUG-IN TRANSDUCER
FINE SERIES
ALARM SETTER
FSDEL
Page 1: ...FSDEL 218 161 INSTRUCTION MANUAL PLUG IN TRANSDUCER FINE SERIES ALARM SETTER FSDEL...
Page 2: ...ase check the tightening of the screw Preparation This product must be set before use Please read this manual and make the setting correctly Maintenance and inspection Inspection during energization i...
Page 3: ...Method of operation 3 1 Name and function of each part 8 3 2 Display mode and operation 8 3 3 Measurement mode 9 3 4 Setting mode 10 3 5 Calibration 12 4 Model name and specification code 13 5 Specifi...
Page 4: ...output operation status is displayed on the monitor lamp red on the front Test function Alarm output operation can be confirmed without applying input Wide variety of setting functions There are setti...
Page 5: ...please install with M3 screw or M4 screw However the screw is not attached The tightening torque of a screw M3 0 45 to 0 60N m M4 1 00 to 1 30N m Please consider radiation and wiring space and separa...
Page 6: ...nd push in the lower Slider 2 How to fix a body to a socket Do in the direction which can read a label character correctly and insert a body straightly Press with the screw of a body Please do not tig...
Page 7: ...5 6 OUTPUT2 7 8 OUTPUT1 10 AUX SUPPLY OUTPUT b 9 8 11 COM 7 a INPUT 3 2 1 INPUT 1 2 INPUT 3 2 1 3 4 E S2 AUX SUPPLY S1 5 6 b 7 8 OUTPUT a COM INPUT 1 2 Terminals 5 and 8 are internally connected when...
Page 8: ...te wiring of input and output and perform consideration to noise And please separate from a line with the power line used as the source of a noise and steep voltage and current as much as possible Ple...
Page 9: ...operation value until the end of the delay time 3 2 Display mode and operation Switching of each mode There are three display modes and it switches to each mode by the following switch operation Measu...
Page 10: ...is displayed in the upper row The operation value of the alarm output is displayed in the lower row H Upper limit detection L Lower limit detection Maximum value display Minimum value display Input v...
Page 11: ...ation SPAN point calibration Decimal point Average number Pre alarm Starting delay time Display off time Software version Luminance Return ENTER ENTER Scaling minimum value Scaling maximum value Unit...
Page 12: ...ng Contact delay Return method Excitation mode Return ENTER At the same time 1 time or more than 1 second or return screen ENTER At the same time 1 time or more than 1 second Switch other setting item...
Page 13: ...f alarm output shifts in the use over many years please adjust in the next way 1 After applying auxiliary power supply pre energize warm up for 15 minutes 2 Set the setting value C BIAS so that the mi...
Page 14: ...ut Contact composition and output points 1 point Change over break before make contact N O N C Omron Corporation G6S 2F DC12V 2 points Both make contact N O Both break contact N C Individual make cont...
Page 15: ...p Relay Monitor lamp ON Monitor lamp OFF Non excitation Excitation L Monitor lamp Relay Excitation Non excitation Non excitation H Monitor lamp Relay Excitation Non excitation L Monitor lamp Relay Non...
Page 16: ...on in shortage input detection Output mode Excitation L Operation value setting Relay action ON OFF Input Contact delay setting time Contact delay setting time Contact delay setting time Dead band Set...
Page 17: ...rm function constitutes OFF Relay action and pre alarm in over input detection Output mode setting Excitation H Pre alarm setting ON Operation value setting Relay action ON OFF Dead band Setting value...
Page 18: ...R M AUTO AUTO HOLD 18 ALARM1 Output mode ALMD1 HIGH High H operation Low L operation OFF Non operation 19 Operation value COMP1 70 0 With respect to the real scale within the measurement display rang...
Page 19: ...mL min L min L h kL h 10t min 10t h 10m3 min 10kL h 10 1 m3 s 102 m3 h 17 Normal m3 s normal m3 min normal m3 h normal m3 d normal L s normal mL min normal L min normal L h normal kL h normal 18 Quant...
Page 20: ...e operating point 0 1 of input span Operating time 0 25 seconds of contact delay time set value However in case of set value 0 second 0 5 0 25 seconds Average number N 1 0 5s 0 25s Average number N 4...
Page 21: ...inutes each No malfunction Shock JIS C 60068 2 27 Shock of 98m s2 X Y Z direction for each 3 times No malfunction Shock of 294m s2 X Y Z direction for each 3 times No abnormality Overload capacity Vol...
Page 22: ...frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During test No malfunction After test Normal operation EN61000 6 2 2005 EN61000 4 8 2014 Voltage d...
Page 23: ...es Power LED does not light up Supplementary power supply is not applied to terminals 10 and 11 Applying the auxiliary supply Display disappears By auto off function Pressing the switch Display error...
Page 24: ...13 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774 54 1353...