Figure 5-12
Step 2. Set statistical cycle (period) and max alarm.
Statistical cycle: time interval of each time alarm count, unit is second, max1800s.
Max alarm: within the statistical cycle, max alarm log number received by the system,
unit is item, which is 6 by default.
Step 3. Click OK.
5.7
Power Failure
When alarms occur due to power failure, high voltage, low voltage, or lack of equal status, the
other alarm points can be set as "filtering monitoring points" to filter out these linkage alarm
messages when other devices generate linkage alarms. .
For example, because the main power-down, resulting in air-conditioning also power-down, this
time will also produce the main power failure alarm information and air conditioning power failure
alarm information. If the main power failure is set to "display monitoring point", air conditioning
power failure is set to "filter monitoring point", you can filter air conditioning power failure alarm
information, only displaying the main power failure alarm information.
Step 1. Select Environment Config>Power Failure, see Figure 5-13.
Summary of Contents for ARC6416C series
Page 1: ...1 Video Field Surveillance Unit User s Manual V 1 0 0 For ARC6416C series...
Page 8: ...Figure 1 1...
Page 23: ...Figure 4 5 4 3 3 Add Peripheral Protocol Step 1 Click 3 Protocol Management see Figure 4 6...
Page 105: ...Figure 7 3 Click to view detailed alarm of each peripheral see Figure 7 4 Figure 7 4...