7 PROTECTION SYSTEMS
The inverter is equipped with protection systems designed to preserve the pump, motor, power line and the
inverter itself. When one or more protections trip, the one with the highest priority is shown on display.
Depending on the type of error, the electric pump may shut down, but when normal conditions are restored,
the error state may clear automatically, immediately or after a set time interval following automatic reset.
In the case of a block due to water supply failure (BL), block due to pump motor current overload (OC), block
due to final output stage current overload (OF), block due to direct short circuit between the phases on the
output terminal (SC), the user can attempt to manually reset the error condition by pressing and releasing
b and - simultaneously. If the error condition persists, the cause of the fault must be located and
eliminated.
Alarm in fault log
Display message
Description
PD Irregular
shutdown
FA
Problems with cooling system
Table 28: Alarms
Block conditions
Display message
Description
BL
Block due to water failure
BP
Block due to pressure sensor reading error
LP
Block due to low power supply voltage
HP
Block due to high internal power supply voltage
OT
Block due to overheating of final power stages
OB
Block due to overheating of printed circuit
OC
Block due to current overload on electric pump motor
OF
Block due to current overload on final stages of output
SC
Block due to direct short circuit between the phases on the output terminal
EC
Block due to lack of rated current setting (RC)
Ei
Block due to “i” internal error
Vi
Block due to “I” internal voltage outside tolerance
Table 29: Block information
7.1 Description of blocks
7.1.1
“BL” Block due to water failure
In flow conditions below minimum value, with pressure lower than the set regulation value, a water failure
signal is emitted and the system shuts down the pump. The delay interval without pressure and flow can be
set in the parameter TB of the TECHNICAL ASSISTANCE menu.
If the user inadvertently enters a pressure setpoint higher than the pressure that the electric pump can
supply on closure, the system indicates “block due to water failure” (BL) even if this is not precisely the
problem. In this case, lower the regulation pressure to a reasonable value, which does not normally exceed
2/3 of the head of the electrical pump installed.
Summary of Contents for MCE-22/P
Page 278: ...274 1 276 2 279 3 280 4 282 5 283 6 4 20 284 7 285 8 286 9 287 10 290 11 290 12 292...
Page 279: ...275 IEC 60634...
Page 280: ...276 1 6 MCE 22 P MCE 15 P MCE 11 P 1 1 1...
Page 282: ...278 2 5 2 1 2 1 2 2 1 1 2 1 2 L L L 2 2 4 15...
Page 283: ...279 2 2 2 1 2 2 1 1 3 1 LN 2 2 3 1 3 4 4...
Page 284: ...280 A 3 3 2 2 1 2 4 3 1 UVW 2 2 4 3 50 60 200 1...
Page 286: ...282 4 2 2 3 Press e Flow 5 A B C D d1 d2...
Page 291: ...287 3 9 64 X 128 4 MODE SET 9 7 MODE 1 SET 8 3 EEprom SET 6 SET MODE...
Page 292: ...288 3 1 9 3 2 1 2 3 2 1 MODE SET MODE 8 2 2 5 5 5 2 2 9...
Page 294: ...290 3 2 2 10 SET 10 15 12 11...
Page 296: ...292 12 12 12 GO SB...
Page 297: ...293 4 4 1 Link 8 4 2 4 2 1 Link 2 Link 5...
Page 300: ...296 4 3 1 2 1 4 3 1 3 SET MODE LA RC FN MS FS FL AC AE O1 1 O2 2 4 4 ET 6 6 9 FL...
Page 326: ...322 BL 10 6 24 24 30 LP 180 200 HP OT TE 100 C 85 C OB BT 120 C 100 C OC 10 6 OF 10 6 30...
Page 327: ...323 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 494: ...490 1 492 2 495 3 496 4 498 5 499 6 4 20 mA 500 7 501 8 502 9 503 10 506 11 506 12 508 13 523...
Page 495: ...491 IEC 364 inverter...
Page 496: ...492 1 Inverter inverter inverter 6 inverter MCE 22 P MCE 15 P MCE 11 P 1 1 1...
Page 499: ...495 2 2 2 1 inverter inverter 2 2 1 1 inverter 3 1 LN 2 inverter 2 PVC 3 inverter 1 3 inverter...
Page 502: ...498 4 2 2 3 Press Flow 5 A B C D d1 d2...
Page 507: ...503 3 9 oled 64 X 128 4 MODE SET 9 inverter 7 MODE 1 SET 8 3 EEprom SET 6 SET MODE...
Page 508: ...504 3 1 9 3 2 1 2 3 2 1 MODE SET Setpoint MODE 9 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 9...
Page 512: ...508 12 12 12 GO SB FAULT...
Page 543: ...539 8 8 1 PMW 4 2 8 2 inverter 8 3 8 3 inverter SET EEPROM FLASH setpoint...
Page 599: ...595...