ENGLISH
97
6.3
Setpoint menu
From the main menu, press and hold MODE and SET simultaneously until “SP” appears on display (or use the b or – in the
selection menu).
B and – enable respectively to increase and decrease the system pressurisation value.
To exit the current menu and return to the main menu, press SET.
This menu enables the user to set the system operating pressure.
The pressure range depends on the sensor used (see PR: Pressure sensor section 6.5.7) and varies as shown in Table 16. System
pressure can be displayed in [bar] or [psi] depending on measurement system used.
Regulation pressure values
Type of sensor used
Regulation pressure [bar]
Regulation pressure [psi]
16 bar
1,0 - 15,2
14 - 220
25 bar
1,0 - 23,7
14 - 344
40 bar
1,0 - 38,0
14 - 551
Table 16: Maximum regulation pressure values
6.3.1
SP: Setting the setpoint pressure
Pressure to apply to the system if the auxiliary pressure regulation functions are not active.
6.3.2
Auxiliary pressure settings
The inverter can vary the set point pressure according to the status of the inputs; up to 4 auxiliary pressure values can be set for a
total of 5 different set points. For the electrical connections, refer to paragraph 2.2.4.2, and for software settings, refer to paragraph
6.6.13.3.
If there are several auxiliary pressure functions active, associated with several inputs, the inverter applies the lowest
pressure of all those activated.
The auxiliary set points are disabled if the flow sensor is not used (FI=0) and when FZ is used in minimum frequency
mode (FZ ≠ 0).
6.3.2.1
P1: Auxiliary pressure 1 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 1.
6.3.2.2
P2: Auxiliary pressure 2 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 2.
6.3.2.3
P3: Auxiliary pressure 3 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 3.
6.3.2.4
P4: Auxiliary pressure 4 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 4.
The pump restart pressure depends both on the set pressure (SP, P1, P2, P3, P4) and RP.
RP expresses the reduction in pressure, with respect to "SP" (or an auxiliary pressure if activated), which generates
pump start-up
.
Example: SP = 3,0 [bar]; RP = 0,5 [bar]; no auxiliary pressure function active:
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...