ENGLISH
93
5.1.3
Setting the direction of rotation
Once the pump has started up, the user must ensure that the direction of rotation is correct (the direction is usually indicated by
an arrow on the pump casing). To start up the motor and check the direction of rotation, simply switch on a utility.
From the same menu as RC (MODE SET – "Installer menu") press MODE and scroll through the menus to RT. In these
conditions, b and – enable the user to invert the direction of motor rotation. The function is also enabled when the motor
is running.
If it is not possible to see the direction of motor rotation, proceed as follows:
Method to check rotation frequency
-
Access parameter RT as described above.
-
Turn on a utility and observe the frequency that is shown on the status bar at the bottom of the utility control page, to ensure that the
operating frequency is less than the rated frequency of the pump FN.
-
Without changing collection, modify parameter RT by means of b or – and check frequency FR again.
-
The correct RT parameter is that which requires, compared to collection, a lower frequency FR.
5.1.4
Setting the setpoint pressure
From the main menu, press and hold MODE and SET simultaneously until “SP” appears on display. In these conditions, buttons
“+” and “–“ enable respectively increase and decrease of the required pressure value.
The regulation range depends on the sensor used.
Press SET to return to the main page.
5.1.5
System with flow sensor
From the installer menu (the same used to set RC, RT and FN) scroll through the parameters using MODE to reach FI.
To work with the flow sensor set FI to 1. Use MODE to scroll through to the next parameter FD (pipeline diameter) and set the
diameter in inches of the pipe mounting the flow sensor.
Press SET to return to the main page.
5.1.6
System without flow sensor
From the installer menu (the same used to set RC RT and FN) scroll through the parameters using MODE to display FI. To
work without the flow sensor, set FI to 0 (default value).
Without the flow sensor, there are two flow reading modes, both settable on parameter FZ in the installer menu.
•
Automatic (self-learning): the system automatically identifies the flow and automatically adjusts settings accordingly.
To set this operating mode, set FZ to 0.
•
Minimum frequency mode: in this mode the shutdown frequency is set at zero flow. To use this mode, move to
parameter FZ, close delivery gradually (to avoid generating overpressure) and read the frequency value at which the
inverter is stabilised. Set FZ at this value + 2.
Example: if the inverter stabilises at 35Hz, set FZ at 37.
An excessively low value of FZ can cause irreparable damage to the pumps, because in this case the inverter would
never stop the pumps.
An excessively high value of FZ can cause pump shutdown even when there is flow present
.
Modifications to the pressure set point thus also requires adjustment of the FZ value.
On multiple inverter systems without the flow sensor, the only admissible method of setting the FZ value is in minimum
frequency mode.
The auxiliary set points are disabled if the flow sensor is not used (FI=0) and when FZ is used in minimum frequency
mode (FZ ≠ 0).
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...