ENGLISH
89
4.2.2.3
Pressure sensors
The pressure sensor/s must be inserted on the delivery manifold. There must be more than one pressure sensor if ratiometric (0-5V),
and only one if current (4-20mA). In the case of multiple sensors, the pressure reading will be the average of all those fitted. To use
multiple ratiometric pressure sensors (0-5V) simple insert the connectors in the relative inputs, without the need for setting any
parameters. The number of ratiometric pressure sensors (0-5V) installed can vary as required, from one to the maximum number of
inverters present. In the case of 4-20mA pressure sensors, only one may be installed; refer to paragraph 2.2.3.1.
4.2.3
Connection and setting of the optical coupling inputs
The inputs of the inverter are photocoupled (see para. 2.2.4 and 6.6.13); this means that galvanic separation of the inputs from the
inverter is guaranteed, to enable the functions for the float, auxiliary pressure, system disable, and low pressure on intake. The
functions are indicated respectively by the messages F1, Paux, F3, F4. If activated, the Paux function boosts the pressure in the
system to the set pressure, see par. 6.6.13.3. The functions F1, F3, F4 stop the pump for 3 different reasons, see par. 6.6.13.2,
6.6.13.4, 6.6.13.5.
When using a multiple inverter system, the inputs must be used with the following settings:
•
the contacts that perform the auxiliary pressures must be connected in parallel on all the inverters so that the same signal
arrives on all the inverters.
•
the contacts that perform the functions F1, F3, F4 may be connected either with independent contacts for each inverter, or
with only one contact connected in parallel on all the inverters (the function is activated only on the inverter at which the
command arrives).
The parameters for setting the inputs I1, I2, I3, I4 are part of the sensitive parameters, so setting one of these on any inverter means
that they are automatically aligned on all the inverters. As the setting of the inputs not only selects the function, but also the type of
polarity of the contact, the function associated with the same type of contact will perforce be found on all the inverters. For the above
reason, when using independent contacts for each inverter (as is possible for the functions F1, F3, F4), these must all have the same
logic for the various inputs with the same name; that is, for the same input, either normally open contacts are used for all the
inverters or normally closed ones.
4.3
Multi inverter operating parameters
The parameters displayed on the menu, in a multi-inverter configuration, can be classed as follows:
•
Read-only parameters
•
Local parameters
•
Multi inverter system configuration parameters
in turn divided as
o
Sensitive parameters
o
Parameters with optional alignment
4.3.1
Parameters related to multi inverter systems
4.3.1.1
Local parameters
These are parameters that can differ from one inverter to another and in some cases actually need to be different. For these
parameters, automatic alignment of inverter configuration is not admitted. In the case of manual assignment of addresses, these
must all be different.
List of local parameters for inverters:
CT
Contrast
FP
Test frequency in manual mode
RT
Direction of rotation
AD
Address
IC
Reserve configuration
RF
Fault and warning reset
4.3.1.2
Sensitive parameters
These are parameters that must be aligned on the entire series for control purposes.
List of sensitive parameters:
SP
Setpoint pressure
P1
Input 1 auxiliary pressure
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...