ENGLISH
88
4.2.1
Communication cable (Link)
The inverters communicate with one another and propagate the flow and pressure signals (only if a ratiometric pressure sensor is
used) via the specific connection cable.
The cable can be connected to any one of the two connectors marked “Link”, see Figure 16.
Figure 16: Link connection
WARNING: only use cables supplied with the inverter or which are considered as inverter accessories (it is not a standard cable
available on the market).
4.2.2
Sensors
To enable operation, a pressure set requires at least one pressure sensor and optionally one or more flow sensors.
The pressure sensors are ratiometric 0-5V versions, and in this case one can be connected per inverter, or 4-20mA current sensors,
in which case only one can be connected.
The flow sensors are always optional and from 0 to 1 can be connected per inverter.
4.2.2.1
Flow sensors
The flow sensor must be inserted on the delivery manifold on which all pumps are connected, and the electrical connection can be
made on any of the inverters.
The flow sensors can be connected in two ways:
•
one sensor only
•
the same number of sensors as inverters
The setting is entered on parameter FI.
Multiple sensors are useful when a specific flow rate is required on each pump, and enhance protection against dry running
operation. To use multiple flow sensors, parameter Fl must be set to multiple sensors and each flow sensor must be connected to
the inverter that controls the pump delivery where the sensor is located.
4.2.2.2
Sets with one pressure sensor only
Pressure sets can also be set up without a flow sensor. In this case the pump shutdown frequency
FZ
must be set as described in
6.5.9.1.
The dry running protection continues to function without the use of a flow sensor.
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...