![DAB PUMPS PWM 201 Instruction For Installation And Maintenance Download Page 77](http://html1.mh-extra.com/html/dab-pumps/pwm-201/pwm-201_instruction-for-installation-and-maintenance_495533077.webp)
ENGLISH
75
Cable section in mm²
10 m
20 m
30 m
40 m
50 m
60 m
70 m
80 m
90 m
100 m
120 m
140 m
160 m
180 m
200 m
4 A
1,5
1,5
1,5
1,5
1,5
1,5
1,5
1,5
2,5
2,5
2,5
2,5
4
4
4
8 A
1,5
1,5
1,5
1,5
2,5
2,5
2,5
4
4
4
6
6
6
10
10
12 A
1,5
1,5
2,5
2,5
4
4
4
6
6
6
10
10
10
10
16
16 A
2,5
2,5
2,5
4
4
6
6
6
10
10
10
10
16
16
16
20 A
2,5
2,5
4
4
6
6
10
10
10
10
16
16
16
16
16
24 A
4
4
4
6
6
10
10
10
10
16
16
16
16
16
16
28 A
6
6
6
6
10
10
10
10
16
16
16
16
16
16
16
32 A
6
6
6
6
10
10
10
16
16
16
16
16
16
16
16
36 A
10
10
10
10
10
10
16
16
16
16
16
16
16
16
16
40 A
10
10
10
10
10
16
16
16
16
16
16
16
16
16
16
44 A
10
10
10
10
10
16
16
16
16
16
16
16
16
16
16
48 A
10
10
10
10
16
16
16
16
16
16
16
16
16
16
16
52 A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
56 A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
60 A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Table applicable to cables in PVC with 4 wires (3 earth)
Table 4: Section of 4-wire cable (3 earth)
As regards the section of the earthing cable, refer to current standards.
2.2.2
Hydraulic connections
The inverter is connected to the hydraulic section by means of pressure and flow sensors. The pressure sensor is always required,
while the flow sensor is optional if operating in stand alone mode, and is compulsory when creating multi inverter systems.
Both are mounted on pump delivery and connected by means of the relative cables to the respective inputs on the inverter board.
Always fit a check valve on pump suction and an expansion vessel on pump delivery.
In all circuits subject to the risk of water hammer (for example irrigation systems with flow rate interrupted suddenly by solenoid
valves), fit a further check valve downline of the pump and mount the sensors and expansion vessel between the pump and valve.
The hydraulic connection between the pump and sensors must not have branched sections.
Pipelines must be sized according to the type of electric pump installed.
Excessively deformable systems may generate oscillations; if this occurs, the user may solve the problem by adjusting control
parameters “GP” and “GI” (see sections 6.6.4 and 6.6.5)
The inverter makes the system work at constant pressure. This setting is best exploited if the hydraulic system
downline of the system is suitably sized. Systems with excessively small pipelines can cause pressure drops for
which the equipment is unable to compensate; the result is constant pressure on the sensors but not on the utility
.
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...