Pressure sensor settings
PR value
Type of sensor
Information
Full scale [bar]
Full scale [psi]
0
6.6 Ratiometric (0-5V)
501 R 16 bar
16
232
1
6.7 Ratiometric (0-5V)
501 R 25 bar
25
363
2
6.8 Ratiometric (0-5V)
501 R 40 bar
40
580
3
4-20 mA
4/20 mA 16 bar
16
232
4
4-20 mA
4/20 mA 25 bar
25
363
5
4-20 mA
4/20 mA 40 bar
40
580
Table 17: Pressure sensor settings
The setting of the pressure sensor does not depend on the pressure to be obtained, but on the sensor to be fitted on the
system
.
6.5.8
MS: Measurement system
This sets the measurement unit system; either international or Imperial The values displayed are shown in Table 18.
Units of measurement displayed
Value
International unit of measurement
Imperial unit of measurement
Restart
bar
Temperature
°C
°F
Flow
l / min
gal / min
Table 18: Unit of measurement system
6.5.9
FI: Flow sensor setting
This enables setting of operation as described in Table 19.
Flow sensor setting
Value
Type of use
Notes
0
without flow sensor
default
1
single specific flow sensor (F3.00)
2
multiple specific flow sensor (F3.00)
3
manual setting for a general single pulse flow sensor
4
manual setting for a general multiple pulse flow sensor
Table 19: Flow sensor settings
In the case of multi inverter operation, use of multiple sensors can be specified.
6.5.9.1
Operation without flow sensor
When the setting without flow sensor is selected, the FK and FD settings are automatically disabled as these parameters are not
necessary. The parameter disabled message is indicated by an icon showing a padlock.
It is possible to choose between 2 different operating modes without flow sensor by means of the parameter FZ (see par. 6.5.12):
Minimum frequency mode: this mode allows you to set the frequency (FZ) below which it is considered that there is zero flow. In this
mode the electropump stops when its rotating frequency falls below FZ for a time of T2 (see par. 6.6.3).
IMPORTANT: An incorrect setting of FZ causes:
1.
If FZ is too high, the electropump could cut out even in the presence of flow and then start again as soon as the pressure
falls below the restarting pressure (see 6.5.5). So there could be repeated episodes of switching on and off, even quite
close together.
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...