background image

D+H UK

D+H UK (DH Mechatronic UK Ltd), Unit 10, Lawnhurst Trading Estate, Cheadle Heath, Stockport, Cheshire SK3 0SD                             Page 1 of 2

www.dh-partner.co.uk 

+44 (0)161 491 4840

  |  

Registered in England 02670985

 | 

VAT No. 611329279   

 

                           V3

RZN 4503-T Troubleshooting Guide

L

A

Z

N-

E

b

RM

K

-

T

RT

Z

A

S

RT 45

Breakglass

2

8

3

1

6

4

7

10kΩ

3

2

LT

SD-O 371 

Smoke detector

LT 84-U

Wall Switch

10kΩ

5

COM

10kΩ

1k

Ω

Fire alarm 

interface

Normally

open, volt 

free contact.

-

R

OR

10k

Ω

 resistor - 

orange

 band 

(from RM “R” & “-” in panel).

1k

Ω

 resistor - 

red

 band (from 

keyring bag).

10k

Ω

 resistor - 

orange

 band 

(from RT “T” & “-” in panel).

EM 47 K

Orange

Black

Black

Vent

24v D+H 

Mechatronic 

drive.

Orange

(High Speed)

White

Brown

End of line terminal resistor

(from MOT E, a & b in panel).

Connection point 

(local to vent - by 

others)

Display fault indications
Battery fault

:

•  Incorrect connection of the battery.

Earth fault

:

•  Issue with incoming power supply 230 v earth.

Detector Line fault

 - 

Solid

:

• 

Indicates an issue between the control panel and control elements (fire alarm interface, smoke detector or 

breakglass).

•  Each control element requires a single 10

kΩ end of line resistor. See above detail.

• 

If no fire alarm interface or smoke detector in system, leave 10kΩ

 end of line resistor in RM terminals “R” & “-”. 

If no RT 45 breakglass, leave 10k

Ω

 resistor in RT terminals “T” & “-”.

Detector Line fault

 - 

Flashing:

•  Indicates line deactivated, press the 1/0 Reset button at top of panel to reactivate.

Drive Group fault

:

•  Issue between the control panel and the drive(s). Ensure EM 47 K end of line terminal resistor is connected as 

shown above.

•  Check 2.5 Amp fuse has not blown.

Terminate all 

other coloured 

cables in 

connection 

point.

a

MOT

RZN 4503-T / RT 45 breakglass display indications

+          +

Solid green

 - System healthy, no faults.

+          +

Solid green + flashing yellow

 - System healthy, no fault. Inbuilt 

service timer expired. Contact our service department.

+          +

Flashing yellow

 - System fault. See panel indications below.

+          +

Solid green + solid red

 - System h in fire. 

+          +

Flashing solid red

 - System in fault + fire.

Alarm open

Reset close

Reviews: