CyberPower PR2600LCDRT2U User Manual Download Page 1

 

IMPORTANT SAFETY WARNINGS 

INSTALLING YOUR UPS SYSTEM 

BATTERY REPLACEMENT 

LCD STATUS DEFINITION 

BASIC OPERATION 

 
 
 
 

Smart App Sinewave Series 

PR2600LCDRT2U/PR3000LCDRT2U 

User’s Manual 

 
 

K01-0000072-02 

 

 

This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read 
and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, 
or operate. 

CAUTION!

    The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an 

outlet that is not grounded.    If you need to de-energize this equipment, turn off and unplug the UPS.   

CAUTION!

   

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!

    CyberPower

 

Systems does not sell products for life support or 

medical  applications.  DO  NOT  use in  any  circumstance  that  would affect  operation  or  safety  of  any life  support  equipment,  with  any medical 
applications, or patient care. 

CAUTION!

    The battery can energize hazardous live parts inside even when the AC input power is disconnected. 

CAUTION!   

For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily accessible. 

CAUTION!

    To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area,  free  of  conductive 

contaminants. (Please see specifications for acceptable temperature and humidity range). 

CAUTION!

    To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no serviceable parts inside, 

except for the battery. 

CAUTION!

    To  avoid  electrical  shock,  turn  off  the  unit  and  unplug  it  from  the  AC  power  source  before  servicing  the  battery  or  installing  a 

computer component. 

CAUTION!

   

DO NOT USE WITH OR NEAR AQUARIUMS!

    To reduce the risk of fire, do not use with or near aquariums.    Condensation from 

the aquarium can come in contact with metal electrical contacts and cause the machine to short out. 

CAUTION!   

For model 

PR2600LCDRT2U

 and 

PR3000LCDRT2U 

–For use in a computer room as defined in the Standard for the Protection of 

Electronic Computer/Data Processing Equipment, ANSI/NFPA 75. 
 

   

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following. 
(1) UPS Unit; (1) User's Manual for UPS; (2) Rack mount Brackets; (2) Stands; (2) Skids; (1) Telephone Cable (black); (1) Emergency Power Off 
Cable  (gray);  (1)  PowerPanel

®

  Business  Edition  Software  CD;  (2)  Serial  Interface  Cable  (DB-9);  (1)  USB  A+B  type  cable;  (1)  Warranty 

Registration Card. 
 

OVERVIEW 

The

 PR2600LCDRT2U/PR3000LCDRT2U 

provides battery backup, automatic voltage regulation (AVR), and 

optimal performance of computers and other network equipment by ensuring consistent sinewave power. The 

PR2600LCDRT2U/PR3000LCDRT2U 

features 1874 Joules of surge protection, and provides battery backup 

during  power  outages.  The

  PR2600LCDRT2U/PR3000LCDRT2U

  ensures  consistent  power  to  your 

computer  system  and  its  included  software  will  automatically  save  your  open  files  and  shutdown  your 
computer system during a utility power loss. 

 

AUTOMATIC VOLTAGE REGULATOR(AVR)

 

The 

PR2600LCDRT2U/PR3000LCDRT2U

 stabilizes inconsistent utility power. The incoming utility power may be damaging to important data 

and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic Voltage Regulator 
automatically increases low or decreases high voltage to a consistent, computer safe 110v/120v. The unit powerful sealed lead-acid batteries will 
provide power only if the incoming voltage drops below 80v or increases above 150v. 
 

SYSTEM BLOCK DIAGRAM 

 
 
 
 
 
 
 
 
 
 
 

 
 
HARDWARE INSTALLATION GUIDE 

1. Battery charge loss may occur during shipping and storage. For the first time the UPS is used, it’s strongly recommended to charge batteries 
for at least eight hours is recommended to ensure that the batteries’ maximum charge capacity. To recharge the batteries, simply make the UPS 
plugs into an AC outlet.   
2. When you use the included software, connect either the serial or the USB cable between the computer and the corresponding port on the UPS. 
Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously. The computer with the PowerPanel

®

 Business 

Edition  S/W  connects  to  the  USB  port  or  the  Serial  port  on  the  UPS.  It  can  control  the  operating  schedule,  battery  test,  outlet,  etc.  and  get 
information on the UPS status. However, other computers with PowerPanel

®

 Business Edition S/W can only get UPS status information via a 

LAN connection. 
3. With the UPS off and unplugged, connect your computer, monitor, and any externally powered data storage device (Hard drive, Tape drive, etc.) 
into the outlets.    DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The 
power demands of these devices will overload and possibly damage the unit.   
4. To protect a fax, telephone, modem line or network cable, connect the telephone or network cable from the wall jack outlet to the jack marked 
“IN” of the UPS. Then, connect a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem, computer, telephone, 
fax machine, or network device.   
5. Press the power switch to turn the UPS on. The Power-On indicator light will illuminate. If an overload is detected, an audible alarm will sound 
and the UPS will emit one long beep. In order to reset it, turn the unit off and unplug some equipment from outlets. Make sure your equipment 
carry a load current within the unit’s safe range, (refer to the technical specifications), and then turn the unit on. 
6. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will be automatically charging, even 
when the unit is switched off! 
7. To always maintain an optimal battery charge, leave the UPS plugged into an AC outlet at all times.   
8. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the batteries fully charged. Recharge 
the batteries every three months or so, to ensure good battery capacity and long battery life; further, this might also prevent damage to the unit 
from an unlikely battery leakage. 
9. The unit provides one Primary Serial Port (I), Secondary Ser city and long battery life; further, this might also prevent damage to the unit from 
an unlikely battery leakage.ial Port (II), and one USB port, (paired with the Primary Serial Port), to allow connection and communication between 
the unit and any attached computers. The Primary Serial Port (I) as well as its paired USB port allow for bi-directional communication among the 
UPS  and  the  primary  connected  computer  running  the  PowerPanel

®

  Business  Edition  S/W  provided.  The  UPS  can  control  the  computer’s 

shutdown in case of an emergency, and at the same time, the computer can monitor the UPS and alter its various programmable parameters. On 
the  other  hand,  secondary  Serial  Port  II,  only  allows  the  UPS  to  initiate  the  connected  computer’s  graceful  auto-shutdown  in  case  of  an 
emergency.

 

10. EPO (Emergency Power Off) Port: 
Use the provided gray cable to connect to a special EPO contact switch.    Follow the appropriate circuit diagram 
below to wire the cable to your EPO configuration. The EPO remote switch is a switch installed in an outside 
area,  connected  to  the  unit  via  an  ordinary  RJ-11  phone  line.  In  case  of  an  emergency,  it  can  be  used  to 
immediately cut-off power from the UPS unit. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

FRONT / REAR PANEL DESCRIPTION

 

1. Power Switch

 

Master On/Off switch for equipment connected to the UPS.   

2. Power on Indicator 

Indicate that the AC utility input power’s condition is normal and that the 
UPS outlets are providing power, free of surges and spikes. 

3. Multifunction LCD Readout

 

An LCD that shows various UPS information using icons and messages. 

4

.

 

LCD Readout Toggle Button 

Used to select among a variety of information the LCD can display. 

5

Battery Backup & Surge Protected Outlets 

This  unit  provides  a  total  of  nine  outlets  with  battery  backup  and  surge 
protection.  They  ensure  that  connected  equipment  will  keep  an 
uninterrupted operation over a period of time, during a power failure. 

Critical /Non-critical   

It is possible to program the unit in a way so that the outle block marked as 
“non-Critical”,  (5  ports),  will  stop  the  provision  of  power  to  connected 
equipment  after  a  certain  period  of  time,  thus  making  more  runtime 
available for the equipment connected on the outlets marked as “Critical”, 
(4 ports). In other words, the user can establish runtime priority for certain 
connected  equipment,  maximizing  its  “availability”  during  a  prolonged 
power outage.   

6

.

 Input Power Cord 

Heavy-duty, extra long power cord. 

7

Output Circuit Breaker                                                                           

 

The circuit breaker serves to provide output overload and fault protection. 

8

.

 Input Circuit Breaker 

The  circuit  breaker  serves  to  provide  input  overload  and  fault 
protection.                                                                                                           

9. USB port to PC                                                                                               

This  is  a  connectivity  port  allowing  communication  and  control 
among the UPS and the connected computer. You should install 
on  your  computer  the  PowerPanel®  Business  Edition  software 
appropriate to the operating system you are using. 

10. Surge Protected Communication Ports - RJ11/RJ45 

These  ports  are  being  used  to  protect  from  various 
surge-conditions the standard RJ-45/RJ-11 based, (ADSL, LAN, 
Phone/Modem-Lines), cabling systems. 
 

 

Contact  your  dealer,  or  email  [email protected].  Refer  to  replacement  battery  pack  number 

RBP852

  for  the 

PR2600LCDRT2U/ 

PR3000LCDRT2U.

 

For model

 PR2600LCDRT2U/ PR3000LCDRT2U 

can support model 

BP48V75ART2U

 for external battery pack.

 

Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel 
knowledgeable of batteries and their precautions

. Servicing the battery should only be performed by trained personnel.

 

Replacement of batteries located in an 

OPERATOR ACCESS AREA.

 

CAUTION!

    When  replacing  batteries,  replace  with  the  same  number  of  the  following  battery:  HR9-12(BB)  for 

PR2600LCDRT2U/ 

PR3000LCDRT2U.

 

CAUTION!   

Risk of Energy Hazard, 12 V, maximum 9  Ampere-hour battery (HR9-12). Before replacing batteries, remove conductive jewelry 

such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns. 

CAUTION!

    Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with  30  amperes  maximum  branch  circuit  overcurrent  protection  in 

accordance with the National Electric Code, ANSI/NFPA 70. 

CAUTION!

    A MAXIMUM of 

five

 additional battery packs can be added to models 

PR2600LCDRT2U/PR3000LCDRT2U.

 

CAUTION!

    Use only the specified CyberPower replacement battery, or battery pack. See your dealer for details.

   

CAUTION!   

The  battery  may  present  a  risk  of  electrical  shock.  Do  not  dispose  of  batteries  in  a  fire,  as  they  may  explode.  Follow  all  local 

ordinances regarding proper disposal of batteries. 

CAUTION!

    Do not open, or mutilate the batteries. Released electrolytes may be toxic, and can be harmful to skin and eyes. 

CAUTION!   

A battery may present a high risk of short circuit current and electrical shock.   

 

Take the following precautions before replacing the battery: 

1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. Do not lay tools or metal parts on top of battery or any terminals. 
4. Wear rubber gloves and boots. 
5. Determine if the battery is inadvertently grounded.    If inadvertently grounded, remove  source of ground. 

CONTACT WITH A GROUNDED 

BATTERY CAN RESULT IN ELECTRICAL SHOCK! 

The likelihood of such shock will be reduced if such grounds are removed during installation 

and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit) 
 

BATTERY REPLACMENT PROCEDURE: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

INPUT voltage meter: 

This meter measures the AC voltage from the wall outlet. The INPUT voltage readout is used to identify the input voltage 

information. This can be used as a diagnostic tool to identify poor-quality input power.    Units are listed in V (Volts). When the UPS connect to 
any  equipment,  the  AVR  can  provide  a  stable  110/120V  power  output.    In  the  event  of  a  complete  loss  of  power,  severe  brownout,  or  over 
voltage, the UPS relies on its internal battery to back up to supply a consistent 110/120V output.

 

OUTPUT  voltage  meter:

  The  Output  Voltage  screen  measures,  in  real  time,  the  AC  voltage  that  the  UPS  is  providing  to  your  connected 

equipment via the UPS outlets.    Units are listed in V (Volts). 

ESTIMATE  RUN  TIME:

  The  Estimated  Runtime  Screen  displays  how  many  minutes  of  runtime  can  be  expected  of  the  UPS  if  it  were  to 

experience a power outage. When runtime becomes shorted, the battery capacity will decrease; (battery capacity bar indicator will be falling.) 
Note: The number displayed may be less than actual runtimes for low loads. 

NORMAL icon:

 This icon illuminates when the UPS is working under normal conditions. 

BATTERY icon:

 When there is a severe brownout or blackout, this icon will appear followed by an alarm, (two short beeps), indicating that the 

UPS is now working using its internal batteries. Once the batteries are run out of power, (over a period of time), a constant alarm will sound. If this 
happens and main power has not been restored, it is recommended that you save your files and turn off your equipment manually as soon as 
possible.     

Automatic Voltage Regulation (AVR) icon

: This icon will appear when the unit is automatically regulating low or high AC input line voltage 

conditions, without resulting to the use of battery power. 

SILENT MODE icon:

 This icon appearing indicates that the buzzer will not be beeping while in battery operating mode. During Silent mode, the 

unit’s alarm does not sound until the Battery Capacity falls to < 20%. 

OVER  LOAD  icon:

  This icon  will  appear  followed  by  an  alarm,  indicating that  an  overload  condition  has  been  reached. To  recover  from  the 

overload condition, start unplugging your equipment from the UPS outlets until the icon disappears and the alarm stops. 

FAULT icon:

 

When activated indicates a system fault error. Please refer to the troubleshooting table for possible causes and solutions.     

BATT.

 

CAPACITY meter: 

BATT. CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of battery capacity. 

LOAD CAPACITY:

 Load CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of load capacity. 

11. Site Wire Fault Indicator 

This LED will illuminate to warn the user that a wiring problem exists 
within  the  AC  receptacle,  such  as  a  bad  ground,  missing  ground  or 
reversed wiring. If illuminated, disconnect all equipment and contact 
an electrician to ensure outlet is properly wired. 

12. Serial Port I (Primary) 

Serial  port  I  allow  for  bi-directional  communication  among  the  UPS 
and the computer. The UPS can control the computer’s shutdown in 
case  of  an  emergency,  and  at  the  same  time,  the  computer  can 
monitor the UPS and alter its various programmable parameters.   

13. Serial Port II (Secondary)   

Serial  Port  II  allows  the  UPS  to  initiate  the  connected  computer’s 
graceful auto-shutdown in case of an emergency.

 

14. SNMP/HTTP Network slot 

Remove the cover panel to install optional SNMP, allowing your UPS 
be controlled and monitored via a network connection. 

15. EPO (Emergency Power Off) Port: 

Allow for an emergency UPS Power-Off from a remote location. 

16. Ground Stud   

Use the Ground Stud to ground the UPS. 

17. Extended Runtime (XL) Battery Pack Connector 

Provide a connection for additional CyberPower XL Battery Packs. 

 

 

Dry connect is controlled by the PowerPanel

® 

Software, please go to 

www.cyberpowersystems.com

 

for free download. 
*

NOTE:

 Both USB and Serial cannot be used 

simultaneously. 

The primary computer 
with PowerPanel

® 

Business Edition 
software connected to 
the UPS with either a 
serial cable or a USB 
cable. 

The equipment can 
read information 
via dry contact. 

1.Remove the six retaining screws, 
and remove the front panel. 

2. Remove the one retaining screws of 
the cable protection cover then remove 
the cover. 

3. Remove the cable protection cover. 

4. Disconnect the black and red cable

 

5. Remove the three retaining screws. 

6.  Pull  out  the  old  battery  pack  and  replace. 
Reassemble the retaining screws, covers, black and 
red  cable,  and  front  panel  in  the  reverse  sequence 
of the above steps. Recharge the unit for 4-8 hours 
to ensure maximum UPS battery runtime. 

1

2

4

5

6

3