background image

 

 

 

       

 

 

 

 

Professional Tower UPS 

PP1500/PP2200 

User Manual 

 

SAFETY WARNINGS   

 

(SAVE THESE INSTRUCTIONS) 

 

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. 
Read this manual thoroughly before attempting to unpack, install, or operate your UPS. 
This equipment can be operated by any individuals with no previous training. 
The socket-outlet shall be installed near the equipment and easily accessible. 
During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not 
exceed 3.5mA. 
Attention,  hazardous  through electric  shock. Also  with  disconnection  of  this  unit  from  the  mains,  hazardous  voltage  still  may  be  accessible 
through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the 
battery when maintenance or service work inside the UPS is necessary. 
Do not dispose of batteries in a fire, the battery may explode. 
Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes. 

 

 

INSTALLING YOUR UPS SYSTEM   

 

UNPACKING 

 
Inspect the UPS upon receipt. The box should contain the following: 

UPS Unit x1; PowerPanel Business Edition Software Disk x1; Serial Interface Cable (DB-9) x1; USB Device Cable x1;Telephone Cable x1; 

 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 

 

1.  Insure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS unit’s rated capacity (1500VA/1000W for 

PP1500, 2200VA/1500W for PP2200). If rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to 
shut down or the circuit breaker to trip. 

2.  If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into VA by doing 

the  calculations  below.  Note:  The  below  equation  only  calculates  the  maximum  amount  of  VA  that  the  equipment  can  use,  not  what  is 
typically used by the equipment at any one time. Users should expect usage requirements to be approximately 60% of below value. 

 

TO ESTIMATE POWER REQUIREMENTS 

 

1.              Watts (W) x 2.0 =                    VA or                Amps (A) x 120 =              VA 
 
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual requirements. There are many factors that can 

affect the amount of power that your computer system will require. The total load that you will be placing on the battery-powered outlets 
should not exceed 80% of the unit’s capacity. 

 

HARDWARE INSTALLATION GUIDE 

 

1.  Connect the equipment to your UPS outlets. Items such as copiers, laser printers, vacuums, 

space heaters, paper shredders, or other large electrical devices should not be connected to 
the UPS. Please assure that the total loads of your equipments must be less than the 
maximum total power load of your UPS. 

 
2.  Connect your UPS power cord into a two-pole, three-wire grounding receptacle only. Please 

avoid using extension cords and adapter plugs. (To maintain optimal battery charge, leave 
the UPS plugged in at all times.) 

 
 
3.  Press the UPS power button to turn it on. The “Power On” indicator will be illuminated in 

“Green”. 

 
4.  Install your optional software and accessories. To use the software, simply connect the enclosed serial interface cable to the serial port on 

the UPS and an open serial port on the computer. 

 
 

BASIC OPERATION 

 

 
FRONT PANEL DESCRIPTION 

 

 Power Switch 

 
Press the ON/OFF button to turn the UPS on or off. 
 
 

 

 Test Switch 

This UPS performs a self-test automatically when power is on. If the UPS passes the test, it 
returns to on-line operation. If the UPS fails the self-test, please recharge the battery for 4 
hours and perform another self-test. If it fails after recharging the battery, please replace the 
battery.   
                                 

   
                                                     

 Battery Indicators 

 
These  indicators  show  a  visual  indication  of  the  battery  charge.  If  battery  capacity  is  under  20%,  no  indicator  LED  will 
illuminate and the UPS starts beeping. 
 
 
 

 Load Level Indicators 

 
These  LED  indicators  show  a  visual  depiction  of  the  UPS  load.  The  load  indicator  LED  will  turn  orange  if  the  load  is 
between 80 and 100%. If the load is under 20%, no indicator LED will illuminate. 
 
 
 
 

 Wiring Fault Indicator 

This LED indicator will illuminate to warn the user that a wiring problem exits with the AC outlet, such as bad ground, miss 
ground or reversed wiring. If this is illuminated, the user is advised to disconnect all electrical equipment from the outlet and 
have an electrician check the outlet to insure proper wiring. 
 

 Using Battery Indicator 

 
This illuminates during utility failure, indicating that the battery is supplying power to the battery-power supplied outlets. 
 
 

 

 AVR Indicator 

This LED indicates that the UPS is operating in automatic voltage regulation mode. When the LED is illuminated continuously, 
it indicates input over-voltage and the UPS unit bucks the voltage. When the LED is flashed in rotation, it indicates that the 
UPS unit is boosting input voltage. 
 

 Power On Indicator 

 
This LED is illuminated when the utility condition is normal and the UPS outlets are providing “clean power”, free of surges and 
spikes. 
 

 
 
 
 
 
 
 

 
 
 

 

REAR PANEL DESCRIPTION 

 

 Backup Power for Critical Loads 

The UPS provides 2 battery powered, surge protected outlets for the most critical connected equipments 
and insures temporary uninterrupted operation of connected equipments during a power failure. 
NOTE: When the UPS is overloaded, the UPS will interrupt power supply to the other 6 battery 
outlets and leave these 2 outlets for critical loads uninterrupted. 

 

 Battery Backup and Surge Protection Outlets   

This  unit  provides  6  battery-powered,  surge-protected  and  AVR  outlets  for  connected  equipments  and 
insures uninterrupted operation of connected equipment during a power failure. 

 
 

 Circuit Breaker Reset for Overload Protection 

 

 

Re-settable circuit breakers provide optimal overload protection. 
 
 

 Communication Protection Ports 

 
Ethernet RJ-45 Network Protection Ports protect your Phone, Fax and Modem from surges over the Ethernet/Phone line. 
 
 
 
 

 Serial/ USB Ports 

 

The PP1500/PP2200 provides two serial and one USB ports to allow connection and communication between the UPS and two computers. 
This allows the simultaneous shutdown of two computer systems. These interfaces are also compatible with the UPS service provided by 
Windows 2000, Windows NT, Windows XP, Windows Server 2003

 
 
1. The Primary PC 

To  control  the  UPS  and  make  any  change  to  the  operation  of  the  UPS, 

please install the PowerPanel Business Editon in your primary computer and  
then connect it to the Serial Port I or USB port of the UPS. 
 
 
 
2. The Secondary PC 

The secondary computer with PowerPanel installed should be connected to 

the  serial  port  II.  This  PC  will  shutdown  following  the  user  settings  in 
PowerPanel Software when a power failure occurs but it is unable to exhibit any 
control over the UPS. 
 
 

When power failure occurs, one of the following shutdown sequences will be executed:  
 
1.  If the Primary and Secondary serial ports are both in use: the Primary computer will start to count down (user controlled delay) for shutdown 

(User Control delay can be set in the PowerPanel Business Edition Recommended time is 5 minutes). Once the Primary computer is shutdown, 
the UPS will signal the Secondary computer and initiate the Secondary to shutdown. The UPS default shutdown time is 2 minutes. Therefore, 
it is recommended that Secondary computer is set to shutdown within 1 minute in PowerPanel Software. 

2.  If  only  the  Secondary  serial  port  is  in  use:  the  Secondary  computer  will  shutdown  following  the  user  settings  in  PowerPanel  Software. 

However, the Secondary computer will not able to signal the UPS to shutdown. Therefore, the UPS  will only power off when it is in low 
battery. 

  

BATTERY REPLACEMENT AND STORAGE 

 
Contact your dealer or call the number in this manual for information on battery replacement.     
 
Read  and  follow  the 

IMPORTANT  SAFETY  INSTRUCTIONS  before  servicing  the  battery.    Service  the  battery  under  the  supervision  of 

personnel knowledgeable of batteries and their precautions. Keep unauthorized personnel away from batteries. 
 
CAUTION! 
Use only the specified type of battery. See your dealer for replacement batteries. 
CAUTION!  The  battery  may  present  the  risk  of  electrical  shock.  Do  not  dispose  of  batteries  in  a  fire,  as  it  may  explode.  Follow  all  local 
ordinances regarding proper disposal of batteries. 
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic. 
CAUTION!  A  battery  can  present  a high risk  of  short  circuit  current  and  electric  shock.  Take  the following  precautions  before replacing  the 
battery: 
1. Remove all watches, rings or other metal objects. 
2. Only use tools with insulated handles. 
3. DO NOT

 lay tools or other metal parts on top of battery or any battery terminals. 

4. Wear rubber gloves and boots. 
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. 

CONTACT WITH A GROUNDED 

BATTERY  CAN  RESULT  IN  ELECTRICAL  SHOCK!  The  likelihood  of  such  shock  will  be  reduced  if  such  grounds  are  removed  during 
installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit). 
 

BATTERY REPLACEMENT PROCEDURE: 

 
1. Turn off and unplug all connected equipments. 
2. Turn the UPS off and unplug it from the AC power source. 
3. Carefully turn the UPS upside down. Remove the 6 retaining screws and the 

cover. 

4. Disconnect the black and red wires from the battery set.   
5. Remove the battery protection cover and take out the battery set from the 

compartment. 

6. Slide a new battery pack into the unit. Assemble the battery protection cover, 

cable, screws in the reverse sequence of above steps. 

 
REMINDER
: Recharge the unit for 4 – 8 hours to ensure the UPS performs 
expected runtime 
 
STORAGE: 
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables connected to the UPS to avoid battery drain. To 
store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure 
battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of capacity. 
 

TROUBLE SHOOTING 

 

Problem 

Possible Cause 

Solution 

The UPS does not perform 
expected runtime. 

Batteries are not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

Battery is slightly worn out. 

Contact CyberPower Systems at [email protected]

The UPS will not turn on. 
 

The on/off switch is designed to 
prevent damage by rapidly 
turning it off and on. 

Turn the UPS off.   
Wait 10 seconds and then turn the UPS on.   

The unit is not connected to an 
AC outlet. 

The unit must be connected to a 110/120v 60Hz outlet.     

The battery is worn out. 

Contact CyberPower Systems at [email protected]

Mechanical problem. 

Contact CyberPower Systems at [email protected]

Outlets do not provide 
power to equipment 

Circuit breaker is tripped due to 
overload 

Turn  the  UPS  off  and  unplug  at  least  one  piece  of  equipment.  Wait  10 
seconds, reset the circuit breaker and then turn the UPS on. 

Batteries are discharged 

Allow the unit to recharge for at least 4 hours. 

Unit has been damaged by a 
surge or spike. 

Contact CyberPower Systems at [email protected]

PowerPanel Business Edition
is inactive (all icons are gray).

 

The serial cable is not 
connected. 

Connect the serial cable to the UPS unit and an open serial port on the back 
of the computer. You must use the cable that came with the unit. 

The serial cable is connected to 
the wrong port. 

Check  the  back  of  the  computer  for  an  additional  serial  port.    Move  the 
cable to this port. 

The unit is not providing battery 
power. 

Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the 
UPS back on. This should reset the unit. 

The serial cable is not the cable 
that was provided with the unit. 

You must use the cable that was included with the unit for the software and 
the unit to be able to communicate. 

 

 

 

(2) 

(1) 

(3) 

(4) 

 

User Manual x1

Please go to www.cyberpowersystems.com for free download PowerPanel Software.

K01-P1K50H0-01

BATTERY

CAPACITY

   LOAD

CAPACITY

Reviews: