CyberPower ENVIROSENSOR User Manual Download Page 1

Environment Sensor

ENVIROSENSOR

User’s Manual

Package Contents

Flat Head Screw (M3x20)

with Plastic Nylon Anchor 

CAT5 RJ45 Ethernet Cable

(10 feet/3.05 m) 

ENVIROSENSOR

Hook and Loop Tape

Cyber

Power

Relia

bility. Qual

ity. Va

lue.

R

User'

s M

anua

l

User’s Manual

Product Features

K01-0000207-00 

Overview

The CyberPower environmental sensor (ENVIROSENSOR)

along with select SNMP/HTTP cards (RMCARDXXX) or most 

Switched and Monitored PDUs enables users to monitor the 

temperature and humidity of a server closet and/or datacenter 

remotely.  With CyberPower's PowerPanel Business Edition 

software, users can establish thresholds that will automatically 

notify users when an event has occurred via email, SMS and 

SNMP traps. Additionally, the ENVIROSENSOR provides 4 input 

dry contacts that enable users to monitor the status of connected 

devices, such as door switch sensors.

Features include:

• Real time environment monitoring

• Remote management and configuration of the sensor via Web 

Browsers or NMS

• Automatic events notification via email, SMS and SNMP traps

• 4 input dry contacts application interface provided

• Displays the name and location of the sensor and 

connected devices

A. LED

B. Input Dry Contact 1-4

C. Common Connection

D. RJ45 Port 

     (connect to RMCARD/PDU) 

NOTE:

 Please refer to Appendix 

for Input Dry Contact Application.

A

DATA

STATUS

COM

4

1

2

3

C

B

D

Technical Specification

Installation Guide

Method 1- Hook and Loop Tape 

Mounting

Step 1. Clean the surface of the 

area where the sensor will 

be installed. Apply one side 

of the hook and loop tape 

to the bottom of the sensor 

and the other side to the 

sensor location.

Step 2. Attach the sensor on the 

surface and hold for about 5 

seconds to ensure cohesion.

NOTE:

 Once the sensor is installed, 

you will want to leave it in place to 

ensure the the hook and loop tape 

maintains its adhesiveness.
Step 3. To connect the sensor with 

RMCARD/PDU, use the 

attached RJ45 Ethernet 

Cable. Plug one end into the 

RJ45 Port and the other end 

into the RMCARD/PDU.

NOTE:

 If the distance of 

RMCARD/PDU and the sensor is 

longer than 10 feet/3.05 m, use a 

standard RJ45 Ethernet Cable as 

needed (max 50 feet/15 m).

Universal

RX/TX

Link

RMCARD203

Copyright © 2011 CyberPower Systems, Inc.

                                    ENVIROSENSOR

 

Input Voltage

 

7V - 28V

 

Halt mode 72 mW/

Power Dissipation

 

Normal mode 110 mW

 

(Default 12V input)

Measurement Range and Accuracy

 

  Temperature 

32-158

 with accuracy ± 1.8

/

 

0-70

 with accuracy ± 1

  Humidity 

10-90 RH with accuracy ± 2% 

Communication

 

  Connection Port 

RJ45 Port

  Input Dry Contact 

4

Physical

 

  Dimensions (L x W x H) 

2.32 x 1.77 x 1.14 inches/

 

59 x 45 x 29 mm

  Weight 

1.46 oz /41.5 g

Safety Approvals

 

FCC Class B, CE, C-Tick

Warranty

 

3 Year Limited