![CWSI CP-3500D Operating And Installation Instruction Manual Download Page 59](http://html1.mh-extra.com/html/cwsi/cp-3500d/cp-3500d_operating-and-installation-instruction-manual_2701247059.webp)
P/N IM-C35KD Rev. C
2014 Commercial Wireless Systems International, LLC.
59
9. The Auxiliary output will activate if programmed to do so.
10. The event is stored in the alarm and all event log.
The membrane buttons will function as described in section 6.1.3. If unacknowledged lower priority
signals are present, they can be displayed as each higher priority signal is acknowledged. The LCD
display shown below is an example of the LCD display when multiple alarms spanning more than one
screen are in process.
The alarm level currently being viewed will be shown at the top of the screen along with the time and
date. The page up and page down soft keys will appear when number of signals spans more than
one LCD page. Use these keys to view alarms on other pages.
6.2.4 Sprinkler Supervisory
Alarm C can be programmed for sprinkler supervisory operation during programming of the system.
Also supervisory can be made to auto-restore as explained in section 4.7.2. Upon reception of a
supervisory signal the following will occur.
1. Any lower priority conditions currently displayed on the LCD will be replaced by the sprinkler
supervisory display.
2. The sounder will pulse once a second.
3. The sprinkler Supervisory LED will flash once a second.
4. Alarm Relay 3 will activate.
5. Relay 1, Relay 2 and auxiliary outputs will not activate.
6. The event is stored in the alarm and all event log.
The membrane buttons will function as described in section 6.1.3. If unacknowledged lower priority
signals are present, they can be displayed as each higher priority signal is acknowledged. The LCD
display shown below is an example of the LCD display when multiple supervisory alarms spanning
more than one page are in process.
NAC circuits must not be programmed to activate upon
receipt of a sprinkler supervisory signal.
If supervisory auto-restore is programmed on the LCD display for each restored supervisory signal
will disappear. When all supervisory signals are restored to normal at the transmitter the CP-3500D
will return to system normal unless other than supervisory are present.
1 2 : 0 0 : 0 0 P M A l a r m L e v e l A 0 1 / 0 1 / 0 9
P a g e U p P g D o w n
A l a r m 0 4 8 1 1 d 1 1 : 5 9 : 0 0 P M 0 1 / 0 1 / 0 9
P u l l S t a t i o n E a s t S t a i r w e l l
A l a r m 0 2 3 a 6 2 1 2 : 0 1 : 0 4 A M 0 1 / 0 2 / 0 9
S m o k e D e t e c t o r E l e c t r i c R o o m
A l a r m 0 4 8 1 1 d 1 2 : 0 5 : 0 0 A M 0 1 / 0 2 / 0 9
F l o w S w i t c h B a s e m e n t
Alarm level of
signals being
viewed
In process
alarms
Use page up
and down soft
keys to view
additional pages