Cutler-Hammer OPTIMizer Instructions For Operation Manual Download Page 1

I.B. 29C892B

Effective 8/99 Supersedes I.B. 29C892A dated October 1996

Cutler-Hammer

Instructions for Operation of OPTIMizer  
Hand Held Programmer 

(For Use with Digitrip OPTIM Trip Units)

P

R

O

T

E

C

T

I

O

N

 

A

N

D

 

C

O

O

R

D

I

N

A

T

I

O

N

C

O

M

M

U

N

I

C

A

T

I

O

N

S

 

S

Y

S

T

E

M

S

E

N

E

R

G

Y

M

O

N

I

T

O

R

I

N

G

P

O

W

E

R

Q

U

A

L

I

T

Y

Summary of Contents for OPTIMizer

Page 1: ...996 Cutler Hammer Instructions for Operation of OPTIMizer Hand Held Programmer For Use with Digitrip OPTIM Trip Units P R O T E C T I O N A N D C O O R D I N A T I O N C O M M U N I C A T I O N S S Y...

Page 2: ...LAR PURPOSE OF MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will Cut...

Page 3: ...8 2 4 Specification Summary 10 SECTION 3 OPERATION AND USE 3 1 General 11 3 2 Getting Started 11 3 3 Power Application 11 3 4 Function Overview 14 3 4 1 Select Address 14 3 4 2 Find Baud Address 14 3...

Page 4: ...lay 14 3 3 Momentary Connect Failure Message Display 14 3 4 Address Invalid Display 14 3 5 Typical Momentary Successful Connection Message Display 14 3 6 Cursor on Password in Main Menu 14 3 7 Passwor...

Page 5: ...Metered Values in Main Menu 19 3 23 First Display in Metered Values 19 3 24 Cursor Indicating Phase B Current Active 19 3 25 PHASE B IB Current Selected and Displayed 19 3 26 Cursor on Test Mode in Ma...

Page 6: ...advanced programmable trip unit system Digitrip OPTIM Refer to Appendix A for all instructional material references Please read and understand this manual and all other relevant manuals before proceed...

Page 7: ...AND FUNCTIONS An OPTIMizer must be used to configure the trip unit for communications on the INCOM Network This requires an operator during initial start up to Assign Unique Device Addresses Select B...

Page 8: ...QUIPMENT AS SUCH IT SHOULD BE HANDLED CAREFULLY AT ALL TIMES TO AVOID POSSIBLE DEVICE DAMAGE 2 2 PACKAGE AND EXTERNAL CONNECTIONS The OPTIMizer Hand Held Programmer is packaged in a high strength plas...

Page 9: ...hours the 9 volt battery will support depends upon the type of battery used Refer to Table 2 2 for information about battery choices When an auxiliary power supply is not being used the programmer wi...

Page 10: ...OPTIMizer Battery Compartment with Battery Installed Figure 2 5 Auxiliary Power Module Shown Connected to OPTIMizer Direct Breaker Connection The first method for connecting the hand held program mer...

Page 11: ...on and off To achieve power up the pushbutton must be pushed and held for approximately one second The programmer cannot be turned off while Find Baud Addr is displayed When the programmer is on power...

Page 12: ...linking cursor horizontally to the right in the display from category to category Continued use of this pushbutton will wrap around and eventually return to the starting category Left Arrow Pushbutton...

Page 13: ...he programmer Figure 2 2 The first line of the display is normally used to show the main menu selection possibilities A blinking cursor indi cates which category on the first line is active The sec on...

Page 14: ...g of setpoints for connected trip unit valid password required to setup or change setpoints LD Long Delay Setting LDTI Long Delay Time LDA Long Delay Action LDS Long Delay Slope SDPU Short Delay Setti...

Page 15: ...2 OPTIMizer Accessory Specifications Power Supply Battery ULTRALIFE Batteries Inc Lithium Power Cell Part U9VL 9 volts dc Auxiliary Power Module Cutler Hammer Catalog PRTAAPM Input 120 Vac Output 32...

Page 16: ...source and the OPTIMizer Hand Held Programmer Refer to paragraph 2 2 2 for details on an external power connection Notice Keep in mind that an Auxiliary Power Module is always required if a Trip Test...

Page 17: ...round Trip or No Trip Test Current Ground Current Neutral Current Total Energy Forward Energy Reverse Energy Power Peak Demand Power Factor Harmonic Distortion A B C and N Harmonic Content A B C and N...

Page 18: ...tions Use Edit Values Up or Down Pushbuttons to alter active item or value Use Select and Save Pushbuttons simultaneously to save to memory or initiate test Some entries in Metered Values and Setpoint...

Page 19: ...The OPTIMizer executes this func tion automatically when the OPTIMizer is first turned on Several attempts will be made to retrieve the address and baud rate If no trip unit is connected to the OPTIMi...

Page 20: ...A For system security a password is required to change settings or use certain features To change the baud rate or trip unit address setpoints run test mode or download copied setpoints a correct pass...

Page 21: ...enter a valid password pro ceed with the following steps Notice If the programmer automatically turns off or is intentionally turned off the procedure must be repeated from the beginning Use of an Aux...

Page 22: ...of the four displayed zeros is active and able to be altered Use the Up or Down pushbuttons to change the active number Use the Right Arrow or Left Arrow pushbuttons to move the cursor from one digit...

Page 23: ...ress is password protected Step 5 may require the entry of a valid password before any changes are accepted If the pro grammer was already turned on and a valid password was initially entered as descr...

Page 24: ...e Right Arrow or Left Arrow pushbuttons to move the cursor from one digit to another Step 4 Once the desired breaker address is displayed hold Save pushbutton depressed and depress Select pushbutton T...

Page 25: ...nt such as I4 t Figure 3 21 Step 8 Hold Save pushbutton depressed and depress Select pushbutton This simultaneous use of the two pushbuttons will enter the new setpoint into memory Notice Keep in mind...

Page 26: ...d in Table 2 1 Step 10 Use the Up Arrow pushbutton to return to the main menu Figure 2 9 3 9 TEST TRIP UNIT Digitrip OPTIM 550 750 and 1050 Trip Units contain a test capability One of the means for pe...

Page 27: ...r in the OPTIM family within a system The set tings are permanently retained in the memory of the OPTIMizer until another copy sequence replaces them 3 10 1 USING THE COPY COMMAND CP Plug the OPTIMize...

Page 28: ...battery information The OPTIMizer Hand Held Programmer should be stored in an environment that does not exceed the stor age temperature range of 30 C to 85 C The environ ment should also be free of ex...

Page 29: ...pond Incorrect key press Let OPTIMizer time out for 30 seconds Paragraph 3 3 to pressing on off Unit will shut off or go to main menu OPTIMizer turns off after Energy saver powered unit off several mi...

Page 30: ...Digitrip OPTIM Trip Unit System OPTIM Trip Unit System Overview IB 29C890 OPTIM Trip Units IB 29C891 OPTIMizer Hand Held Programmer IB 29C892 Breaker Interface Module IB 29C893 Digitrip RMS Trip Units...

Page 31: ...6 2500A I2t Long Flat Short Delay Phase SC 6340 96 2500A I4t Long Flat Short Delay Phase SC 6341 96 1600A Instantaneous Override Phase SC 6342 96 2000A Instantaneous Override Phase SC 6343 96 2500A In...

Page 32: ...act between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL IN...