50
PNEG-308
Purafire
15. Examples
Example 1
Determine the pipe sizing for a 2 PSI Natural Gas installation.
Because the appliance near junction N is farthest away from the gas meter, use this distance.
Section A-N is 95' long. Use the 100' line on the “Natural Gas @ 2 PSI” chart.
NOTE:
Sections I-K, C-H, and D-F are identical to the section L-N and should also use 1" pipe.
Figure 15A
Section
BTU Demand
Pipe Size
A-B
1220
1-1/4"
B-D
305
1"
B-C
915
1-1/4"
C-I
610
1"
I-L
305
1"
L-M
305
1"
M-N
80
1"