background image

  Installation manual CHARGESTORM® Connected

 

 

page 

10

 

 

 

Figure 13 Configuration of current limit 

6.4

 

Portal access 

Portal configuration connection requires that the internet access is working. The OCPP chargeboxid 

and server address must be known in advance in order to connect CHARGESTORM® Connected to 
the portal.  The information shall be provided by the portal operator. In case the CTEK E-Mobility 

portal “Charge Portal” is used is the URL to 

the portal on the following format.  

wss://<companyname>.oamportal.com/Ocpp/websocket

 Chargeboxid must not contain more than 

22 characters and it must be unique (charging stations cannot have the same chargeboxid). 
CHARGESTORM® Connected uses OCPP v1.5 or v1.6, which must be supported by the selected 

portal. 

 

Select 

Configuration

Server

 and enter the 

”ChargeboxId”

 

 

Select communication protocol to OCPP v1.5 or OCPP v1.6. 

 

Enter server address. Most often can the other parameters remain unchanged.  

 

Push the “Save” button

 (on the bottom of the page) 

After completing the configuration navigate to the status page and verify that the portal 
communication is established.  

 

Figure 14 Portal configuration 

Summary of Contents for E-MOBILITY CHARGESTORM Connected

Page 1: ...document Read and follow the instructions in this document before installation and usage of the product Installation must fulfill local safety regulations 3 Delivery content Part of delivery Charging...

Page 2: ...available for use inside CHARGESTORM Connected Make sure that power is off during installation 4 3 Network connection In case CHARGESTORM Connected shall be connected to a portal or a local controlle...

Page 3: ...ing CHARGESTORM Connected in direct light sunlight Symbol visibility is limited and heat in the unit is increasing CHARGESTORM Connected has a temperature sensor in the unit that adjust charging curre...

Page 4: ...le gland for 1 that is delivered with the product supports cable dimensions between12 22mm while the gland for 2 supports 3 6mm The glands must be replaced if the cables are outside specified range If...

Page 5: ...e end The wires cross section area must not exceed 16mm2 Make sure protected ground wire is longer than the other wires sot that it will be the last wire to detach if pulled Connect the supply wires t...

Page 6: ...nect cable to RJ45 connector on the control board located on the front panel When cable is connected in both ends shall link and activity led on the RJ45 connector be active If 3G is in use check that...

Page 7: ...dard USB port is used on the computer for configuration If the computer is running Microsoft Windows must an Ethernet to USB driver be installed to support access to the local web interface For Linux...

Page 8: ...r Configuration interfaces When network configuration is ready check on the status page that internet access is established Ethernet To set the IP settings for Ethernet follow the instruction below Un...

Page 9: ...WWAN is a specific 3G mode WWAN tends to be more robust than PPP described in previous chapter Follow the step by step instruction to configure WWAN Under Configuration Interface General select WAN W...

Page 10: ...owing format wss companyname oamportal com Ocpp websocket Chargeboxid must not contain more than 22 characters and it must be unique charging stations cannot have the same chargeboxid CHARGESTORM Conn...

Page 11: ...D tags that shall be activated on CHARGESTORM Connected 7 Product information Power input Power 16 32A 230V 1 phase or 16 32A 400V 3 phase 50Hz Power input connector depends on model Charging current...

Page 12: ...intenance of CHARGESTORM Connected shall be conducted at least once per year At installation and maintenance of CHARGESTORM Connected shall the following tests be performed Test Trip ground circuit br...

Page 13: ...Installation manual CHARGESTORM Connected page 13 11 Electrical schematics 11 13 phase Below is an example of a schematics for CHARGESTORM Connected 3ph dual outlet...

Page 14: ...Installation manual CHARGESTORM Connected page 14 11 1 IT nett Below is an example of a schematics for CHARGESTORM Connected 1ph dual outlet IT nett...

Page 15: ...orrect in the manual CTEK E Mobility is not responsible for faults or incidents or damages that can be traced to the usage of this manual Copyright CTEK E Mobility All rights restricted copying adapti...