Air Flow

AIRFLOW

AIR FLOW

The importance of proper air flow over the heat exchanger
cannot be over emphasized.

TEMPERATURE RISE CHECK

To determine if the air flow is correct, make a temperature
rise check.

 1.  Insert a thermometer in the supply air duct as close to

the furnace as possible yet out of a direct line from the
heat exchanger. See Figure 49.

 2.  Insert a thermometer in the return air duct as close to

the furnace as possible.

 3.  Operate the furnace for a minimum of 15 minutes in

gas heat mode.

 4.  When the thermometer in the supply air duct stops ris-

ing (approximately five minutes), subtract the return air
temperature from the supply air temperature. The dif-
ference is the temperature rise.

 5.  Compare the measured temperature rise to the ap-

proved temperature rise range listed on the furnace
name plate. See Figure 50.

If the measured temperature rise is above the approved
range, the air flow is too low. Airflow must be increased by
speeding up the blower, by removing restrictions in the
duct system, or by adding more supply or return air duct. If
the measured temperature rise is below the approved
range, the air flow is too much. Use lower speed tap on the
multi-speed blower.

FIGURE 49

TEMPERATURE RISE MEASUREMENT

FIGURE 50

TYPICAL FURNACE NAME PLATE

RHEEM SALES COMPANY, INC.

FORT SMITH, ARKANSAS

MODEL NO./NUMERO DE MODELE: R

96

TA

0702317

MSA

SERIAL NO./ NUMERO DE SERIE: W

0000100001

MFG. DATE SEE DATE NOTE

CONTROL SYSTEM JC

CATEGORY IV FORCED AIR FURNACE WHEN USING INDOOR AIR FOR COMBUSTION

CATEGORY IV TYP FSP DIRECT VENT FORCED AIR FURNACE WHEN USING OUTDOOR AIR FOR COMBUSTION.

FOR INDOOR INSTALLATION ONLY, IN A BUILDING CONSTRUCTED ON-SITE.

CATÉGORIE IV GÉNÉRATEUR D'AIR CHAUD Á AIR FORCÉE LORSOUE DE L'AIR INTÉRIEUR EST EMPLOYÉ

POUR LA COMBUSTION. CATÉGORIE IV TYPE FSP ÉVACUATION DIRECTE GÉNÉRATEUR D'AIR CHAUD À

AIR FORCÉE LORSOUE DE L'AIR EXTÉRIEUR EST EMPLOYÉ POUR LA COMBUSTION. POUR INSTALLATION

À L'INTÉREIER SEULEMENT, DANS UN BATIMENT CONSTRUIT SUR LE SITE.

ELECTRIC 

115

 V. 

60

 HZ. 

1

 PH, MIN. CIRCUIT AMPACITY ____AMPS, IB MOTOR FLA__, ID MOTOR FLA___

ELECTRIQUE 

115

V. 

60

 HZ 

1

 PH, COURANT MINIMAL ADMISSIBLE DE CIRCUIT ___A. INTENSITÉ MAXIMAL DE ___

MOTEUR DE SOUFFLANTE INTÉRIEURE ET___ MOTEUR DE TIRANGE INDUIT.

MAXIMUM OVERCURRENT PROTECTION DEVICE ___AMPERES. DISPOSITIF DE PROTECTION CONTRE UNE

SURINTENSITE DE ___A AU MAXIMUM.

NOx EMISSION LIMIT (NANOGRAMS.JOULE) ___. LIMITE D'ÉMISSION D'OXYDES D'AZOTE (NOx) EN

NANORAMMES PAR JOULE ___.

HOURLY INPUT RATING

DEBIT CALORIFQUE

MAXIMUM

Btu/hr      (Kw)       

75

,

000

 (

21

.

98

)

HOURLY INPUT RATING

DEBIT CALORIFQUE

MINIMUM

Btu/hr      (Kw)       

FACTORY EQUIPPED FOR   

AGENCE A L'USINE POUR

FOR GAS / GAZ          

NATURAL / NATUREL

ORIFICE / INJECTEUR 

51

 DMS

LIMIT SETTING / LIMITE COUPE-CIRCUIT 

120

° (4

9

°) °F(°C)

AUXILIARY LIMIT SETTING/

LIMITE COUPE-CIRCUIT COUPE-CIRCUIT AUXILIAIRE  °F(°C)

MAXIMUM PERMISSIBLE GAS SUPPLY PRESSURE TO FURNACE

PRESSION MAXIMUM D'ALIMENTATION EN GAZ À CHAUDIÈRE

MINIMUM GAS SUPPLY PRESSURE FOR PURPOSES OF INPUT ADJUSTMENT

PRESSION MINIMUM D'ALIMENTATION EN GAZ POUR LE

RÈGLAGE DE PUISSANCE D'ENTRÉE

MANIFOLD PRESSURE /PRESSION A LA TUBULURE

AIR TEMPERATURE RISE/

AUGMENTATIONDE LA TEMPÉATUREDE L'AIR 4

0

°(

22

°) - 

70

°(

39

°)°F (°C)

MAXIMUM EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTÉRIEURE MAXIMAL

INCHES W.C. (kPa)-PO. C.E. (kPa)           

NATURAL GAS/

GAZ NATUREL

IN. W.C.(kPa)/

PO. C.E. (kPa)

10

.

5

 (

2

.

61

)

10

.

5

 (

2

.

61

)

5

.

0

 (

1

.

2

4)

5

.

0

 (

1

.

2

4)

3

.

5

 (

0

.

87

)

LP GAS OR PROP/

GAZ DE PÉTROLE

LIQUÉFIÉ OU PROP.

IN. W.C.(kPa)/

PO. C.E. (kPa)

13

.

0

 (

3

.

23

)

13

.

0

 (

3

.

23

)

11

.

0

 (

2

.

73

)

11

.

0

 (

2

.

73

)

10

.

0

 (

2

.4

9

)

.

15

 (.

038

1

.

00

 (.

2

4

9

)

ASSEMBLED IN MEXICO

91

-

22176

-

11

CANADIAN ENERGY

PERFORMANCE

VERIFIED

RENDEMENT

ENEGETIQUE

VERIFIE

IN THE U.S. AND CANADA, AT ELEVATIONS ABOVE 

2

,

000

 FT. (

610

M), DERATE THE INPUT 

2

% PER 

1

,

000

 FT. (

305

M)

ABOVE SEA LEVEL. REFER TO INSTALLATION INSTRUCTIONS FOR PROPER ALTITUDE ADJUSTMENT.

AUX ÉTATS-UNIS ET AU CANADA, À DES ALTITUDES SUPÉRIEURES À 

610

M(

2

,

000

PI), IL FAUT APPLIQUER UNE PUERTE

DE 

2

% PAR TRANCHE DE 

305

M(

1

,

000

PI) AU-DESSUS DU NIVEAU DE LA MER. SE REPORTER AUX INSTRUCTIONS DE

MONTAGE POUR PROCÉDER AUX RÉGLAGES DUS À L'ALTITUDE.

ST-A1254-04-00

!

CAUTION

IT IS IMPORTANT THAT EACH DUCT SYSTEM BE
SIZED AND INSTALLED FOR THE SPECIFIC APPLICA-
TION BY PROPERLY APPLYING THE APPROPRIATE
INDUSTRY ACCEPTED STANDARD. IF LESS THAN
MINIMUM STANDARDS ARE APPLIED, THE EQUIP-
MENT USER COULD EXPECT TO EXPERIENCE
HIGHER UTILITY BILLS, MAJOR COMPONENT FAIL-
URE, VARYING DEGREES OF AIR NOISE OR OTHER
UNSATISFACTORY ISSUES, OVER WHICH THE MANU-
FACTURER HAS NO CONTROL.

!

WARNING

THE MEASURED TEMPERATURE RISE SHOULD BE AS
CLOSE TO THE MIDDLE OF THE STATED RANGE AS
POSSIBLE. FOR EXAMPLE, IF THE RISE RANGE IS 40
TO 70°F (4.5°-21°C), THE MIDDLE OF THE RISE RANGE
IS 55°F (12.8°C). IN ALL APPLICATIONS, THE IN-
STALLER MUST ADJUST THE TEMPERATURE RISE TO
THIS “MIDDLE” POINT AS CLOSELY AS POSSIBLE.
ALSO, THE TEMPERATURE RISE SHOULD NEVER BE
ABOVE OR FALL BELOW THE STATED RANGE. DOING
SO COULD CAUSE DAMAGE TO THE HEAT EX-
CHANGER OR INTERMITTENT OPERATION. THIS
COULD CAUSE INJURY OR DEATH AND WILL VOID THE
MANUFACTURER’S WARRANTY FOR THIS PRODUCT.

Summary of Contents for 96MDT SERIES

Page 1: ...6T SERIES 96MDT SERIES U L and or C S A recognized fuel gas and CO carbon monoxide detectors are rec ommended in all applications and their installation should be in accordance with the manufacturer s...

Page 2: ...ard Vertical Direct Vent Termination 58 Option 2 Standard Horizontal Direct Vent Termination 60 Option 3 Variant of Standard Horizontal Direct Vent Termination 60 Option 4 Alternate Horizontal Direct...

Page 3: ...t return the unit without open ing the carton If the model number is correct open the carton and verify that the furnace rating label specifies the same furnace model number that is specified on the c...

Page 4: ...facturer products meet current Fed eral OSHA Guidelines for safety California Proposition 65 warnings are required for certain products which are not covered by the OSHA standards California s Proposi...

Page 5: ...record height above anticipated snow level or in Canada intake and exhaust vents conform with CSA B149 1 Canadian Natural Gas and Propane Installation Code ______ Correct relationship exhaust to inta...

Page 6: ...INSTRUC TIONS WARNING COMBUSTION AND VENTILATION AIR MUST BE PRO VIDED TO THE FURNACE AS REQUIRED BY THE NA TIONAL FUEL GAS CODE U S AND CSA B149 1 CANADA AND THE COMBUSTION AND VENTILATION AIR SECTIO...

Page 7: ...MBUSTION RETURN AIR TEMPERATURE MAINTAINED BE TWEEN 55 F 13 C AND 80 F 27 C AND CLEAN FURNACE DUCT WORK AND COMPO NENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS AND VERIFY THAT THE FURN...

Page 8: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less tha...

Page 9: ...the furnace cabinet no freeze protection is required When the trap is mounted out side or partially outside the cabinet it must be protected from freezing Regardless of the location of the drain trap...

Page 10: ...F L O W NOTE HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION ST A1194 05 X0 FIGURE 4 OPTION B 2 3 PIPE OPTION A 2 PIPE 8 6 ST A1194 40 X0 C...

Page 11: ...ORIZONTAL OPTIONAL VENT AIR INLET CONDENSATE DRAIN UPFLOW ELECTRICAL CONNECTION LINE VOLTAGE ELECTRICAL CONNECTION LOW VOLTAGE 22 96 23 80 8 00 11 00 17 44 29 05 26 17 32 88 23 00 14 00 28 06 1 12 29...

Page 12: ...RIZONTAL AS SHOWN HORIZONTAL INSTALLATIONS REQUIRE CONDENSATE TRAP TO BE MOUNTED EXTERNALLY BELOW THE UNIT USE CAUTION MOUNT THE TRAP AFTER THE UNIT IS AT THE POINT OF INSTALLATION TO PREVENT DAMAGE T...

Page 13: ...LKHEAD COUPLING HOSE DOUBLE ELBOW TUBE C HOSE CLAMP INTAKE AIR DIFFUSER 8 X 1 2 SCREW X4 8 X 1 2 SCREW X10 5 8 DRAIN HOSE B CONDENSATE TRAP BRACKET DOWN FLOW 2 PVC VANE 1 4 HOLE PLUG 1 2 DRAIN HOSE F...

Page 14: ...LOW WITH VERTICAL VENT Pg 15 16 UPFLOW WITH LEFT SIDE VENT Pg 17 18 DOWNFLOW WITH RIGHT VENT NON ZERO CLEARANCE Pg 19 22 DOWNFLOW ZERO CLEARANCE Pg 23 27 HORIZONTAL RIGHT WITH RIGHT VENT Pg 28 30 HORI...

Page 15: ...STALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE INSTALL 2 OPTION DRAIN RIGHT DETERMINE RIGHT OR LEFT DRAIN OPTION LOCATE 7 8 HOLE IN JACKET SIDE REMOVE PLUG DISCARD DRILL 2 1 8 HOLE...

Page 16: ...ED __ UNIT HAS FORWARD PITCH __ HEAT TAPE INSTALLED IF REQUIRED __ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED __ CONFIRM THAT ALL HOSES ARE FREE OF KINKS __ CONFIRM ALL HOSES AND OTHER DRAIN PARTS H...

Page 17: ...PLATE 2b INSTALL 2 PIPE GROMMET AS SHOWN 2c INSTALL INTAKE COUPLING AS SHOWN 2b 2c 2a 2 5 8 1a 1b 1c 1 1a REMOVE FLUE TRANSITION TRANSITION COUPLING AND ELBOW NOTE REMOVE INDUCER COUPLING W ELBOW FOR...

Page 18: ...P OVER END 1 OF HOSE DOUBLE ELBOW 5b4 INSTALL TUBE C WITH HOSE CLAMP AS SHOWN TO HOSE A PRE ASSEMBLED 5b5 ATTACH HOSE DOUBLE ELBOW TO BULKHEAD COUPLING POSITION WIRE HOSE CLAMP __ VERIFY ALL HOSES ARE...

Page 19: ...NSTRUCTIONS ARE INTENTIONALLY GENERIC SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE FLAT HEAD SCREWDRIVER 1 4 BLACK VENT TUBE TRAP BRACKET DOWN FLOW 1 1a TRANSITION COUPLING DISCARD FLUE TRANSITION DISC...

Page 20: ...BRACKET WITH 2 SCREWS AS SHOWN 4c INSTALL 559 DRAIN PLUG IN THE CONDENSATE TRAP 4 3d 3c 3a 3b 3a RELOCATE 403 DRAIN PLUG IN THE COLLECTOR BOX 3b INSTALL 2 PIPE GROMMET 3c INTAKE COUPLING IN JACKET AS...

Page 21: ...IN STEP 1 FROM INDUCER COUPLING TO THE FLUE TAP IN THE CONDENSATE TRAP 6e INSTALL HOSE E FROM COLLECTOR BOX TO TOP OF CONDENSATE TRAP 20 10 APPROXIMATELY 10 20 TILT ON INDUCER COUPLING GROUND ROTATE I...

Page 22: ...T ALL HOSES ARE FREE OF KINKS __ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW __ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP O...

Page 23: ...1 4 SHOWN WITH FURNACE IN AS SHIPPED CONDITION NOTE THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE 5 16 HEX HEAD DRIVER TRANSITION COUPLING RETAIN...

Page 24: ...ECTRICAL WIRING SECTION FOR INSTRUCTIONS 5c SEE ELECTRICAL WIRING SECTION FOR INSTRUCTIONS 5c DRILL 2 1 8 HOLES IN BLOWER SHELF 5d 6 5a ROTATE UNIT 180 5b REMOVE KNOCKOUTS WITH HAMMER AND FLAT HEAD SC...

Page 25: ...SEATED 10c SLIDE PIPE COLLAR ASSEMBLIES FROM STEP 7 OVER THE 2 PIPES AND DRILL 8 PVC GLUE JOINT SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS...

Page 26: ...2 SCREWS 11c CUT 1 4 VENT TUBE TO FIT APPROX 10 1 2 11a ROTATE INDUCER COUPLING 10 NOTE TIGHTEN ELBOW COUPLING CLAMPS TO FLUE PIPE WITH 5 16 NUT DRIVER NOT SHOWN NOTE USE SOAPY WATER TO FACILITATE EA...

Page 27: ...PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW __ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP OF THE COUPLING SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTR...

Page 28: ...E 1 4 VINYL CAP YELLOW ON COLLECTOR BOX VENT TAP 2a 2b 2c MOVE MOVE MOVE 1 1a REMOVE TRAP AND HOSES NOTE TO REMOVE TRAP REMOVE 2 SCREWS AND PULL STRAIGHT OUT 1b INSTALL INTAKE COUPLING IN TOP PLATE AS...

Page 29: ...ONDENSATE DRAIN PLUG AND CONDENSATE TRAP GASKET AS SHOWN 4d INSTALL CONDENSATE TRAP MAKE SURE THE CHANNEL AT THE LOCATION SHOWN IN THE IMPORTANT SECTION ENGAGES THE EDGE OF THE JACKET AT THE LOCATION...

Page 30: ...VE A SLOPE IN DIRECTION OF WATER FLOW __ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE FLUE TRANSITION MUST BE LOCATED ON THE TOP OF THE COUPLING SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTRUCTION...

Page 31: ...PARTS MAY BE DIFFERENT IN YOUR FURNACE 1a REMOVE FLUE TRANSITION TRANSITION COUPLING AND ELBOW NOTE REMOVE INDUCER COUPLING W ELBOW FOR EASIER 1b REMOVE CONDENSATE TRAP AND HOSES NOTE TO REMOVE TRAP R...

Page 32: ...LLOW ON COLLECTOR BOX VENT TAP 3b 3a 5 5a REMOVE METAL BRACKET AND THE 403 DRAIN PLUG DISCARD 5b REMOVE HOSE A DISCARD 5c INSTALL 559 CONDENSATE DRAIN PLUG AND CONDENSATE TRAP GASKET AS SHOWN 5d INSTA...

Page 33: ...D COUPLINGS ARE TIGHTENED Checklist 6 HOSE E 6c HOSE F 6d ROTATE UNIT 90 6a ROTATE UNIT 90 6b CUT 1 4 VENT HOSE TO FIT APPROX 5 1 2 AND INSTALL AS SHOWN 6c CUT HOSE E AT LINE 1 INSTALL NOTE MAKE SURE...

Page 34: ...34 Field Conversions...

Page 35: ...35 Field Conversions...

Page 36: ...36 Field Conversions...

Page 37: ...37 Field Conversions...

Page 38: ...Field Conversions 38...

Page 39: ...SE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE 2 INTAKE COUPLING NOTE STEPS 1 4 SHOWN WITH FURNACE IN AS SHIPPED CONDITION NOTE THESE CONVERSION INSTR...

Page 40: ...TEP AFTER THE UNIT IS ROTATED 4a REMOVE METAL BRACKET AND 403 DRAIN PLUG DISCARD 4b REMOVE HOSE A DISCARD 4c INSTALL 559 CONDENSATE DRAIN PLUG 4d CONDENSATE TRAP GASKET AS SHOWN 4e INSTALL CONDENSATE...

Page 41: ...ARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW __ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE FLUE TRANSITION MUST BE LOCATED ON THE TOP OF THE COUPLING SEE LOCATION DETAIL IN THE GENERAL CONVERSION INST...

Page 42: ...living space 6 If a filter is installed near the furnace be sure to have adequate space for installation and removal of the unit filter 7 NOTE Where the maximum airflow is 1800 CFM or more BOTH sides...

Page 43: ...or cold areas Avoid return air from utility rooms kitchens and laundry rooms Ducting DUCTING WARNING UPFLOW FURNACE THE SOLID METAL BASE PLATE SHIPPED WITH THE FURNACE MUST BE IN STALLED IN THE FURNA...

Page 44: ...installation and removal of the unit filter NOTE DO NOT take return air from furnace rooms garages or cold areas Avoid return air from utility rooms kitchens and laundry rooms FIGURE 10 CUT OUT USING...

Page 45: ...Chlorine based swimming pool chemicals Water softening chemicals De icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Printing inks paint removers varnishes etc Cleaning solvents...

Page 46: ...every 4 feet No sags or dips are permitted 3 IMPORTANT Do not common vent with any other ap pliance Do not install in the same chase or chimney with a metal or high temperature plastic pipe from an o...

Page 47: ...SOLVENT CEMENT IMPORTANT After cutting pipe remove all ragged edges and burrs This is important to prevent reduction in pres sure drop throughout the system 1 Cut pipe end square Chamfer edge of pipe...

Page 48: ...ucture such as in areas with large accumulations of snow in winter Table 3 shows the equivalent lengths of dif ferent types of elbows Table 4 specifies the equivalent maximum vent lengths specified by...

Page 49: ...commended maximum number of long sweep elbows for either 2 or 3 inch pipe Combinations of long sweep 90s standard 90s or 45s may be used but the manufacturer recommends the use of long sweep 90s whene...

Page 50: ...Lengths section Table 4 Application of these products is limited to the terminations listed in Tables 5 and 6 below These manufacturers have provisions for B vent liners and chimney liners which can b...

Page 51: ...t and Figure 32 Direct Vent the vent location should also be governed by the following guidelines 1 Avoid terminating under any kind of patio or deck How ever if necessary vent piping may be installed...

Page 52: ...ave openings into the space which are located in accor dance with the requirements set forth in the following subsections A and B Size connected to the heated area or to the outside and by the input o...

Page 53: ...horizon tal ducts each opening shall have a minimum free area of 1 square inch for each 2 000 BTUH of total appliance input rat ing of all equipment in the enclosure see Figure 15 Table 10 specifies t...

Page 54: ...or spaces NON DIRECT VENT cont GENERAL VENTING REQUIREMENTS AND GUIDELINES FIGURE 14 NON DIRECT VENT AIR FROM ATTIC OR CRAWL SPACE OPTIONAL INLET AIR 1 SQ IN 6 5 SQ CM PER 4000 BTUH ST A1194 19 FIG D...

Page 55: ...7 VENT PENETRATIONS FOR NON DIRECT VENT FURNACES ST A1194 19 FIG B FIGURE 18 VENT PENETRATIONS FOR NON DIRECT VENT FURNACES WALL PENETRATIONS 8 MIN 12 MAX 20 31cm ST A1194 19 FIG F WARNING DO NOT USE...

Page 56: ...M WALL 60 Max TIP PORTION MUST REMAIN VERTICAL VENT MAY BE ROTATED AS MUCH AS 45 LEFT OR RIGHT FROM VERTICAL AS LONG AS TIP PORTION RE MAINS VERTICAL 45 45 ST A1194 19 FIG F 12 31cm ABOVE GRADE OR AVG...

Page 57: ...opening 6 inches 15cm for appliances 10 000 Btuh 3kw 12 inches 30cm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches 9m for appliances 100 000 Btuh 30kw 12 30cm 3 ft 9m 10 ft 3 05 m pref...

Page 58: ...ND GUIDELINES WARNING ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE OR IN CANADA CSA B149 1 NATURAL GAS AND PROPANE INSTALLATION CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUS...

Page 59: ...standard direct vent vertical termination 3 8cm minimum only if no snow accumulation is anticipated Venting Terminations more than 24 above roof penetration re quire additional support 12 31cm U S CA...

Page 60: ...ES TO OPT B TERMINATION ONLY NOTE This detail applies to the ter mination and NOT the penetra tion through the wall EXHAUST COUPLING REQUIRED INTAKE 12 31cm From Walll NOTE 1 A TRAP IN TH IS NOT REQ 2...

Page 61: ...TERMINATION 9 PIPING EXTERNAL TO THE STRUCTURE MUST BE INSULATED AS REQUIRED FOR LOCAL CLIMATE 10 WALL PENETRATION AND VENT TERMINATION MUST BE WITH 2 PIPE OPTION B ONLY NOTE 1 A TRAP IN THE COMBUSTI...

Page 62: ...ion elbows must be at the same angle and face the same direction left or right 2 A wind vane must be installed in the combustion air inlet pipe as shown in the diagram 3 Number and distance between re...

Page 63: ...rtical horizontal intake air vent runs and may be installed through roofs or sidewalls One 5 inch diameter hole RXGY E03 RXGY E03A or 3 5 8 inch diameter hole RXGY E02 RXGY E02A is required for the in...

Page 64: ...nadian Natural Gas and Propane Installation Code NOTE Dimensions between the inlet and outlet pipes di rect vent only are fixed by the sidewall termination Other drawings in this manual which specify...

Page 65: ...10 ft 3 05 m preferred 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 15cm for appliances 10 000Btuh 3kw 12 inches 30cm for appliances 10 000...

Page 66: ...24 61cm ABOVE ROOF A SEE 6 1 8m MINIMUM 10 3m RECOMMENDED A SEE MINIMUM 12 31cm ABOVE GRADE IN U S ST A1194 18 DETAIL ST A1194 21 ST A1194 22 DETAIL A CONCENTRIC VENTING THROUGH ROOF CONCENTRIC VENTI...

Page 67: ...d drain will cause the condensate water to overflow the vent and spill water on the floor below it but the furnace will con tinue to run and heat will be provided If the installer uses this approach h...

Page 68: ...DRAIN ROUTING THE INSTALLER HAS THE OPTION TO ROUTE THE DRAIN TO THE RIGHT OR LEFT SIDE OF THE FURNACE AS NEEDED A I R F L O W HEIGHT OPTION B HEIGHT OPTION A HEIGHT OF LOWER CONDENSATE DRAIN SENSOR...

Page 69: ...N AIR AND TENDS TO COLLECT AT LOWER LEVELS MAKING IT MORE DIFFICULT TO SMELL AT NOSE LEVEL NATURAL GAS IS LIGHTER THAN AIR AND WILL RISE POSSIBLY ACCUMULATING IN HIGHER PORTIONS OF THE STRUCTURE IF A...

Page 70: ...company for the lo cation of the manual main shut off valve The gas line and manual gas stop must be adequate in size to prevent undue pressure drop and never smaller than the pipe size to the gas va...

Page 71: ...ply CONTINUED ON NEXT PAGE ways use a pipe compound resistant to the action of lique fied petroleum gases on all threaded connections IMPORTANT When making gas pipe connections use a back up wrench to...

Page 72: ...SHUT OF VALVE FOR CANADIAN INSTALLATIONS CSST CAN BE USED INSTEAD OF 2 STREET ELBOWS 2 STREET ELBOWS UNION MANUAL SHUT OF VALVE DRIP LEG UNION MANUAL SHUT OF VALVE 2 STREET ELBOWS HORIZONTAL FIGURE 36...

Page 73: ...ABLE 12 NATURAL GAS PIPE CAPACITYTABLE CU FT HR Capacity of gas pipe of different diameters and lengths in cu ft per hr with pressure drop of 0 3 in and specific gravity of 0 60 natural gas Nominal Le...

Page 74: ...the furnace has been converted to LP gas LP CONVERSION FIGURE 38 TYPICAL LP KIT CONTENTS TABLE 13 LP GAS PIPE CAPACITYTABLE CU FT HR Maximum capacity of pipe in thousands of BTU per hour of undiluted...

Page 75: ...upplier adjust the line pressure at the regulator MANIFOLD GAS PRESSURE MEASUREMENT Natural gas manifold pressure should be 3 5 3 w c for high fire and 1 8 1 w c for low fire LP gas manifold pressure...

Page 76: ...Association Inc Batterymarch Park Quincy MA 02269 CSA International 5060 Spectrum Way Mississauga Ontario Canada L4W 5N6 online www csa ca REVERSING THE ELECTRICAL CONNECTION JUNCTION BOX If the line...

Page 77: ...c sheet for compatibility concerns Generally all thermostats that are not of the current robbing current robbing thermostats require the addition of an isolation relay See Figure 41 types are compatib...

Page 78: ...oltage neutral terminal on the control board This will power the humidifier whenever the burner is on and the circulating air blower is operating in the heat ing mode NOTE Maximum current 1 0 amps for...

Page 79: ...SORT FILTER RACK FIELD SUPPLIED FILTER ST A1194 10 X0 ST A1194 11 X0 RXGF CC ACCESSORT FILTER RACK FIELD SUPPLIED FILTER ST A1194 12 X0 FIGURE 43 FILTER LOCATIONS ACCESSORIES FIELD INSTALLED OPTION AC...

Page 80: ...e to provide correct airflow to each furnace for supply and return UT ELECTRONIC CONTROLS 1095 310 CONTROL BOARD 62 104059 01 1 Single Stage Operation a Control board ONE is on furnace connected to th...

Page 81: ...SHOWN IS FIELD INSTALLED NOTE A FAULT CODE 20 WILL FLASH TO INDICATE A TWINNING PROBLEM CONFIRM PROPER WIRING IF THIS FAULT IS PRESENT 100 HEAT AT ALL TIMES ACCESSORIES CONTROL BOARDS Accessories FIGU...

Page 82: ...T A1254 07 01 NOTE ALL WIRING SHOWN IS FIELD INSTALLED NOTE A FAULT CODE 20 WILL FLASH TO INDICATE A TWINNING PROBLEM CONFIRM PROPER WIRING IF THIS FAULT IS PRESENT SW 7 SW6 TIME TO 2nd STG OFF ON N A...

Page 83: ...WN IS FIELD INSTALLED NOTE A FAULT CODE 20 WILL FLASH TO INDICATE A TWINNING PROBLEM CONFIRM PROPER WIRING IF THIS FAULT IS PRESENT TWIN TWIN ACCESSORIES CONTROL BOARDS Accessories FIGURE 46 UT ELECTR...

Page 84: ...he volume of natural gas per hour 14 000 900 Q 15 56 FT3 Q The volume of natural gas used on this furnace at sea level is 15 56 ft3 per hour Use this value to locate the ori fice size in table Table E...

Page 85: ...est method 5 Furnace operation is optimized when operating at design rate Installer is responsible to verify rate 6 This table applies to 90 models only with 14 000 BTU Burner DO NOT USE THIS CHART FO...

Page 86: ...rates must be measured on site with manifold pressure adjustment to ensure that an actual 10 reduction in input rate is achieved Once this field adjustment has been made the label shown in Figure 47 m...

Page 87: ...tegrated Controls with Direct Spark Ignition UT ELECTRONIC CONTROLS Integrated Controls with Direct Spark Ignition 1 Each time the thermostat W Heating contacts close the furnace control checks to mak...

Page 88: ...esent the fault displayed is normally re solved by priority noted in the table above The lower pri ority number is displayed over a higher fault priority number For example a fault priority 2 Unexpect...

Page 89: ...condition cannot be reset by cycling the heat call 2 Voltage is detected unexpectedly on the gas valve contacts welded relay and will not clear by cycling the inducer Fault code 93 is set and display...

Page 90: ...n a vertical orientation and the low voltage terminal block T2 is on the left Cool Blower Off Delay SW2 SW3 A means of selecting the cooling speed blower off delay time is provided In legacy mode dips...

Page 91: ...r amber L E D is provided to indicate flame sta tus When normal flame is sensed the flame L E D is con tinuously on The flame L E D will flash at a rate of one to four flashes per second if a weak fla...

Page 92: ...y major changes in the gas flow rate should be made by changing the size of the burner orifices To change orifice spuds shut off the manual gas valve and remove the gas manifold On LP gas furnaces the...

Page 93: ...nifold pressure and or gas orifice size may need to be changed to adjust the furnace to its nameplate input Consult the local gas utility to obtain the yearly average heating value and orifice size re...

Page 94: ...IMITE D MISSION D OXYDES D AZOTE NOx EN NANORAMMES PAR JOULE ___ HOURLY INPUT RATING DEBIT CALORIFQUE MAXIMUM Btu hr Kw 75 000 21 98 HOURLY INPUT RATING DEBIT CALORIFQUE MINIMUM Btu hr Kw FACTORY EQUI...

Page 95: ...279 x 178 High 1423 1387 1355 1320 1285 1250 1215 1180 1144 Low 916 869 820 752 685 646 586 530 488 R96T 1 2 373 Med Lo 1064 1022 979 937 888 820 770 729 673 602317 Med 1192 1161 1121 1081 1041 998 9...

Page 96: ...M1 or M2 Check motor lead color for speed designation Heating speeds should not be reduced where it could cause the furnace air temperature to rise to exceed the maximum outlet air temperature specifi...

Page 97: ...neutralizer if used be replaced by a qualified installer service agency or the gas supplier IMPORTANT It is recommended that an annual inspec tion and cleaning of all furnace markings be made to as su...

Page 98: ...pes or wires in walls Check heat anticipator setting Furnace may need an isolation relay Check installation instructions under section titled Isolation Relay for details Verify correct furnace sizing...

Page 99: ...RING REGULATIONS AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL 105C MIN FIELD INSTALLED FACTORY STANDARD LOW VOLTAGE FIELD INSTALLED FACTORY O...

Page 100: ...100 CM 1016...

Reviews: