Modbus
Page 17
FA 550 V1.00
11 Modbus Register
The dew point sensor FA 550 comes with a Modbus RTU Interface.
Before commissioning
of the sensor
the
communication
parameters
Modbus ID, Baud rate, Parity und Stop bit
must be set in order to ensure the communication with the Modbus master.
The adjustment can be
done either with the CS Instruments
PC
service
software
,
DS
400
,
DS
500
and
the
hand-held instrument
PI
500
done
.
Modbus communication default values:
Modbus ID : 1
(1 -247)
Baudrate:
19200 bps
(1200,2400, 4800, 9600, 19200, 38400 bps)
Parity:
even
(none, even, odd)
Stoppbit:
1
(1,2)
Supported are following function codes:
Function code 03:
Read Holding Register
Function code 16:
Write multiple Register
For parameter settings/- changing see chapter 12 Operation/Modbus Settings
11.1
Register Mapping measuring values
Modbus
Register
Modbus
Address
No.of
Byte
Data
Type
Description
Default
Setting
Read
Write
Unit /Comment
1001
1000
4
Float Temperature
R
[°C]
1003
1002
4
Float Temperature
R
[°F]
1005
1004
4
Float Relative Humidity
R
[%]
1007
1006
4
Float Dew Point
R
[°Ctd]
1009
1008
4
Float Dew Point
R
[°Ftd]
1011
1010
4
Float Absolute Humidity
R
[g/m³]
1013
1012
4
Float Absolute Humidity
R
[mg/m³]
1015
1014
4
Float Humidity Grade
R
[g/kg]
1017
1016
4
Float Vapor Ratio (Volume)
R
[ppm]
1019
1018
4
Float Saturation vapor pressure
R
[hPa]
1021
1020
4
Float Partial Vapor Pressure
R
[hPa]
1023
1022
4
Float Atmospheric DewPoint
R
[°Ctd]
1025
1024
4
Float Atmospheric DewPoint
R
[°Ftd]
Remark for DS400 / DS 500 / Handheld devices - Modbus Sensor Datatype:
„
Data Type R4-
32“ match with „Data Type Float“