Accessory Enclosure 

Installation, Commissioning and Maintenance Instructions 

 
 

The Accessory enclosure enables flammable gas detectors with a pellistor mV bridge output to be 
connected to Gasmaster or any other 4-20mA control panel. These instructions refer to Crowcon’s 
Gasmaster  system,  but  can  be  used  as  guidance  for  any  similar  control  system.  Other  4-20mA 
type gas detectors or fire detectors should be connected directly to the Gasmaster panel. 
 
The  Accessory  Enclosure  contains  between  1  and  4  sensor  amplifier  PCB’s  which  convert  the 
sensor  mV  bridge  signal  to  a  4-20mA  signal  which  can  be  monitored  by  the  control  panel.  The 
amplifier PCB’s are designed for use with catalytic beads rated at 2V dc 300mA (approx). 
 
To enable an Accessory Enclosure to be used, the Gasmaster must be fitted with the appropriate 
connector  and  wiring  loom.  If  the  connector  was  not  fitted  when  the  Gasmaster  system  was 
ordered, it can be purchased and fitted at a later date (see spare parts and accessories section for 
the part number). 
 

1.  Installation 

The Accessory Enclosure should be fixed to a wall adjacent to the control system using the 6mm 
(1/4”)  mounting  holes  provided.  The  enclosure  is  supplied  with a  75cm  (3’)  lead fitted for  simple 
connection to the Gasmaster panel. The flammable gas detectors should be connected directly to 
the Accessory Enclosure as shown in Figure 2. An earth continuity plate is fitted for bonding cable 
glands. 

 

 

Figure 1 Accessory Enclosure Layout 

 
 
 
 

Cable glands (supplied 
by customer) 

Connection lead to 
Gasmaster  

Screw-lock 
connector 

Sensor amplifier 
PCB’s (1 to 4  
may be fitted) 

M07642 
Issue 4  
January 2015 