background image

The Crestron®

HZ-KPEX

Horizon™ in-wall keypad features the following:

l

infiNET EX® Wireless Communication to Crestron Gateway
(CEN-GWEXER)

l

Field replaceable, engravable button caps available in various sizes (not
supplied)

l

Provides multiway functionality

The HZ-KPEX controls Crestron devices such as lighting, shading, and A/V
equipment from a single location. The device offers the following rating:

l

Line Power: 120 VAC, 50/60 HZ, 30 mA (requires neutral wire )

l

DC Power: 60 VDC, 30 mA (requires SolaHD® SDP™ 1-48-100T power
supply, not included)

WARNING:

Do not use the REM terminal when the HZ-KPEX is

powered by 60 VDC.

NOTE:

When wiring the device for 60 VDC operation, ensure that the

polarity is correct. C (positive) to the NEU terminal and -
(common) to the HOT terminal.

In the Box

1

HZ-KPEX, Horizon™ In-Wall Keypad with infiNET EX®
Wireless Communication, 120 VAC

Additional Items

2

Screw, 6-32 x 1 in., Truss Head, Combo (2054883)

1

Spacer, Multi-Gang Alignment (2049924)

1

Nut, Wire, Red (2053634)

NOTE:

Faceplates are not included. Refer to the

HZ-FP-G series

faceplates for more information.

Important Notes

WARNING:

To avoid fire, shock, or death, turn off the power at the

circuit breaker or fuse and test that the power is off before wiring!

NOTE:

When using the HZ-KPEX as a multiway controller, all 3- or 4-

way switches in a multi-way circuit must be replaced by HZ-AUX units
or HZ-KPEX units with a single HZ-DIMEX, HZ-DIMUEX, or HZ-SWEX
unit installed at the load side of the multi-way chain.

NOTES:

Observe the following points.

l

Codes: This product should be installed and used in accordance with
appropriate electrical codes and regulations.

l

Installation: This product should be installed by a qualified electrician.

l

Wiring: Use copper wire only. For supply connections, use wires rated
for at least 75° C (167° F).

l

Temperature: For use where temperatures are between 32° to 86° F
(0° to 30° C).

l

Electrical Boxes: Devices mount in standard electrical boxes. For easy
installation, use 3-1/2 in. (89 mm) deep electrical boxes. Several
devices can be installed in one electrical box (multigang). For a
smooth appearance, one-piece multigang faceplates (not supplied)
must be installed. When installing into a multigang box, do not fully
tighten the devices to the box until the faceplate has been aligned.

l

Switches: Mechanical 3- or 4-way switches do not work with
HZ-KPEX keypads.

1

HZ-KPEX

Quick Start

Horizon™ In-Wall Keypad with infiNET EX® Wireless Communication, 120 VAC

Summary of Contents for Horizon infiNET EX HZ-KPEX

Page 1: ...ock or death turn off the power at the circuit breaker or fuse and test that the power is off before wiring NOTE When using the HZ KPEX as a multiway controller all 3 or 4 way switches in a multi way circuit must be replaced by HZ AUX units or HZ KPEX units with a single HZ DIMEX HZ DIMUEX or HZ SWEX unit installed at the load side of the multi way chain NOTES Observe the following points l Codes ...

Page 2: ...ss wiring Avoid overcrowding the electrical box and remove unnecessary wiring when possible NOTE To wire one or more HZ AUX or HZ KPEX refer to Wiring Diagrams 3 Fold the wires into the electrical box Avoid pinched wires 4 Secure the HZ KPEX to the electrical box using the included mounting screws on the device To allow for adjustments do not fully tighten the screws at this time Ensure that any t...

Page 3: ...racket When the HZ FP G is available refer to the Quick Start guide for installation 6 Attach the HZ FP G series faceplate using the faceplate mounting screws Ensure that the Top label is properly oriented 7 Ensure that the HZ KPEX is properly aligned within the HZ FP G and then fully tighten the integrated mounting screws to secure the device to the electrical box 8 Attached the magnetic top and ...

Page 4: ...HZ KPEX Multigang Installation 4 HZ KPEX Quick Start Horizon In Wall Keypad with infiNET EX Wireless Communication 120 VAC ...

Page 5: ...Wiring Diagrams Two Points of Dimming or Switching Control 3 Way 5 HZ KPEX Quick Start Horizon In Wall Keypad with infiNET EX Wireless Communication 120 VAC ...

Page 6: ...Three or More Points of Dimming or Switching Control 4 Way 6 HZ KPEX Quick Start Horizon In Wall Keypad with infiNET EX Wireless Communication 120 VAC ...

Page 7: ...and hold actuation sequences for each local button option as selected in programming There is only one local button available per device The HZ KPEX can be used as a multiway controller When using the device as a multiway controller the local button that controls the master load controller must be selected Button behavior can be altered by the control system program If the local button is disabled...

Page 8: ... the MC3 internal gateway when using channels 25 or 26 Joining an infiNET EX Network Before a device can be used in a lighting system it must first join an infiNET EX network by being acquired by an infiNET EX gateway NOTE A device can be acquired by only one gateway 1 Put the infiNET EX gateway into Acquire mode from the unit itself or from Crestron Toolbox software as described in the gateway s ...

Page 9: ...device from an infiNET EX network To place a device into Acquire mode refer to step 2 in Joining an infiNET EX Network Verifying Communications Status To check the communications status of the device tap the top button three times and then press and hold it down tap tap tap press hold for up to 2 seconds The button must be released before the LEDs flash to indicate the communications status Refer ...

Page 10: ...backlights flash magenta This can also be triggered in programming 4 Avoid blocking the light sensor on the bottom of the HZ KPEX The light sensor should remain unobstructed and free of direct light After about 5 seconds the calibration process is complete The keypad returns to normal operation Backlight Customization Backlight color customization can be accomplished locally or through programming...

Page 11: ...orrect Check that the program is driving the LED indicators The keypad does not function All LEDs flash when a button is pressed The keypad is not acquired by a gateway Perform the acquire process Trouble Probable Cause s Corrective Action The keypad does not function All LEDs flash three times when a button is pressed The keypad is not communicating with the gateway Ensure that the gateway is pow...

Page 12: ...tron com warranty The specific patents that cover Crestron products are listed at www crestron com legal patents Certain Crestron products contain open source software For specific information visit www crestron com opensource Crestron the Crestron logo Crestron Home Crestron Toolbox Horizon and infiNET EX are either trademarks or registered trademarks of Crestron Electronics Inc in the United Sta...

Reviews: