29 • GL-IPAC-SW8
Product Manual — Doc. 7389C
Photo Sensors
Photo Sensors configures loads and lighting thresholds for photo sensors attached to the
GL-IPAC-SW8.
Select Photo Sensors from the Setup menu to enter the Photocell List screen. The screen
displays the available photo sensors. The GL-IPAC-SW8 types of sensors include:
l
4 internal (Sensors 5 through 8)
l
10 external non-system sensors wired directly to a Cresnet occupancy sensor (Sensors
B0.2 through B9.2)
l
10 external non-system sensors wired to a Cresnet GLS-SIM (Sensors C0.2 through C9.2)
l
10 external
sensors wired to a Cresnet network (Sensors C0 through C9)
Photocell List Screen
Photo Sensor Range
Configure lighting levels for each sensor:
1. Press Loads.
2. Use ▼ and ▲ to highlight the desired sensor on the Photocell List screen, then press Setup
to configure the sensor. The screen provides four lighting levels in foot-candles (fc).
3. For open loop sensors (
) select 3-300 (GLS-LOL), 30-3000 (GLS-LOL), or 60-
6000 (GLS-LOL) depending on the lighting level required to trigger an action. Settings on
the Select range (fc) screen must match jumper settings on the GLS-LOL. Other photo
sensors should be assigned to 0-1000 (Other).
Select range (fc) Screen