Description

The GLS-SIM is a compact interface device designed to allow Crestron Green Light

®

 

sensors to be connected directly to a Cresnet

®

 control network. Cresnet is the 

communications backbone for Crestron

®

 sensors, dimmers, keypads, touchpanels, 

shade controllers, thermostats, and many other devices. This flexible 4-wire bus provides 
data communications and 24 Vdc power for all of the devices on the Cresnet network. 
The GLS-SIM installs easily at the sensor location, mounting inside the electrical box or 
exposed above the ceiling. Wiring connections to the network and sensor are facilitated 
using miniature screw terminals.

GLS-SIM Specifications

Identity Code

The Net ID of the GLS-SIM has been factory set to 92 (with a mechanical setting of 00).

NOTE

:  The ID CODE switches on the GLS-SIM are factory set to 00. This allows 

changing the Net ID with Crestron Toolbox™ software (optional).

The Net ID of the GLS-SIM can be set using one of two methods:
  •  Manual Setting: Set the two ID CODE switches (from 03 to FE) to match a Net ID in 

the SIMPL Windows program.

  •  Touch-settable ID: Set the two ID CODE switches to 00 and set the Net ID using 

Crestron Toolbox. This is the factory setting. For more details, refer to the Crestron 
Toolbox help file.

ID CODE Switches

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

Hardware Hookup

Make the necessary connections as called out in the illustration. Apply power after all 
connections have been made.

CAUTION

:  Insufficient power can lead to unpredictable results or damage to the 

equipment. To help calculate how much power is needed for the system, use the 
Crestron Power Calculator at www.crestron.com/calculators.

NOTE

:  Use Crestron Certified Wire.

NOTE

:  When making connections, strip the ends of the wires approximately 1/2 in 

(13 mm). Use care to avoid nicking the conductors. Twist together the ends of the 
wires that share a connection.

GLS-SIM Connections

NOTE

:  The SENSOR port is a 4-pin 3.5 mm detachable terminal block. The sensor 

input is comprised of 24 Vdc power output and two Versiports (referenced to GND), 
5 V and 2k ohms pull-up resistor per pin.

NOTE

:  Depending on the available Cresnet power, the GLS-SIM can pass a maximum 

of 1 A @ 24 Vdc to the devices or sensors that are connected to the SENSOR port. 

Other Connections

The GLS-SIM can be configured as a digital input, an analog input, or a digital output. 
This setting is determined by the program running in the attached control processor. 
Other settings are controlled by the DIP switches. Refer to the “Configuration” section for 
diagrams that show how the GLS-SIM should be wired for each application.

CAUTION

:  Incorrect wiring may damage the GLS-SIM.

When setting the Net ID, consider the following:
  •  The Net ID of each unit must match an ID code specified in the control system 

program.

  •  Each network device must have a unique Net ID.

Installation

NOTE

:  Observe the following points.

  •  Install and use this product in accordance with appropriate electrical codes and 

regulations.

  •  If unsure about any part of these instructions, consult a qualified electrician.
  •  Mount the sensor on a vibration-free surface.
  •  All sensors must be mounted at least 6 feet (1.8 m) away from air vents.
  •  Do not mount sensors closer than 10 feet (3 m) from each other.
  •  Do not touch the inner surface of the lens. Clean outer surface with a damp cloth 

only.

NOTE

:  Before using the GLS-SIM, ensure the device is using the latest firmware. 

Check for the latest firmware for the GLS-SIM at www.crestron.com/firmware. Load 
firmware onto the device using Crestron Toolbox software.

The GLS-SIM can be installed inside a standard 4-inch electrical box or mounted above 
the ceiling using the included mounting bracket or the included dual-lock fastener. Use a 
#1 Phillips screwdriver and the included screws to attach the included mounting bracket.

Attaching the Mounting Bracket to GLS-SIM (Optional)

NOTE

:  Screws used for securing the GLS-SIM to a surface are not included.

Using a Dual-Lock Fastener on the GLS-SIM (Optional)

Mounting in an Octagon Back Box Installed Flush to a Drop Ceiling

2.88 in 
(74 mm)
2.48 in 
(63 mm)

0.20 in 
(6 mm)

Drop ceiling

Octagon back box
4 in x 1-1/2 in deep

#8-32 screws
(2 places)

GLS-SIM

Low-voltage 
wires

SENSOR:

Sends power to 

and receives input 

from sensor(s)

NET:

To control system 
and other Cresnet 

devices

Configuration

Use the DIP switches to configure the GLS-SIM to work with various device types, as 
described in the following illustrations and associated tables.

DIP Switches on GLS-SIM

1 2 3 4

On
Off

Sensor Digital Input 

The GLS-SIM can be configured for sensors that use relay contacts (normally open or 
normally closed) or voltage level (active high or active low). The digital input is rated for 
0–24 Vdc, the input impedance is 18.5k ohms, and the logic threshold is 1.25 Vdc.
Refer to the tables and wiring diagrams to configure the GLS-SIM.

Switch Settings for Digital Input (Dry Contact Closure)

SENSOR

24  1    2   G

Detecting a 
contact 
closure from 
a switch or 
relay

Detecting 
a low 
voltage

24 Vdc 
max.

SENSOR

24  1    2   G

Switch Settings for Digital Input (Voltage Detection)

SPECIFICATION 

DETAILS 

Power Requirements 

 

 

Cresnet Power Usage 

1 W (0.04 A @ 24 Vdc)  
(Does not include power draw of attached devices.) 

Environmental 

 

 

Temperature 

32° to 104 °F (0° to 40 °C) 

 

Humidity 

0% to 95% RH (noncondensing) 

Dimensions 

 

 

Height 

2.00 in (51 mm) 

 

Width 

2.00 in (51 mm) 

 

Depth 

0.86 in (22 mm) 

Weight 

2 oz (57 g) 

 

INPUT 

CHANNEL 

DIP 

SWITCH 

SETTING 

OFF: Enables pull-up resistor 
ON: Disables pull-up resistor 

OFF: Normal polarity 
ON: Inverted polarity 

OFF: Enables pull-up resistor 
ON: Disables pull-up resistor 

OFF: Normal polarity 
ON: Inverted polarity 

 

INPUT 

CHANNEL 

DIP 

SWITCH 

SETTING 

OFF 

OFF: Normally open 
ON: Normally closed 

OFF 

OFF: Normally open 
ON: Normally closed 

 

INPUT 

CHANNEL 

DIP 

SWITCH 

SETTING 

ON 

OFF: Active low 
ON: Active high 

ON 

OFF: Active low 
ON: Active high 

 

Reviews: