DIN-8SW8-I

DIN Rail High-Voltage Switch with Digital Inputs
Installation Guide

Hardware Hookup

Make the necessary connections. Apply power after all connections have been made.

WARNING

:  Prior to connecting the device, turn off the power at the circuit breaker. 

Failure to do so may result in serious personal injury or damage to the device. Restore 
the power after all connections have been made.

CAUTION

:  Connecting this device to the wrong type of load or short-circuiting the 

load can cause severe product damage. Test each load to identify a short-circuit 
condition prior to wiring the load to the module.

NOTE

:  Install in accordance with all local and national electric codes.

NOTE

:  High-voltage connections accept 12 AWG (2.5 mm

2

) wire. Wire should be 

stripped to 1/3 inch (8 mm). Tighten terminal blocks to 5 in-lbs (0.5 Nm).

NOTE

:  Use copper wire only. For high-voltage connections, use wire rated for at least 

75ºC.

NOTE

:  Each switch leg of the DIN-8SW8-I may be fed from a separate circuit breaker.

When making Cresnet

®

 (NET), INPUTS, and OVERRIDE connections, strip the ends of 

the wires approximately 1/4 in (6 mm). Use care to avoid nicking the conductors. Twist 
together the ends of the wires that share a connection. Apply solder only to the ends of 
the twisted wires. Avoid tinning too far up the wires, or the end becomes brittle.
When making power connections to the DIN-8SW8-I, use a Crestron power supply.

Hardware Connections for the DIN-8SW8-I

Description

The Crestron

®

 DIN-8SW8-I is an 8-channel lighting control module designed to support 

switching of non-dimmable lighting and fans. In addition, the DIN-8SW8-I features eight 
isolated digital inputs, allowing standard momentary switches to trigger events with or 
without a control system. A single model supports both 120 and 220−240 volt 
applications. Each channel handles incandescent loads up to 10 amps, fluorescent loads 
up to 5 amps, and also 1/2 HP motors. The DIN-8SW8-I may not be compatible with 
some high inrush current loads.

DIN-8SW8-I Specifications

Installation

WARNING

:  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that power is off before wiring! 

CAUTION

:  This equipment is for indoor use only. Mount in a well-ventilated area. The 

ambient temperature must be 32º to 104ºF (0º to 40ºC). The relative humidity must be 
10% to 90% (non-condensing).

NOTES

:  Observe the following points:

  •  When installing in an enclosure, group high-voltage devices separately from 

low-voltage devices.

  •  Install and use this product in accordance with appropriate electrical codes and 

regulations.

  •  A licensed electrician must install this product.
The DIN-8SW8-I is designed for installation on a DIN rail. Refer to the following diagram 
when installing.

Installing the DIN-8SW8-I

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

Install the DIN-8SW8-I.
  1.  Place the top of the DIN-8SW8-I’s rail mount over the top of the DIN rail.
  2.  Tilt the bottom of the DIN-8SW8-I toward the DIN rail until it snaps into place.

NOTE

:  It may be necessary to use a flat-head screwdriver to pull the DIN rail release 

tab while snapping the device onto the DIN rail.

To remove the DIN-8SW8-I from the DIN rail, use a small, flat object (i.e., a flat-head 
screwdriver) to pull the DIN rail release, and tilt the bottom of the DIN-8SW8-I away from 
the DIN rail.

NOTE

:  Certain third-party DIN cabinets provide space for an informational label 

between each DIN rail row. Crestron’s Engraver software (version 4.0 or later) can 
generate appropriate labels for all Crestron DIN rail products.

INPUTS:

Connections from 

Switches and Other 

Control Devices

OVERRIDE:

From Device Providing Override 

Signal and to Other Devices 

Receiving Override Signal

1 to 8:

Connections for 

Controlled Devices

NET:

To Control System and 

Other Cresnet Devices

With the circuit breaker turned off, connect the wires to the terminal blocks per the 
markings provided on the DIN-8SW8-I.

Load Connection Example for the DIN-8SW8-I

 

120/240 Volts

From Breaker

120/240 Volts

Load

Neutral

Line

DIN-8SW8-I

DIN Rail
(Not Supplied)

DIN Rail
Release

Top

1 2 3 4 5 6 7 8 C

INPUTS

Momentary 

Switches

12 to 24 V 

Power 

Supply

Y

1 2 3 4 5 6 7 8 C

INPUTS

24

Z G

Momentary 

Switches

24 V 

Cresnet 

Power 

Supply

SPECIFICATION 

DETAILS 

Load Ratings 

 

 

Switch Channels 

 

Maximum per Channel 

10 amps incandescent, 5 amps fluorescent,  
0.5 HP @ 120 to 240 volts ac, 50/60 Hz; 
5 amps @ 30 volts dc; 

16 amps resistive 

 

Module Total 

80 amps incandescent, 40 amps fluorescent @  
120–240 volts ac, 50/60 Hz 

 

Load Types 

Incandescent, Magnetic Low-Voltage, Electronic 
Low-Voltage, Neon/Cold Cathode, Fluorescent, 

Motors 

NOTE

:  May not be compatible with some high 

inrush current loads. 

Environmental 

 

 

Temperature 

32° to 104°F (0° to 40°C) 

 

Humidity 

10% to 90% RH (noncondensing) 

 

Heat Dissipation 

18 Btu/h 

Weight 

14 oz (369 g) 

 

Power Supply Connections (Using an Isolated Power Supply)