CLW-DIM, DIMS, & SLVD(W/A/B)

 

Operating Buttons and Switches 

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

The -DIM, -DIMS, and -SLVD feature three pushbuttons 
(one large, and two-small). The -DIM and -DIMS also 
have a three-position mode selection switch. The function 
of each button is determined by the position of the mode 
selection switch. Refer to the following diagram. 

CLW-DIMS with CLW-SLVD Wiring 

NOTE:

  The -SLVD does not have a mode selection 

switch. It will act in the same mode as the -DIMS. 

NOTE:

 The -DIMS must be installed in the same wallbox 

that contains the connections to the load.

 

Buttons of CLW-DIM, -DIMS, and -SLVD 

Button 1

Button 2

Button 3

Mode Selection Switch

(-DIM & -DIMS Only)

 

The following wiring diagram illustrates installation of 
the -DIMS with a -SLVD. 

Wiring Diagram of CLW-DIMS with multiple CLW-SLVDs 

Hot

Neutral

Load

RED

CLW-DIMS

BLACK

WHITE

CLW-SLVD

BLUE

BLACK

BLUE

Ground

Ground

GREEN

GREEN

LINE

120VAC

60Hz

WHITE

Ground

GREEN

BLACK

BLUE

CLW-SLVD

WHITE

Cresnet

 

OFF 

When the mode selection switch is in the “OFF” position, 
the buttons will not have any function and the load is 
disconnected from the power source. This 

must

 be used 

when changing light bulbs to ensure that the load is fully 
disconnected from power. 

NOTE:  

Do not connect the BLUE (Slave) wire to the 

Black (Hot) or RED (Load) wires. 

ADJ 

When the mode selection switch is in the “ADJ” position, 
the large button is used to switch between the “Button 1-
High” and “Button 1-Low” presets (typically “On” and 
“Off”). The lighting level can be manually adjusted using 
the two small buttons to raise (right button) and lower 
(left button) the lighting level.  

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

If the lighting level is to be stored as a preset, move the 
mode selection switch to the PRE position. Press and hold 
the desired preset button until the LED flashes. 

NOTE:  

If a -DIMS is installed without a -SLVD, the 

BLUE lead (Slave) should be capped. 

PRE 

5.  Splice the gray wires of the -DIM or -DIMS to 

the Class 2 low voltage wires connected to the 
Crestron control system, a Crestron power 
supply, a Crestron C2N-NPA8, or a Crestron 
connection block device. Push the wires and the 
splices into a hole in the drywall to provide the 
necessary separation. 

NOTE:

  Before storing a preset, the lighting must be 

adjusted to the desired level while in the ADJ mode. 

When the switch is in the PRE position, it is in the preset 
mode and can be used to recall and/or store preset lighting 
levels. The large button is used to recall and/or store the 
“Button 1-High” and “Button 1-Low” presets. The lower 
left button (button 2) is used to recall and/or store preset 
level two. The lower right button (button 3) is used to 
recall and/or store preset level three. Pressing and 
releasing a button will fade to the preset lighting level 
over a three second period. Tapping a button while the 
light is fading will cause the light level to “jump” to the 
preset without fading. Pressing and holding a button until 
the LED flashes will store the current lighting level. 

6.  Push all Class 1 power wires back into the 

wallbox and fasten the device to the wallbox 
with the provided screws. 

7.  Attach decorative faceplate. 

8. Restore 

power. 

Installation Guide – DOC. 5995B 

Stand Alone Wall Box Dimmer:  CLW-DIM, DIMS, & SLVD  

  5  

 

Summary of Contents for CLW-DIM

Page 1: ...ion mode selection switch Refer to Operating Buttons and Switches on page 5 for more information In the absence of Cresnet communications the dimmer can still be used to control lighting The CLW DIMS DIMS is similar to the DIM with the added capability of working with a slave unit CLW SLVD in a multi switch single circuit application The CLW SLVD SLVD is a slave unit that when used in conjunction ...

Page 2: ...d Front Industry Compliance This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc Important Notes Read before installation Codes Install in accordance with all local and national electrical codes Alternate wiring methods may be used for the Class 2 wiring connection The 2002 National Electrical Code Article 725 55 prohibits Class 2 conductors of the DI...

Page 3: ...h the DIM DIMS or SLVD Derating Information for Incandescent and Tungsten Halogen Applications Spacing If mounting one device above another leave at least 4 vertical space between them Part Number No Side Removed One Side Removed Two Sides Removed DIM 1000W 600W 400W DIMS 1000W 600W 400W SLVD No Derating Necessary Low Voltage Applications Use with core and coil magnetic low voltage transformers on...

Page 4: ...tion of the Crestron website http www crestron com dealer tech_resources design_center hot_design_tips_and_ diagrams tech_sales_tips NOTE The BLACK wire Cresnet ground should not be grounded with the GREEN Ground wire on the DIM DIMS SLVD CLW DIM CLW DIMS Wiring NOTE Crestron recommends using Crestron s Cresnet DM cable for connecting the DIM and DIMS to the Cresnet network NOTE The DIM and DIMS r...

Page 5: ...ed using the two small buttons to raise right button and lower left button the lighting level NOTE The RED Load and BLACK Hot wires are 14 AWG The BLUE Slave and WHITE Neutral wires are 18 AWG The GREEN Ground wire is 16 AWG The GRAY Cresnet wires are 22 AWG The BLACK wire Cresnet ground paired with the GRAY Cresnet wires is 22 AWG If the lighting level is to be stored as a preset move the mode se...

Page 6: ...o CRESTRON 6 Volvo Drive Rockleigh N J or its authorized subsidiaries with RMA number clearly marked on the outside of all cartons Shipments arriving freight collect or without an RMA number shall be subject to refusal CRESTRON reserves the right in its sole and absolute discretion to charge a 15 restocking fee plus shipping costs on any products returned with an RMA 3 Return freight charges follo...

Reviews: