Crestron CLCI-MCEX Installation Manual Download Page 1

CLCI-MCEX

Shutter Motor Controller
Installation Guide

Description

The Crestron

®

 CLCI-MCEX is a motor controller that provides open and close control of 

one shade or shutter motor. The CLCI-MCEX has outputs for raise/open and lower/close 
control. 
Its ultra-slim design allows it to be installed in the ceiling, either next to or near the motor. 
Powered by infiNET EX

®

 technology, the CLCI-MCEX communicates wirelessly with the 

control system, making it perfect for both new and retrofit applications. Install an in-line 
switch to provide local control of the shade or shutter motor.

Additional Resources

Visit the product page on the Crestron website (

www.crestron.com

for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

Important Notes

CAUTION:

  Observe the following points:

•  Install the CLCI-MCEX only on 10 A branch circuits.
•  Install using wires that are 1 mm

2

 to 2.5 mm

2

 and that comply with  

IEC 60227-5 and local electrical codes. 

•  Use the CLCI-MCEX with loads that have a power factor of 0.50 or greater.
•  To meet radiated emissions requirements, ensure that 3 feet (1 meter) of wiring 

leading to and from the CLCI-MCEX is straight and that there are no loops in the 
wiring.

NOTE:

  Observe the following points:

•  Codes: This product must be installed by a licensed electrician and in 

accordance with all local and national electrical codes.

•  Wiring: The CLCI-MCEX requires a neutral connection to operate.
•  Wiring: Use copper wire only. For supply connections, use wires rated at least 

75 °C.

•  Motor Type: For use with a permanently installed motor.
•  Temperature: For use where temperatures are between 0° and 40 °C  

(32° and 104 °F).

•  Transportation and Storage: Transport and store this device when temperatures 

are between -25° and 60 °C (-13° and 140 °F). 

•  Spacing: If mounting one device above another, leave at least 115 mm (4-1/2 in) 

vertical space between them.

Installation

WARNING:

  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that the power is off before wiring! 

Install the CLCI-MCEX:

1.  Turn off the power at the main circuit breaker. 

WARNING:

  The device should be mounted in a well-ventilated and dry area. 

2.  Identify the installation location for the CLCI-MCEX. 
3.  Remove the end caps from the device by unfastening the two screws shown. 

 

Unscrew 

and remove.

Unscrew 

and remove.

4.  Loosen the strain relief clamp screw and rotate the clamp to the side for wiring.

 

L  N  G  G   N  L  L  R

Loosen the screw. 

(Do NOT remove.)

5.  To mount the device (optional), use two M3 X .05 screws (not included).

 

Mounting Screw Locations

6.  Wire the device as shown in the illustration in the “Wiring” section. 

CAUTION:

  Use with wires that are 1 mm

2

 to 2.5 mm

2

.

7.  Tuck the wires under the strain relief clamps, and tighten the clamp screws. The 

jacketed cable must be clamped under the strain relief clamps.

 

Tighten the screws.

L  N  G  G   N  L  L  R

8.  Replace the end caps.
9.  With the device still accessible, turn on the main circuit breaker. 

Wiring

WARNING:

  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that the power is off before wiring! 

Wire the CLCI-MCEX and a remote switch.

infiNET EX 

communication to 

control system

L  N  G  G   N  L  L  R

SW2 N SW1 N

Remote (brown)

AC input 

from 

breaker

AC to 

next 

device

Neutral (blue)

Live (brown)

Live 

(brown)

Neutral (blue)

Live (brown)

Earth

(green/yellow)

Earth

(green/yellow)

230 VAC 

maintained or 

momentary 

switch

To motor

SW1 and N to 
motor open

SW2 and N to 
motor close

NOTE:

  The jacketed cable must be clamped under the clamping bar.

Remote Maintained (Single Switch)

Live

Remote

Remote Maintained (Multiway)

Live

Remote

Remote Maintained (Multiway)

Live

Remote

Remote Momentary (Single Switch)

Remote

Live

Remote Momentary (Multiway)

Remote

Live