background image

Crestron 

Thermostat

 

 

 

Quick Start Guide

 

 

Thermostat Quick Start Guide – Doc. 6145A  

 

CHV-TSAT and CHV-THSTAT Series 

   

Crestron Quick Start Thermostat  

CHV-TSTAT and CHV-THSTAT Series 

Step 2
Thermostat System Connections

Mounting

Screws

(not provided)

Wall Anchors

(not provided)

Backplate

Panhead

6/32 x 1 in

Single-gang

electrical box

(not provided)

Stud

Step 1
Thermostat Mounting

Backplate

For Additional details, refer to the latest version of

the Operations and Installation Guide, Doc. 8163

TOP

HU

M

RHU

RS

R

RS

R

RS

1

RS

2

24(C

)

24(

R)

24V

Y

Z

G

NETWORK

RH

RC

G

Y/

Y1

Y2

O

B

W/

W

1

W2

Backplate

24(R)

 - 24 VAC reference terminal. Can be connected to RH or RC

            by P4 jumper setting (refer to following page), or tied directly

            to power source

24(C) 

- 24 VAC common terminal supplies remote 24 VAC power

            to thermostat

RS2

 - Remote Sensor terminal - Connect the sensor from RS2 to RSR

RS1

 - Remote Sensor terminal - Connect the sensor from RS1 to RSR

RSR 

- Remote Sensor Returns - Common sensor terminal

RHU 

- Reference for humidifier

HUM 

- Energized (connected) to RHU during humidity call

W2

 - Heat (stage two), energized (connected) to RH during a call for

         second stage heat in heat/cool systems

W/W1

 - Heat (single stage)/heat (stage one) energized

             to RH during a call for heat in heat/cool systems or aux heat

             in heat pump systems

- Energized to RC during non-cooling modes

O

 - Changeover control, energized to RC during cooling modes

Y2 

- Compressor (stage two), energized to RC on two-stage

        systems on call for second stage

Y/Y1

 - Compressor (stage one), energized to RC when

           compressor (or first stage) is run

G

 - Fan, energized to RC during call for fan

RC

 - Reference Cool, used for calls to cooling system

RH 

- Reference Heat, used for calls to heating system

Network Connection

for Crestron

Installer Only

NOTE:

Fill the Electrical Box

with Thermal

Insulation Material

 

1