Crestron C2N-RTHS Installation Manual Download Page 1

C2N-RTHS

Temperature and Humidity Sensor
Installation Guide

Wiring

Make the necessary connections as called out in the illustration. Apply power after all
connections have been made.

CAUTION

:  Insufficient power can lead to unpredictable results or damage to the 

equipment. Use the Crestron Power Calculator to help calculate how much power is 
needed for the system (www.crestron.com/calculators).

NOTE

:  When wiring the Cresnet network, consider the following:

  •  Use Crestron Certified Wire.
  •  Use Crestron power supplies for Crestron equipment.
  •  Provide sufficient power to the system.

Wiring the C2N-RTHS

Description

The Crestron

® 

C2N-RTHS is a wall-mounted temperature and relative humidity sensor that 

communicates directly with any Crestron control system via the Cresnet

®

 control network. 

One-piece mounting makes the C2N-RTHS simple to install. The 1-1/2 in (38.1 mm) 
diameter face protrudes just 1/8 in (3.2 mm) from the wall surface and is easily painted or 
wallpapered to blend into the wall surface.

C2N-RTHS Specifications 

Installation

NOTES

:  Ensure the installation location is not close to a heat or humidity source and is 

away from direct sunlight, skylights, and windows. When mounting the sensor outdoors, 
do not place in direct sunlight, and do not place where the sensor will be directly 
exposed to precipitation. Sensors are suitable for mounting in dry or damp locations as 
defined by the National Electrical Code.

  •  Install and use this product in accordance with appropriate electrical codes and 

regulations.

  •  A licensed electrician should install this product.
  •  Mount sensors on a vibration-free surface.

NOTE

:  Before using the C2N-RTHS, ensure the device is using the latest firmware. 

Check for the latest firmware for the C2N-RTHS at www.crestron.com/firmware. Load 
the firmware onto the device using Crestron Toolbox™ software.

Complete the following procedure to install the C2N-RTHS:
  1.  Locate an area on the wall that is free of miscellaneous wiring and studs.
  2.  Make a small hole near the center of the designated mounting site to verify that the 

location is suitable.

  3.  Drill or cut a 1 in (26 mm) diameter circular hole in the wall at the desired position.
  4.  Route the Cresnet wires to the sensor. Use the four wire nuts included to connect 

the wires (red to red, white to white, blue to blue, and black to black).

 

Cresnet Wiring for the C2N-RTHS

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

Black  Ground

Red    24 V

White  Y
Blue    Z

Wire nuts

Cresnet 
wires

Pigtail wires 
from sensor

Mounting clips

1 in (26 mm) hole

C2N-RTHS Front and Angled View

NOTE

:  The miniature setup button and red LED are used for setting the network ID 

for the initial configuration or when the device is being added or replaced. They are 
also used for touch-settable ID (TSID).

Mounting clips

Setup 
button 

Red 
LED

C2N-RTHS Rear and Angled Views

10 in 

(254 mm)

  5.  Press fit the sensor into the hole; the clips on either side of the sensor hold it in 

place.

NOTE

:  The face of the sensor may be painted or wallpapered to match the wall. 

Ensure that paint does not enter (or that wallpaper does not cover) the perimeter 
gap or the holes for the setup button and LED.

SPECIFICATION 

DETAILS 

Measuring Range 

 

 

Temperature 

-40º to 176 ºF (-40º to 80 ºC) 

 

Humidity 

0% to 100% RH 

 

Output Resolution 

0.1 ºF (0.1 ºC); 1% RH 

 

Accuracy 

±1.0 ºF (0.5 ºC); 5% RH 

Temperature Accuracy 

 

 

Over Full Range 

±0.9 °F (0.5 °C) 

 

At Room Temperature 

+0.2/-0.7 °F (+0.1/-0.4 °C) 

Humidity Accuracy 

±5% 

Connection 

~10 in (~25 cm) 4-wire pigtail; 
Connects to Cresnet control network 

Power Requirements 

 

 

Cresnet Power Usage 

0.25 W (0.01 Amps @ 24 Vdc) 

 