background image

IR Gateway 

Crestron 

C2N-IRGW-1G & C2N-IRGW-F

 

chained must be added together to determine the Cresnet power usage of the entire 
chain. If the unit is a home-run from a Crestron system power supply network port, 
the Cresnet power usage of that unit is the Cresnet power usage of the entire run. 
The wire gauge and the Cresnet power usage of the run should be used in the 
following equation to calculate the cable length value on the equation’s left side. 

Cable Length Equation 

L = Length of run (or chain) in feet
R = 6 Ohms (Crestron Certified Wire: 18 AWG (0.75 MM  ))

or 1.6 Ohms (Cresnet HP: 12 AWG (4 MM  ))

P = Cresnet power usage of entire run (or chain)

2

2

L <

40,000

R x P

Where:

 

Make sure the cable length value is less than the value calculated on the right side of 
the equation. For example, a Cresnet run using 18 AWG Crestron Certified Wire and 
drawing 20 watts should not have a length of run more than 333 feet.  If Cresnet HP 
is used for the same run, its length could extend to 1250 feet.  

NOTE:

  All Crestron certified Cresnet wiring must consist of two twisted pairs. One 

twisted pair is the +24V conductor and the GND conductor, and the other twisted 
pair is the Y conductor and the Z conductor.  

Strip and Tin Wire 

When daisy-chaining Cresnet units, strip the ends of the wires carefully to avoid 
nicking the conductors. Twist together the ends of the wires that share a pin on the 
network connector, and tin the twisted connection. Apply solder only to the ends of 
the twisted wires. Avoid tinning too far up the wires or the end becomes brittle. 
Insert the tinned connection into the Cresnet connector and tighten the retaining 
screw. Repeat the procedure for the other three conductors. 

Add Hubs

 

For larger networks (i.e., greater than 28 network devices), it may become necessary 
to add a Cresnet Hub/Repeater (CNXHUB) to maintain signal quality throughout the 
network. Also, for networks with lengthy cable runs, it may be necessary to add a 
Hub/Repeater after only 20 devices. 

Reference Documents 

The latest version of all documents mentioned within the guide can be obtained from 
the Crestron website (

http://www.crestron.com/manuals

). This link will provide a list 

of product manuals arranged in alphabetical order by model number.  

List of Related Reference Documents 

DOCUMENT TITLE 

2-Series Control Systems Reference Guide  

Further Inquiries 

If you cannot locate specific information or have questions after reviewing this 
guide, please take advantage of Crestron's award winning customer service team by 
calling the Crestron corporate headquarters at 1-888-CRESTRON [1-888-273-7876]. 
For assistance in your local time zone, refer to the Crestron website 
(

http://www.crestron.com/

) for a listing of Crestron worldwide offices. 

You can also log onto the online help section of the Crestron website to ask 
questions about Crestron products. First-time users will need to establish a user 
account

 

to fully benefit from all available features.

 

20  

  IR Gateway: C2N-IRGW-1G & C2N-IRGW-F 

Operations & Installation Guide – DOC. 6468A 

Summary of Contents for C2N-IRGW-1G

Page 1: ...Crestron C2N IRGW 1G C2N IRGW F IRGateway Operations Installation Guide ...

Page 2: ...n by the Technical Documentation department at Crestron Electronics Inc 15 Volvo Drive Rockleigh NJ 07647 1 888 CRESTRON All brand names product names and trademarks are the property of their respective owners 2007 Crestron Electronics Inc ...

Page 3: ...on Software Requirements for the PC 14 Programming with Crestron D3 Pro or SystemBuilder 14 Programming with SIMPL Windows 15 Uploading and Upgrading 17 Establishing Communication 17 Programs and Firmware 17 Program Checks 18 Problem Solving 19 Troubleshooting 19 Check Network Wiring 19 Reference Documents 20 Further Inquiries 20 Future Updates 21 Appendix Mapping Table 22 Return and Warranty Poli...

Page 4: ......

Page 5: ...esnet integration Compatible with any 2 Series control device Compatible with standard electrical gang boxes and Decora style faceplates not included C2N IRGW 1G only Easy one piece mounting no additional hardware required C2N IRGW F only Specifications Specifications for the C2N IRGW 1G and C2N IRGW F are listed in the following table C2N IRGW 1G C2N IRGW F Specifications SPECIFICATION DETAILS IR...

Page 6: ...sions Without Faceplate Height 4 13 in 10 48 cm Width 1 75 in 4 45 cm Depth 1 37 in 3 45 cm C2N IRGW F Dimensions Diameter 1 50 in 3 81 cm Depth 2 19 in 5 54 cm C2N IRGW 1G Weight 2 4 oz 68 04 g C2N IRGW F Weight 0 9 oz 25 52 g Compatible Remote Controls Crestron MT 1000C Crestron ST 1700CIR Crestron WPR 48 Crestron CLS IRHT8 Any universal remote capable of generating RC5 commands 1 The latest sof...

Page 7: ...s section provides information on the connections controls and indicators available on your C2N IRGW 1G and C2N IRGW F C2N IRGW 1G Physical View Faceplate not included C2N IRGW F Physical View Operations Installation Guide DOC 6468A IR Gateway C2N IRGW 1G C2N IRGW F 3 ...

Page 8: ...0 79 in 1 99 cm 1 12 in 2 83 cm 1 75 in 4 45 cm 4 13 in 10 48 cm 3 28 in 8 33 cm 3 81 in 9 68 cm 1 2 3 C2N IRGW F Overall Dimensions 2 19 in 5 54 cm 11 4 wire pigtail to Cresnet 1 59 in 4 03 cm 1 50 in 3 81 cm 1 2 3 4 IR Gateway C2N IRGW 1G C2N IRGW F Operations Installation Guide DOC 6468A ...

Page 9: ...st accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio fre...

Page 10: ...on page 19 Identity Code The Net ID of the C2N IRGW 1G and C2N IRGW F has been factory set to 2D The Net IDs of multiple C2N IRGW 1G and C2N IRGW F devices in the same system must be unique Net IDs are changed from a personal computer PC via the Crestron Toolbox When setting the Net ID consider the following The Net ID of each unit must match an ID code specified in the SIMPL Windows program Each ...

Page 11: ...he remote transmitter 80 70 60 90 0 50 40 30 20 10 80 70 60 90 50 40 30 20 10 Wall C2N IRGW 1G C2N IRGW F Vertical Reception Angle Distance will depend on the remote transmitter 80 70 60 90 50 40 30 20 10 80 70 60 90 50 40 30 20 10 0 Wall Floor Operations Installation Guide DOC 6468A IR Gateway C2N IRGW 1G C2N IRGW F 7 ...

Page 12: ...N IRGW 1G in a standard single gang electrical box refer to illustration that follows this paragraph 1 Turn Cresnet system power OFF 2 Connect the Cresnet cable with the supplied connector plug to the C2N IRGW 1G s Cresnet port and the other end to the control system C2N IRGW 1G Installation view 6 32 x in combo head Single gang electrical box not supplied CAUTION Excess wire that is pinched betwe...

Page 13: ...r OFF 2 Locate an area on the wall or ceiling that is free of miscellaneous wiring and studs Make a small hole near the center of the designated mounting location to verify that the location is suitable 3 Drill or cut a 1 inch 2 54 cm diameter circular hole in the wall or ceiling at the desired location 4 Route the Cresnet wires from the control system to the C2N IRGW F location 5 Use the four sup...

Page 14: ...e C2N IRGW F Apply power after the connection has been made When making the connection to the C2N IRGW 1G and C2N IRGW F use Crestron power supplies for Crestron equipment Hardware Connection for the C2N IRGW 1G CRESNET CONNECT TO THE CRESNET CONTROL NETWORK Hardware Connection for the C2N IRGW F Pigtail Wires from C2N IRGW F CRESNET CONNECT TO THE CRESNET CONTROL NETWORK Red 24 Power White Y data...

Page 15: ...nging to the RC5 code set Two procedures are required to setup a universal remote The first procedure verifies that the universal remote chosen does transmit an identifiable code and therefore can communicate with the Crestron control system The second procedure maps the buttons on the universal remote so that they can be used in the SIMPL Windows program Code Verification Each universal remote co...

Page 16: ...ith another code b If activity is observed with each button press the code used was an acceptable code and the Crestron control system can accept commands from the universal remote Map the Universal Remote Once communication between the Crestron control system and the universal remote is achieved it is necessary to understand what commands are transmitted and to which devices Transmitter ID codes ...

Page 17: ...C or a piece of scrap paper create a table for recording the Button ID Decimal number associated with each button press on the universal remote Appendix Mapping Table on page 22 contains a table to record this information Create as many copies of the table as necessary 3 Click the Clear button in the Identify Transmitter window to reset the setup 4 Press a single button on the universal remote and...

Page 18: ...ogram control system to operate C2N IRGW 1G or C2N IRGW F SIMPL Windows version 2 07 24 or later with SIMPL Cross Compiler version 1 1 or later and Library update 454 or later Also requires Crestron Database version 18 1 4 or later Upload program and firmware Crestron Toolbox 1 04 16 or later Program with simple wizards for systems using a C2N IRGW 1G or C2N IRGW F optional but recommended Crestro...

Page 19: ... the Device Library To incorporate the C2N IRGW 1G or C2N IRGW F into the system drag the C2N IRGW from the Wireless Receivers Wireless Receivers IR folder of the Device Library and drop it in the System Views Locating the C2N IRGW in the Device Library The system tree of the control system displays the device in the appropriate slot with a default Net ID as shown in the following illustration C2N...

Page 20: ...nager Program Manager is the view where programmers program a Crestron control system by assigning signals to symbols The symbol can be viewed by double clicking on the icon or dragging it into Detail View A description for each signal in the symbol is described in the SIMPL Windows help file F1 16 IR Gateway C2N IRGW 1G C2N IRGW F Operations Installation Guide DOC 6468A ...

Page 21: ... http www crestron com manuals Use the Address Book in Crestron Toolbox to create an entry for the C2N IRGW 1G or C2N IRGW F using the expected communication protocol Indirect Select the Cresnet ID of the C2N IRGW 1G or C2N IRGW F and the address book entry of the control system that is connected to the C2N IRGW 1G or C2N IRGW F Display the C2N IRGW 1G s or C2N IRGW F s System Info window click th...

Page 22: ...upgrade the C2N IRGW 1G or C2N IRGW F firmware Program Checks Display the network device tree Tools Network Device Tree to show all network devices connected to the control system Right click on the C2N IRGW 1G or C2N IRGW F to display actions that can be performed on the C2N IRGW 1G or C2N IRGW F 18 IR Gateway C2N IRGW 1G C2N IRGW F Operations Installation Guide DOC 6468A ...

Page 23: ...ittent response when remote is transmitting Obstruction blocking communication path Avoid large obstructions in communication path Check Network Wiring Use the Right Wire In order to ensure optimum performance over the full range of your installation topology Crestron Certified Wire and only Crestron Certified Wire may be used Failure to do so may incur additional charges if support is required to...

Page 24: ... the twisted connection Apply solder only to the ends of the twisted wires Avoid tinning too far up the wires or the end becomes brittle Insert the tinned connection into the Cresnet connector and tighten the retaining screw Repeat the procedure for the other three conductors Add Hubs For larger networks i e greater than 28 network devices it may become necessary to add a Cresnet Hub Repeater CNXH...

Page 25: ...made available as manual updates These updates are solely electronic and serve as intermediary supplements prior to the release of a complete technical documentation revision Check the Crestron website periodically for manual update availability and its relevance Updates are identified as an Addendum in the Download column Operations Installation Guide DOC 6468A IR Gateway C2N IRGW 1G C2N IRGW F 2...

Page 26: ...uttons on the universal remote The list can then be used as a reference when creating the SIMPL Windows program PHYSICAL DEVICE BEING CONTROLLED TRANSMITTER ID HEX BUTTON TITLE ON UNIVERSAL REMOTE BUTTON ID DECIMAL Sheet of 22 IR Gateway C2N IRGW 1G C2N IRGW F Operations Installation Guide DOC 6468A ...

Page 27: ...0 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which i...

Page 28: ...ron Electronics Inc Operations Installation Guide DOC 6468A 15 Volvo Drive Rockleigh NJ 07647 2014708 Tel 888 CRESTRON 02 07 Fax 201 767 7576 Specifications subject to www crestron com change without notice ...

Reviews: