Decorator Wall Panels
Crestron
C2N-DB6/8/12
8
•
Decorator Wall Panels: C2N-DB6/8/12
Operations & Installation Guide - DOC. 6154
Wire Gauge Values
RESISTANCE (R)
WIRE GAUGE
4
16
6
18
10
20
15
22
13
Doubled CAT5
8.7
Tripled CAT5
NOTE:
All Cresnet wiring must consist of two twisted pairs. One twisted
pair is the +24V conductor and the GND conductor, and the other twisted
pair is the Y conductor and the Z conductor.
NOTE:
When daisy-chaining Cresnet units, strip the ends of the wires
carefully to avoid nicking the conductors. Twist together the ends of the
wires that share a pin on the network connector, and tin the twisted
connection. Apply solder only to the ends of the twisted wires. Avoid
tinning too far up the wires or the end becomes brittle. Insert the tinned
connection into the Cresnet connector and tighten the retaining screw.
Repeat the procedure for the other three conductors.
Identity Code
Every equipment and user interface within the network requires a unique
identity code (NET ID). These codes are recognized by a two-digit
hexadecimal number from 03 to FE. The NET ID of each unit must
match an ID code specified in the SIMPL Windows program. Refer to
“Setting the Net ID in Device Settings” on page 17 for details of the
SIMPL Windows procedure.
Refer to note
on page 20
for a
definition of
Viewport.
The NET ID of the wall panel has been factory set to
71
(72 and 73 for
C2N-DB8 and C2N-DB6, respectively). The NET IDs of multiple wall
panels in the same system must be unique. NET IDs are changed from a
personal computer (PC) via the Crestron Viewport.
NOTE
: For detailed information on establishing communication between
the PC and control system, refer to “Communication Settings” on page
20. If communication cannot be established, refer to the