1 of 2
LPN00283X0001A0_E
RUL Series
LED Rural Utility Luminaire
INSTALLATION INSTRUCTIONS
INSTRUCTIONS D’INSTALLATION
TO INSTALL:
LUMINAIRE INSTALLATION
STEP 1:
To open cover, press tabs in on both sides of the cover and carefully let the
cover swing down. See
Figure 1.
STEP 2:
Slide fixture on to a 1.66"O.D. or 2.38"O.D. pole tenon or mast arm through
opening on the rear of housing. See
Figure 2.
STEP 3:
Adjust leveling of fixture from side to side. To level from front to back, slide
pole to different Adjustment Steps in housing. Each step changes the angle
in 2.5° degree increments.
STEP 4:
Once desired position is achieved, use 9/16" socket wrench to tighten
mounting bolts to 150 in-lbs torque See
Figure 2
.
STEP 5:
IMPORTANT - DO NO
T
exceed 300 in-lbs torque on the mount bolts.
Exceeding recommended torque value resulting in excessive deformation of
mounting bracket will cause stripping of mount hardware which could lead
to an unsafe mounting condition.
STEP 6:
Reference
Electrical Connections
section for completing electrical
connections.
NOTE:
Refer to chart below for torque values for the screws on the
terminal block.
STEP 7:
If luminaire has a cord, route the cord down through the pole and make
electrical connections to customer supplied junction box.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed
including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. DANGER
- Risk of shock- Disconnect power before installation.
DANGER
– Risque de choc – Couper l’alimentation avant l’installation.
2. This luminaire must be installed in accordance with the NEC or your local electrical
code. If you are not familiar with these codes and requirements, consult a qualified
electrician.
Ce produit doit être installé conformément à NEC ou votre code électrique local.
Si vous n’êtes pas familier avec ces codes et ces exigences, veuillez contacter un
électricien qualifié.
3. If NEMA photo control is installed refer to NEMA® Receptacle section for
instructions.
4.
If mounting bolts are completely removed in the field they should be hand threaded
(prior to use of power tools) to ensure proper engagement of the thread when re-
installing. Failure to pre-start threads may result in cross-threading or stripping of the
bolts during reinstallation.
SAVE THESE INSTRUCTIONS FOR FUTURE
REFERENCE
1
2
Mounting
Bracket
Cover Tabs
Pole
Mounting Bracket
Bolts
Adjustment
Steps
Wire Size (AWG)
Assigned Torque Value for Screws
2-14 Copper, 2-8
Aluminum
AWG
In.-lbs.
2-3
50
4-6
45
8
40
10-14
35