14. Take down all HSN links on the specified blade.
This prepares the blade for the warmswap.
smw$
xtbounce --linkdown BladeID
15. Activate routing on the newly installed blade.
This command will
xtbounce
the blade.
smw$
xtwarmswap -a BladeID
16. Boot compute node Linux.
smw$
xtcli boot CNL0 BladeID
17. Mark the blade nodes up in the SDB.
smw$
xtprocadmin -k s up -n BladeID
5.3
Remove a Compute or IO Blade
Prerequisites
Tools Required:
T15 Torx driver
Time Required:
5 minutes
About this task
Use this procedure when the operating system is not running. If the operating system is running, use
on page 129.
Two videos are available that show how to install and remove these two components:
XC Series-AC Compute Blade Replacement
XC Series-AC IO Blade Replacement
Procedure
1. Log on to the SMW as
crayadm
.
2. Power down a blade slot:
a. Verify the operating system is not booted.
smw$
xtcli status cabinet_id
Compute and IO Blade Procedures
133