FRP 19: Blower Controller Bypass Switch (SW3) Replacement
AC Repair and Adjustment Procedures
122
Cray Research/Silicon Graphics Proprietary
HMM-168-A
FRP 19: Blower Controller Bypass Switch (SW3) Replacement
Use the following procedure when you replace the Blower Controller Bypass
switch (SW3).
Part Number
•
57199101 (switch, rocker silver contacts -- blower bypass)
Tools Required
•
#2 Phillips screwdriver
•
Small flatblade screwdriver
Switch Removal
1.
Open the front cabinet door.
2.
Open the cabinet’s main disconnect circuit breaker (CB1) and unplug the
cabinet. Place a lockout device over the cabinet’s plug and lock/tag it.
You may also open, lock, and tag the customer’s wall breaker(s).
3.
Open the WACS panel.
4.
Use a #2 Phillips screwdriver to remove the panel that covers the blower
controller (SCR1). Four screws hold the panel in place.
5.
Use a small flatblade screwdriver to depress the top flange on the switch
as you push the top of the switch through the cutout (switch hole) in the
WACS box. Refer to
WARNING
Ensure that the electrical plug for the
equipment that you service is
unplugged, locked, and tagged. Failure
to do so could result in severe shock
and burns.