background image

CF

S_

DR

V_

11

09

IO

M

0A

03

77

5B

DOUBLE REGULATING AND

COMMISSIONING VALVES

D921/923 - D931/933/934 - DP931/933/934

Crane Double Regulation Valve (DRV) & Fixed Orifice Double Regulation Valve (FODRV);

• are Y-pattern globe valves having characterised disks tending towards equal

percentage performance

• the double regulating feature allows valve opening to be set with an 3mm Allen key
• operation of the valve is by means of the Microset hand wheel
• the D921/D923 DRV and D931/D933/D934 FODRV valves are WRAS approved
• the DP931/DP933/DP934FODRV are designed as ʻCompanion Valvesʼ for the

Differential Pressure Control Valve

LIMITS OF USE

These installation, operation and maintenance instructions have been categorised in
accordance with the Pressure Equipment Directive – PED.

The fluid to be transported is limited to Group 2 liquids i.e. non-hazardous.
On no account must these valves be used on any Group 1 liquids, Group 1 gases
or Group 2 gases.

INSTALLATION AND OPERATING INSTRUCTIONS

COMMISSIONING

In the D931/D933/D934 and DP931/DP933/DP934 ranges, the flow rate is established by

measuring the differential pressure using the P84 test points - red is high pressure and blue

is low pressure. All valves are fitted with our ʻMicrosetʼ handwheel, which indicates the

valve set position, open to shut is 4 complete turns. The outer ring indicates 1/10th of turns

and the inner window indicates complete turns open, ie. a reading of 3 in the inner window

and 1 on the outer ring indicates 3.1 open; 4 being fully open.
Set flow rate as follows;
• connect measuring device to test points following the connection procedure specified by

the manufacturer of the device

• either by calculation or use of graphs, equate differential pressure to flow rate.

Graphs are available on our website or from our technical department

• flow regulation is achieved by adjusting the handwheel position
• once design flow rate is achieved, note handwheel position. The handwheel contains a

setting facility which should be used to maintain the set position, this can be set

as follows;

- remove cap in centre of handwheel

- using a 3mm Allen key tighten the centre screw until it stops, care should be taken

not to over tighten

- replace centre cap

- the valve can now be closed to isolate but will only open to the set position

www.cranefs.com

• Designed and manufactured under quality management

systems in accordance with BS EN ISO 9001-2008

The Company reserve the right to amend any product without notice.

FM311

ISO 9001

www.cranebsu.com

CRANE HOUSE, EPSILON TERRACE

WEST ROAD, IPSWICH

SUFFOLK IP3 9FJ
TELEPHONE: +44 (0)1473 277300

FAX: +44 (0)1473 277301

EMAIL: [email protected]

Reviews: