Maintenance and De-installation
This section defines the activities required to properly maintain the inverter and
must be facilitated by qualified personnel, trained in the installation,
de-installation and maintenance of inverters.
8.1
Product Maintenance
Maintenance is required to ensure the inverter remains in proper condition,
prolonging service life and prevent potential issues.
8.1.1
Check Electrical Connections
Check all conductor connections as regular maintenance inspection every
6 months to one year, depending on the temperature changes at the
installation site.
Check the conductor/cable connections. If loose, tighten all the
terminals to proper torque, referring to 3.3 Electrical Installation.
Check for damage to the conductor/cable jacket. Repair or replace
any damaged conductors/cables.
8.1.2
Clean the Air Vent Grate
The inverter can become hot during normal operation. It uses built in
cooling fans to provide sufficient air flow and help in heat dissipation.
Check the air vent grate regularly to make sure it is not blocked. Clean the
grate with a soft brush or vacuum cleaner attachment if necessary. The
frequency of this cleaning depends on the installation environment.
8.1.3
Replace the Cooling Fans
If the internal temperature of the inverter is too high or abnormal noise is
heard, assuming the air vent is not blocked and is clean, it may be