125
“ON/OFF” submenu, move the curser to “ON” and press
ENT
to start the
inverter. Then the inverter will start up and operate normally if the start-up
condition is met. Otherwise, the inverter will go to stand-by mode.
6.7
Shut-Down
Automatic shutdown
: The inverter will be shut down automatically when the
output voltage and power of PV modules are lower than the set value, AC
power grid fails, or the ambient temperature exceeds the normal range.
Manual shutdown
: Normally, it is not necessary to shutdown the inverter, but
it can be shut down manually if regulation setting or maintenance is required.
Press
ESC
and then
ENT
to access the Main Menu. Move the cursor to the
submenu
Manual
Power ON/OFF
and press
ENT.
Move the cursor to “OFF”
and press
ENT
, and then the inverter will be shut down.
6.8
Operation Mode
There are 4 operation modes: Logo/Start-up, Normal Operation, Standby and
Fault modes. See section 4.3 for details of these modes.
1. Logo/Start-up
mode displays the Chint Power Systems logo when the
inverter is checking if conditions are met for connection after a manual
start-up of the inverter.
2. Normal Operation
mode is the default indication interface for normal
operation. In this mode, the inverter is converting the DC power from the
array to AC power, feeding it continuously to the grid.
3. Standby
mode is active when the output voltage and power of PV
modules do not meet the startup conditions or PV voltage and input
power are lower than the set value. The inverter will check automatically
whether it meets the startup conditions in this mode until it turns back to
Normal Operation mode.