User Manual for Lead Acid Interactive UPS
04/22v.1
Page 34
VD-Series (5000VA-10kVA)
Chatsworth Products (CPI)
5 Specifications
MODEL NUMBER
VD5000B
VD6000B
VD10kB
CAPACITY
Power rating
5kVA (5kW)
6kVA (6kW)
10kVA (10kW)
INPUT
Voltage
110–300VAC*
Frequency
50/60Hz
OUTPUT
Voltage
200/208/220/230/240VAC (208/120V or 240/120V with optional transformer)
Frequency
50/60Hz ± 4Hz
THD (full load)
< 4%
Overload capacity
110% 10 min; 130% 1 min; > 130% 1 sec
Efficiency
Up to 95% online mode or 99% ECO mode
BATTERY
Charger amps
1–4A
Nominal/float voltage
240/273VDC
DIMENSIONS
& WEIGHT
Dimensions (W x D x H)
17.2 x 23.6 x 3.5 in
Weight
33.1 lbs
39.7 lbs
BYPASS
Model
BDM2A
BDM3A
BDM3B
BDM3C
DISTRIBUTION
Input connection
L6–30P (5, 6kVA) Terminal Block
(5,6,10kVA)
Terminal Block
(5,6,10kVA)
Terminal Block
(5,6,10kVA)
MODULE
Output connection
(2) L6-30R+
(2) C19
Terminal Block +
(2) L6-30R+ (2)
C19
Terminal block +
(1) L6-30R+
(2) C19
Terminal Block +
(2) L6-30R
ENVIRONMENT Operating temperature
32–104°F (0–40°C)
Audible noise
< 55dBA
< 58dBA
Altitude
11,500 ft above sea level
APPROVALS
UL, FCC, RoHS (pending)
WARRANTY
3 years electronics, 3 years battery warranty (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP)
INCLUDED IN BOX
Software CD, horizontal brackets, tower pedestals, USB cable
*Depending on load level.