Setting the "Connected" and "Read Setpoints" Attributes
MultiFlex PAK E2 Interface • 25
7.1.2. Deleting a PAK
To remove a PAK from the E2:
When PAKs are deleted in this way, E2 will
always delete the highest numbered PAKs first.
Therefore, if you have seven PAKs (numbered 1-
7) and you change the number of PAKs to five,
the E2 will delete board #6 and #7, leaving
boards #1 through #5.
7.2. Setting the "Connected"
and "Read Setpoints" At-
tributes
Unlike other MultiFlex devices, the PAK
will not automatically communicate with the E2
once the board is properly numbered and added
in the Connected I/O screen. To enable commu-
nication with the PAK, you must set the "Con-
nected" parameter in the General tab of the PAK
setup screens to "Yes." By default, a new PAK
added to the E2 will have the "Connected"
parameter set to "No."
The PAK also has a feature called Read Set-
points, which allows contractors who configure
the PAK via Hand-Held Terminal before connec-
tion to an E2 to have the PAK setpoints saved to
the E2 upon initial connection.
1. Press
I
(Configured Applications).
2. Select item "187. MultiFlex PAK". If multi-
ple PAKs are associated with this E2, a list
will appear prompting you to select a single
PAK. Use the arrow keys to highlight the
PAK you wish to view, and press
>
.
3. Press
E
- SETUP.
4. Use the arrow keys to highlight the "Con-
nected" field. Press Y to set this field to Yes.
5. If you want the E2 to read the setpoints from
the PAK and write them to the E2 upon con-
nection, set the "Read Setpoints" field to
Yes.
6. Press
J
to save changes and return to
the Status Screen.
The E2 will attempt to establish connection
with the PAK. If the Read Setpoints field was set
to Yes, the E2 will read the setpoints from the
PAK and write them to the PAK application’s
configuration. If Read Setpoints is set to No, the
E2 will write the PAK application’s setpoints to
the PAK upon initial connection.
7.2.1. Verifying Online Status
If you have properly set up the MultiFlex
PAK board on this E2’s I/O Network, after set-
ting the Connected parameter, you can go view
the status of the I/O Network (press
I
- Online Status). If E2 and the
PAK boards are communicating, this screen will
show the PAK board as “Online.” If not, it will
be shown as "Offline."
E2
1. Log in to the E2.
2. Press
I
to access the System Configuration
Menu.
3. Press
- Network Status/Setup
4. Press
- Connected I/O Boards & Controllers.
5. Change the number of PAK boards in the PAK Control-
lers field to the correct number of boards.