LEMCOM CANopen®
– User manual
Detailed
description of CANopen objects
COVAL
– LMCOP-EN-A-1155UM0068
39/49
12.22
3012h – Restore factory settings
Any given module or all of an island’s modules can be reset to their factory settings by sending the
following message:
CAN-ID
(600h+ID)
620h
Command
2Fh
Object L
12h
Object H
30h
Subindex
00h
Byte 0
Module no.
Byte 1
00h
Byte 2
00h
Byte 3
00h
Byte 0
is used to define the module to reset:
- Byte 0 = 0x00
Reset parameters of master module (address #0)
- Byte 0 = 0x01
Reset parameters of secondary module at address #1
-
…
- Byte 0 = 0x0F
Reset parameters of secondary module at address #15
- Byte 0 = 0x10 or higher
Reset parameters of all modules on the island
The factory settings are the following:
LEMC60X...
60% vacuum max.
LEMC90X…
85% vacuum max.
L1/h1
35%
/10%
65%
/10%
L2/h2
45%
/10%
75%
/10%
Automatic blowing
OFF
Automatic blowing duration (ms)
500
ASC
ON
DIAG ECO
ON
Max. number of bounces (DIAG/E)
2
DIAG/ECO assessment time (s)
1
Blue LED mode
BL1
Valve status (if comm. lost)
MD1
Table 15
– Factory settings