LEMCOM CANopen®
– User manual
Detailed
description of CANopen objects
COVAL
– LMCOP-EN-A-1155UM0068
33/49
12.12
2015h – Control system activation counter
The number of switchovers to air saving mode (ASC control) can be accessed using the following
SDO command:
Client (master)
server (LEMCOM)
CAN-ID
(600h+ID)
620h
Command
40h
Object L
15h
Object H
20h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The subindex is used to define the module to query (from 1 to 16):
- Subindex = 0x01
request for counter value on master module (address #0)
-
…
- Subindex = 0x10
request for counter value on secondary module at address #15
The reply is as follows:
Server (LEMCOM)
Client (master)
CAN-ID
(580h+ID)
5A0h
Command
43h
Object L
15h
Object H
20h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The number of ASC cycles is provided in hexadecimal format by the following:
Byte 3
– Byte 2 – Byte 1 – Byte 0
12.13
2016h – Control fault counter
The number of cycles interrupted subsequent to leakage in the vacuum network (switchover to
continuous suction) can be accessed using the following SDO command:
Client (master)
server (LEMCOM)
CAN-ID
(600h+ID)
620h
Command
40h
Object L
16h
Object H
20h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The subindex is used to define the module to query (from 1 to 16):
- Subindex = 0x01
request for counter value on master module (address #0)
-
…
- Subindex = 0x10
request for counter value on secondary module at address #15
The reply is as follows:
Server (LEMCOM)
Client (master)
CAN-ID
(580h+ID)
5A0h
Command
43h
Object L
16h
Object H
20h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The number of ASC cycles is provided in hexadecimal format by the following:
Byte 3
– Byte 2 – Byte 1 – Byte 0