16
3-1-3. AC Input / Output Terminal
④⑦
3-1-3-1. AC Input Terminal
④
SR-1600 Plus provides the AC utility input terminal at the rear side, and
user can connect the AC cable at L / N / PE. The SR-1600 Plus support
the AC input side internal parallel connection.
3-1-3-2. AC Output Terminal
⑦
The AC output terminal at the rear side of the SR-1600 Plus. User can
connect the L / N / PE.
Figure 10. AC terminal connection
3-1-3-3. Cabling
Interface
Wire Color
Wire AWG
AC Input
Line (L)
Black
Breaker suggestion
200-240Vac
:
50A/Shelf/8AWG
100-120Vac
:
80A/Shelf/6AWG
Neutral (N)
White
AC Output
Line (L)
Black
Neutral (N)
White
Ground
Green-Yellow
6 ~16AWG
Table 11. AC cabling definition
3-1-4. Parallel Connection Port
⑤⑥
In case the user needs more than 1 shelf, please use the CN1 and CN2
port to connect multi-shelves. Ensure that user sets the terminal resistor
first (please refer to section 3-2).
Please use RJ-45 cable for connection. To have better performance, we
suggest the cable length is less than 100cm.