3 Temperature
Measurement Point
¡
Installation environment
When using it,it is necessary to radiate heat by the heat of the pow-
er supply.
Table 3.1 - 3.8 shows the relation between the upper limit tempera-
ture (Point
1
and Point
2
) and load factors.
Please consider the ventilation so that the convection which is
enough for the whole power supply is provided.
Temperature of Point
1
and Point
2
become lower than upper limit
temperature.
The life expectancy in the upper bound temperature (Point
1
and
Point
2
) is three years or more.
Please refer to External View for the position of Point
1
and Point
2
.
Remarks:
*
Please be careful of electric shock or earth leakage in case of
temperature measurement, because Point
1
and Point
2
is
live potential.
*
Please contact us for details.
¡
Maximum temperature of measurement points
Table 3.1 Maximum temperature of measurement points (LHA10F-3R3-Y, LHA10F-
O
)
Cooling
Method Voltage
Mounting
Method
Load factor
Maximum temperature [
C
]
1
:Capacitor
2
:Capacitor
Convection
3.3, 5,
12V
A
40%
<
Io
[
100%
80
83
Io
[
40%
85
83
B
70%
<
Io
[
100%
75
75
Io
[
70%
85
83
C
50%
<
Io
[
100%
80
83
Io
[
50%
85
83
D
50%
<
Io
[
100%
80
77
Io
[
50%
85
83
E
50%
<
Io
[
100%
80
83
Io
[
50%
85
83
F
40%
<
Io
[
100%
77
77
Io
[
40%
85
83
15, 24V
A
50%
<
Io
[
100%
77
77
Io
[
50%
85
83
B
70%
<
Io
[
100%
80
80
Io
[
70%
85
83
C
50%
<
Io
[
100%
80
80
Io
[
50%
85
83
D
70%
<
Io
[
100%
78
80
Io
[
70%
84
83
E
50%
<
Io
[
100%
77
80
Io
[
50%
83
83
F
50%
<
Io
[
100%
77
77
Io
[
50%
83
83
Forced air 3.3 - 24V A,B,C,
D,E,F
Io
[
100%
80
80
Table 3.2 Maximum temperature of measurement points (LHA15F-3R3-Y, LHA15F-
O
)
Cooling
Method Voltage
Mounting
Method
Load factor
Maximum temperature [
C
]
1
:Capacitor
2
:Capacitor
Convection
3.3, 5,
12V
A
40%
<
Io
[
100%
75
80
Io
[
40%
85
85
B
60%
<
Io
[
100%
75
77
Io
[
60%
85
85
C
40%
<
Io
[
100%
77
83
Io
[
40%
87
85
D
60%
<
Io
[
100%
77
77
Io
[
60%
87
85
E
40%
<
Io
[
100%
77
80
Io
[
40%
85
85
F
40%
<
Io
[
100%
77
83
Io
[
40%
85
83
15, 24V
A
60%
<
Io
[
100%
77
77
Io
[
60%
83
83
B
70%
<
Io
[
100%
77
77
Io
[
70%
83
83
C
70%
<
Io
[
100%
85
80
Io
[
70%
89
85
D
60%
<
Io
[
100%
75
70
Io
[
60%
80
80
E
60%
<
Io
[
100%
80
77
Io
[
60%
83
83
F
50%
<
Io
[
100%
80
77
Io
[
50%
85
85
Forced air 3.3 - 24V A,B,C,
D,E,F
Io
[
100%
80
80
Table 3.3 Maximum temperature of measurement points (LHA30F-3R3-Y, LHA30F-
O
)
Cooling
Method Voltage
Mounting
Method
Load factor
Maximum temperature [
C
]
1
:Capacitor
2
:Capacitor
Convection 3.3 - 24V
A
60%
<
Io
[
100%
81
85
Io
[
60%
85
87
B
60%
<
Io
[
100%
81
83
Io
[
60%
85
85
C
60%
<
Io
[
100%
81
85
Io
[
60%
85
87
D
60%
<
Io
[
100%
86
84
Io
[
60%
86
82
E
60%
<
Io
[
100%
83
87
Io
[
60%
83
83
F
60%
<
Io
[
100%
83
85
Io
[
60%
87
87
Forced air 3.3 - 24V A,B,C,
D,E,F
70%
<
Io
[
100%
75
75
Io
[
70%
75
75
AC-DC Power Supplies Open Frame
Instruction Manual
LHA-27
May 26, 2022