A15ES
© Corroventa Avfuktning AB
2022.05
35 (67)
Alarms
If the machine detects an error, this information is presented in a pop-up screen and for as long as
one or more problems exist, there is a warning symbol in the top right corner of the default view.
The alarms that can be displayed are the following, each presented with recommendation on what to
do.
Alarm
Action / Advice
Mainboard connection failure
Internal error. If it remains, please contact service
technician.
Rotor failure
The rotor sensor indicates the rotor is not turning
and therefore the heaters have been switched off
to prevent excessive temperature with the wet
air. Please contact service technician.
Internal RHT sensor failure
Internal RHT sensor cannot be read.
If not and if it remains, please contact service
technician.
External RHT sensor failure
The machine has lost contact with the external
RHT sensor(s). Please check that the cables are
correctly mounted. When losing the external
sensors, the machine automatically reverts to
using the built-in RHT sensor.
One or more slaves are not
responding
This alarm is presented when the machine, used
as Master on a network, has lost connection with
one or more of its slave machines. If it is
presented, check all the system cables and the
power to the respective machines. As soon as
communication is re-established, the alarm will
automatically disappear.
Ambient temperature too high!
The machine has shut off the heaters due to too
high ambient temperature, above 40 degrees
Centigrade. If continuous fan is selected, the fans
will continue operating. The machine
automatically resumes operation if the
temperature drops.
Energy meter connection failure
The communication with the energy meter is
failing and the machine can therefore not present
the energy consumption. In other regards, the
Setpoint RH 60%, start drying.
Hysteresis
5%
5 %
Stop drying = RH 55 %.
Top position
Summary of Contents for A15ES
Page 1: ...A15ES Corroventa Avfuktning AB 2021 11 1 67 USER MANUAL ADSORPTION DEHUMIDIFIER A15ES ...
Page 3: ...A15ES Corroventa Avfuktning AB 2021 11 3 67 ...
Page 46: ...A15ES Corroventa Avfuktning AB 2022 05 46 67 APPENDIX 1 WIRING DIAGRAM ...
Page 47: ...A15ES Corroventa Avfuktning AB 2022 05 47 67 ...
Page 48: ...A15ES Corroventa Avfuktning AB 2022 05 48 67 ...
Page 49: ...A15ES Corroventa Avfuktning AB 2022 05 49 67 ...
Page 50: ...A15ES Corroventa Avfuktning AB 2022 05 50 67 ...
Page 51: ...A15ES Corroventa Avfuktning AB 2022 05 51 67 ...
Page 52: ...A15ES Corroventa Avfuktning AB 2022 05 52 67 ...
Page 53: ...A15ES Corroventa Avfuktning AB 2022 05 53 67 ...
Page 54: ...A15ES Corroventa Avfuktning AB 2022 05 54 67 ...
Page 55: ...A15ES Corroventa Avfuktning AB 2022 05 55 67 ...
Page 56: ...A15ES Corroventa Avfuktning AB 2022 05 56 67 ...
Page 57: ...A15ES Corroventa Avfuktning AB 2022 05 57 67 ...
Page 58: ...A15ES Corroventa Avfuktning AB 2022 05 58 67 ...
Page 59: ...A15ES Corroventa Avfuktning AB 2022 05 59 67 ...
Page 60: ...A15ES Corroventa Avfuktning AB 2022 05 60 67 ...
Page 61: ...A15ES Corroventa Avfuktning AB 2022 05 61 67 ...
Page 62: ...A15ES Corroventa Avfuktning AB 2022 05 62 67 ...
Page 63: ...A15ES Corroventa Avfuktning AB 2022 05 63 67 ...
Page 64: ...A15ES Corroventa Avfuktning AB 2022 05 64 67 ...
Page 65: ...A15ES Corroventa Avfuktning AB 2022 05 65 67 ...
Page 66: ...A15ES Corroventa Avfuktning AB 2022 05 66 67 ...
Page 67: ...A15ES Corroventa Avfuktning AB 2022 05 67 67 ...