![Cooper Wheelock Exceder LSPK C Series Installation Instructions Download Page 1](http://html1.mh-extra.com/html/cooper/wheelock-exceder-lspk-c-series/wheelock-exceder-lspk-c-series_installation-instructions_2661697001.webp)
273 Branchport Ave.
Long Branch, N.J. 07740
(800) 631-2148
www.coopernotification.com
1
PN P85445A
Copyright 2014 Cooper Wheelock, Inc. dba Cooper Notification
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL
The Wheelock Exceder LED LSPSTxC Series High-Fidelity Multi-Candela Speaker Strobes are UL Listed under Standard 1971 for Signaling
Devices for the Hearing Impaired, UL Standard 1480 for Speaker Appliances and ULC Listed under Standard CAN/ULC-S541-07 and CAN/
ULC-S526-07 for indoor Fire Protective Service. They are designed for multiple power requirements with high dBA output at each power tap,
and are designed for ceiling mounting only. Series LSPKxC, High Fidelity Speakers, are UL Listed under UL Standard 1480 and ULC Listed
under Standard CAN/ULC-S541-07 for Speaker Appliances; and can be ceiling or wall mounted. All models offer a choice of field select-
able taps, 1/8W to 2W for either 25.0 V
RMS
or 70.0 V
RMS
audio systems. The design incorporates a high efficiency speaker for maximum output
at minimum power across a frequency range of 300-8000Hz. The Speaker Strobes can provide non-synchronized strobe operation when
connected directly to a Fire Alarm Control Panel (FACP), or provide synchronized strobe operation when used in conjunction with a Dual Sync
Module (DSM), or Wheelock’s Power Supplies. All models are Listed for
indoor use only
with the backboxes specified in these instructions
(see Mounting Options).
NOTE:
All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems – CAN/
ULC-S524-01 and Canadian Electrical Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING
: This appliance is a “
FIRE ALARM DEVICE - DO NOT PAINT
”
WARNING: Please read these instructions carefully. Failure to comply with any of the following instructions, cautions and warn-
ings could result in improper application, installation and/or operation of these products in an emergency situation, which could
result in property damage and serious injury or death to you and/or others.
SPECIFICATIONS
Table 1: UL/ULC Listed Models and Ratings
Speaker
Model
*
Voltage
dBA at 10 Feet (Rated Watts)
Reverberant Per UL 1480
Anechoic dBA
Per CAN/ULC-S541-07
1/8
1/4
1/2
1
2
1/8
1/4
1/2
1
2
LSPKxC
25/70
75
79
82
85
87
75
79
82
85
87
LSPSTxC
25/70
75
79
82
85
87
75
79
82
85
87
*
when ordering, “x” denotes the product color (W = White, R = Red)
NOTES
•
Strobes will produce 1 flash per second over the “Regulated Voltage” range.
•
All models are Listed for indoor use with a temperature range of +32ºF to +120ºF (0ºC to +49ºC) and maximum humidity of 93% RH.
The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the
original cartons and is not subjected to misuse or abuse.
•
dBA is rated per UL Standard 1480 and ULC Standard ULC-S541-07 for Speaker Appliances. Frequency range of speakers is 300-
8000Hz.
•
These appliances were tested to the operating voltage limits of 16-33 volts using Filtered (DC) or unfiltered Full-Wave-Rectified (FWR).
Do not apply 80% and 110% of these voltage values for system operation.
•
Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit
wiring resistance to determine the applied voltage to the strobe.
Table 2:
Current Ratings for Strobe Only
Maximum RMS Current (AMPS)
LSPSTxC
Voltage Range
Regulated Voltage
15cd
30cd
75cd
95cd
DC
16-33VDC
24
0.040
0.058
0.155
0.258
FWR
16-33VRMS
24
0.056
0.078
0.195
0.330
NOTE:
Candela setting will determine the current draw of the product.
Table 3: ULC Directional Characteristics
25/70V
-3dBA
+/- 75 degrees horizontal; +/- 70 degrees vertical
-6dBA
+/- 90 degrees horizontal; +/- 90 degrees vertical
NOTE:
The maximum wire impedance between strobes shall not exceed 35 OHMS.
NOTE
: Make sure that the total RMS current required by all appliances that are connected to the system’s primary and secondary power
sources, NAC Circuits ,DSM Sync Modules or Wheelock Power Supplies do not exceed the power sources’ rated capacity or the current
ratings of any fuses on the circuits to which these appliances are wired.
CAUTION:
Speaker
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WARNING: Overloading power sources or exceeding fuse ratings could result in loss of power and failure to alert occupants dur-
ing an emergency.
When calculating the total currents, use Table 2 to determine the highest value of “RMS Current” for an individual strobe (across the
expected operating voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for
any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the
listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For ex-
ample, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across
the output) may exhibit this characteristic.
CAUTION:
The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If
these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the
product.
WIRING INFORMATION
A 1.5µF blocking capacitor for DC supervision of audio lines by the FACP is factory wired in series with the speaker input. Supervision
voltage must not exceed 33 VDC.
1. Speaker and Speaker Strobe models have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at
each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in Figure 2. The polarity shown in
the wiring diagrams is for operation of the appliances.
3. Connect speaker wires to common and positive of terminal block and select the power tap terminal for 1/8W, 1/4W, 1/2W, 1W or 2W;
25V or 70V as required (see Figures 1, 2, 3,5 and Table 4). Each doubling of rated Watts increases sound output by 3 dBA.
4. Using the slide switch shown in Figure 3, select voltage and wattage as shown in Table 4. Each letter corresponds to a position of the
switch located on the printed circuit board.
Refer to Sync Module instruction sheets DSM (P83177) or Wheelock Power Supplies for additional information.
Figure 1 LED Strobe Wiring Figure 2 Wire Connection
NOTE:
Check electrical ratings specified in Tables 1 and 2 (as appropriate) to ensure proper electrical input. Ensure the speaker wiring is
connected to speaker terminals only, and strobe wiring is connected to strobe terminals only. Ensure the wiring at the FACP is correct.
NOTE:
Wiring method shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installa-
tions, Section 32.
WARNING: Improper electrical input can damage the product or cause it to malfunction.
NOTE:
The Speaker Strobe appliances must be set to the desired dBA sound output level before they are installed. This is done by
properly setting the slide switch in accordance with these instructions.
WARNING: Incorrect settings will result in improper performance. Factory setting is F: 70V @ 1/2 W.
Figure 3: Speaker Selection Switch
NOTE
: Slide the Switch Indicator selection switch to the desired tap setting.
INSTALLATION INSTRUCTIONS
EXCEDER LED CEILING MOUNT HIGH FIDELITY
SPEAKER AND SPEAKER STROBES