Cooper Notification IPC-8000 Installation Instructions Manual Download Page 7

Installing the IPC-8000

 

Installation Instructions: IPC-8000 
P/N P10-00059 Rev A 

 

 

 

I

N

S

T

A

L

L

A

T

I

O

N

 

 

 

I

N

S

T

R

U

C

T

I

O

N

S

 

7

 

 

1.

 

Ensure the AC power source is off.  

2.

 

Identify or cut the following penetration holes. Refer to 

Figure 3

 for available penetration 

hole locations on the top and sides of the enclosure. 

a.

 

AC Power Cord 

b.

 

Network Cable (if required) 

c.

 

RF Antenna Cable (if required) 

 

 

 

 

Table 3 Conduit Hole Size and Flat Surface 

Trade Size of Conduit 

 

Recommended Diameter of 

Opening 

Recommended Minimum 

Diameter of Flat Surface  

Inches 

mm 

Inches 

mm 

Inches 

mm 

0.375 

9.53 

0.709 

18 

0.98 

25 

0.5 

12.70 

0.866 

22 

1.20 

30 

0.75 

19.05 

1.10 

28 

1.50 

38 

25.4 

1.38 

35 

1.90 

48 

1.25 

31.75 

1.73 

44 

2.40 

60 

1.5 

38.10 

1.97 

50 

2.60 

67 

50.80 

2.48 

63 

3.30 

83 

 

6.2.2  Connecting External AC Power Cable 

When routing the external AC power, take care to allow for the following: 

 

Follow best practices for proper separation of the AC power cable, RF Antenna 
cable and Ethernet cable to avoid RF interference. 

 

Installation of a NEMA-rated conduit and fitting.  

 

 

All conduit and cables inserted into the enclosure shall adhere to the 
Local Codes and per the Authority having jurisdiction. 

 

Connect to an AC circuit protected by a maximum 20 AMP fuse or circuit 
breaker. A readily accessible disconnect device must be provided.

 

Summary of Contents for IPC-8000

Page 1: ...ower to equipment at any time maintenance work is in progress Do not make any unauthorized alterations to equipment or components Changes or modifications not expressly approved by Cooper Notification...

Page 2: ...8000 shall be determined by the Installer based on the placement of the Unit and the construction of the wall material Appropriate Installation Instructions and Manuals as listed in Table 1 Optional U...

Page 3: ...ECIFICATIONS AC Input 100 240 VAC 50 60 Hz 1 A Power Consumption Refer to the IPC Installation Instructions for details Back Up Power UPS 901 rechargeable battery backup optional for non ACU 8411 appl...

Page 4: ...Keyhole Locations Shown with optional RADIO 900M and UPS 901 1 Verify power is disconnected to the IPC 8000 enclosure 2 Disconnect all cables to the IPC 3 Remove the IPC from its mounting plate as fo...

Page 5: ...n Refer to Figure 1 to identify the keyhole locations on the IPC 8000 enclosure 3 Open and remove the IPC 8000 enclosure door 4 Mount the enclosure at the selected location 5 Reinstall the enclosure d...

Page 6: ...be installed into the IPC 8000 enclosure Optional equipment may cover or impair the routing of cables Refer to Figure 3 for the location of available penetration hole locations on the left side right...

Page 7: ...mm Inches mm 0 375 9 53 0 709 18 0 98 25 0 5 12 70 0 866 22 1 20 30 0 75 19 05 1 10 28 1 50 38 1 25 4 1 38 35 1 90 48 1 25 31 75 1 73 44 2 40 60 1 5 38 10 1 97 50 2 60 67 2 50 80 2 48 63 3 30 83 6 2...

Page 8: ...ow ample slack in the cable to properly route and terminate all wires to the AC Terminal Board 3 Terminate the external AC power cord to TB1 inside of the enclosure as shown in Figure 4 as follows Lin...

Page 9: ...6 2 3 External Appliance Connections Refer to the IPC Installation Instructions P10 00063 for all IPC connector and pin out specifications to connect the Ethernet cable speakers strobes LED signs and...

Page 10: ...g Plate Keyhole Locations 4 Loosen the locking tabs and position them perpendicular to the mounting plate as shown previously in Figure 2 5 Tighten the locking tabs 6 3 2 Internal Connections The inte...

Page 11: ...A I N S T A L L A T I O N I N S T R U C T I O N S 11 Figure 6 IPC 8000 shown with RADIO 900M and UPS 901 and Internal Cabling ENSURE PROPER GROUNDING OF EARTH TERMINAL CONNECT THE RADIO 900M MAIN GRO...

Page 12: ...Installing the IPC 8000 Installation Instructions IPC 8000 P N P10 00059 Rev A I N S T A L L A T I O N I N S T R U C T I O N S 12 Figure 7 IPC 8000 w Radio 900M Wiring Diagram...

Page 13: ...rovide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not ins...

Page 14: ...VES system The External Source s audio is converted to digital audio by the associated External Audio Source IP located in the IPC 8000 and sent out to the IPC network Refer to the WAVES 8 Administrat...

Page 15: ...ding a contact closure to the designated External Source IPC as follows o PTT Input J3 pin 5 In o PTT Ground J3 pin 4 Ground o Digital Input 1 J2 pin 8 In o Digital Input 1 J2 pin 3 Common Line Level...

Page 16: ...the Play PlayAudioSource commands Refer to the WAVES 8 Administrator Manual for configuration of the IPC and details regarding the operation and sequence of events for connecting the VOX feature When...

Page 17: ...indicate to the WAVES IPC that the External Source is in a fault condition o Digital Input 3 J2 pin 10 In o Digital Input 3 J2 pin 3 Common Line Level Audio a connection from WAVES providing 1 VRMS 60...

Reviews: