FEATURES
This emergency battery pack (EBP) includes extra features which enhance its
operation and maintainability.
1. Patented EZ key battery disconnect:
When the EZ key is inserted into the test button,
the battery is disconnected. This feature prevents unnecessary cycling of the battery
during the construction process. It can also be used if the room is decommissioned
for an extended period to prevent the batteries from being over discharged.
2. Patent pending Test Button / Indicator Light / Laser Input:
The test button
houses the EZ key, powers the indicator light, contains the laser input for testing
and functions as the mechanical test button. Integration of these functions
improves performance and fixture aesthetics.
3. Power controlled output:
This feature maintains consistent light output during
the entire 90 minutes of emergency operation ensuring there is no drop in lumen
output as the battery voltage drops
4. Self Diagnostics Testing:
The unit will perform a battery capacity, lamp/LED, and
charge circuit test every 30 days for 30 seconds. During this time, the indicator
LED will change to a steady yellow. It will perform a full battery capacity (90
minute) test once per year. During this time, the indicator LED will change to a
blinking yellow.
Field Installation Classification
1. Determine electrical compatibility with fixture: Verify the emergency driver wattage
(14 watts) does not exceed the driver’s AC input. Also, verify that the forward voltage
of the LEDs is within the operating parameters of the selected model (see table
below).
2. Calculate Lumen output during emergency operation:
Go to the website www.
designlights.org and identify the light fixture by using the available search criteria.
Determine the fixture rated data – efficacy in lumens/watt. Multiply the fixture efficacy
by the output wattage of the selected emergency battery pack to determine the lumen
output of the fixture during emergency operation.
Example:
Fixture efficacy = 100 lumens/watt
EBPLED14WSD provides 14 watts of constant power
Fixture output = 100 lumens/watt X 14 watts = 1400 lumens during
emergency operation
3. Insure means of egress lighting levels:
Follow industry standard methods of
lighting layout to determine placement of emergency battery pack equipped fixtures.
Verify the selected EBP will provide enough lumen output to meet path of egress
illumination requirements.
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD
ALWAYS BE OBSERVED INCLUDING THE FOLLOWING
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at adequate heights to prevent
tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by Cooper Lighting Solutions
may cause an unsafe condition and will void the warranty.
6. Do not use this equipment for other than its intended purpose.
7. Not for use with sealed and gasketed fixtures.
8. SAVE THESE INSTRUCTIONS.
NOTES:
1. To prevent voltage from being present on the output wires (Red/White & Blue/White),
do not connect the test button assembly to the EBP or insure the EZ key is securely in
place.
2. This product is for use with LED fixtures with loads capable of the output wattage and
forward voltage within the ranges below
3. Make sure all the connections are in accordance with the National Electrical Code
and any local regulations.
4. To reduce the risk of electrical shock, disconnect both normal and emergency
power supplies, including the test button indicator light (which disconnects the
battery) before servicing. Ensuring the battery disconnect (EZ Key) is securely in
place also prevents battery powered operation.
5. These emergency battery packs can be field, or factory installed depending on
version. See mounting section for details.
6. This product is for use in indoor fixtures only. Do NOT use near heated air
handling outlets, wet locations or hazardous locations.
7. An un-switched AC power source is required. (120 - 277 volts 50/60 HZ) for
proper operation.
8. The sealed, no-maintenance battery is field replaceable. Contact the
manufacturer for information on replacement if needed.
9. All maintenance should be performed by qualified service personnel.
ENGLISH
EBPLEDSD14W
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
Output Power (W) MinVf (V)
Max Vf (V)
14W Versions
14
16
55
Output Power (W) MinVf (V)
Max Vf (V)
14W Versions
14
16
55
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before installing or servicing
Instructions for Surelites LED Emergency Battery Packs