Installation Instructions
Description
Model # OXC-P-1500-R
Model # OXC-P-2MH0-R
Extreme Temperature PIR Sensor
10-30 VDC
• Read all instructions on both sides of this sheet first.
• Plan all component locations carefully.
• Install in accordance with ALL local codes.
• For use with Greengate Switchpacks & Systems Only. For use with other systems,
contact Technical Support.
• Sensor performance optimized when temperatures range from -40°C (-40°F)
to 52°C (125°F)
• For indoor use only.
• DO NOT run any Greengate low voltage wiring in the same conduit as power
conductors.
• UL listed for damp locations
General Information
Cooper Controls
203 Cooper Circle, Peachtree, GA 30269
800-553-3879
www.coopercontrol.com
The OXC-P-1500-R Extreme Temperature and OXC-P-2MH0-R Extreme Temperature High Bay Sensor
uses passive infrared (PIR) technology with temperature compensating circuitry to control lighting in applica-
tions where extreme temperatures/humidity must be tolerated. When motion is detected, the blue wire is
electronically connected to the red wire, energizing the relay in the switchpack to turn on the load. If vacancy
is detected, the blue wire is disconnected from the black, causing the relay to open, turning off the load. The
red lead is +15 VDC supply, the black lead is common, and the blue is the relay control.
Controls:
Time delay, self-adjust enable/disable, ambient lights setting, HID interface, lighting sweep
option, pull-up option and manual override option are adjusted with the DIP switch. See DIP
switch options under
CHECKOUT AND ADJUSTMENT
on the reverse.
Description
Model
Coverage
Field of View
Power Requirements
OXC-P-1500-R
Up to 1,500 sq. ft.
360° (Two Way)
10-30VDC 25mA
from switchpacks
OXC-P-2MH0-R
When mounted @ 25 ft.,
360° (Two Way)
10-30VDC 25mA
up to 25 sq. ft. in all
from switchpacks
directions or 50 linear ft.
for warehouse aisles.
Sensor:
Choose sensor location carefully. The sensor must have a clear view of the area to be controlled.
There must be an unobstructed line-of sight from the sensor to any part of the controlled area.
For maximum coverage, position the sensor parallel to the longest dimension in the area.
Switchpack:
The switchpack is generally mounted above the ceiling
on the outside of the junction box that contains a hot line,
neutral and the existing switch leg from which the lighting
is controlled. If additional switchpacks are required, they
are mounted on the outside of the boxes containing the
appropriate switch legs. In installations where there are no
existing switch legs, the switchpack may be mounted on the
outside of any conventional standard junction box, with or
without an extension ring.
Product Mounting Location
Coverage Diagrams
OXC-P-2MH0-R
OXC-P-1500-R
CAUTION:
Before installing or performing any service on a Greengate system,
the power MUST be turned off at the branch circuit breaker. According to NEC
240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent
lighting circuit, the circuit breaker should be marked “SWD.”
NOTE REGARDING COMPACT FLUORESCENT LAMPS:
The life of some compact
fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching.
Check with CFL and ballast manufacturer to determine the effects of cycling.
NOTE: Model OXC-P-1500-R and OXC-P-2MH0-R is designed specifically for parking
structures, cold storage areas, and other applications where extreme temperatures
exist. Use Model OXC-P-1500-R in areas up to a maximum of 1,500 square feet of
major motion at a mounting height of 8 feet. Coverage of Model OXC-P-2MH0-R is
2MH or twice the mounting height when mounted up to 25 feet. In a warehouse aisle,
a sensor mounted at 25 feet will provide coverage for 25 feet in any direction or 50 lin.
ft.
Time Delay:
The sensor has eight (8) discreet time delay settings from 15 seconds to 30 minutes.
Bas Interface:
The sensor has an isolated Form C relay for BAS interface.
Lighting Sweep Option:
If selected, this DIP switch option forces an initial 50-second delay upon “power up” to prevent
false activation in buildings with computer control systems.
Ambient Lights Control Circuit:
Use the Ambient Lights controls located on the DIP switch to select the footcandle level at which
ambient light will be sufficient. If ambient light is at the selected level when occupancy is detected,
lights will not be activated. The Ambient Lights Control Circuit incorporates a deadband and time
delay which ignore brief changes in light levels, such as headlights of a passing car.
High/Low Hid Interface:
Setting the HID control DIP switch to On, allows the lamps to achieve and maintain full brightness for
20 minutes. The sensor signals the switchpack to keep its relay engaged for the 20 minutes after initial
power up. After the 20-minute warm-up, normal time delay function takes over and bi-level dimming is
enabled. Full auto-off is achieved by installing a timer switch in series to the HID lighting.
Setting the HID control DIP switch to Off allows normal control of fluorescent and incandescent
loads via the switchpack.
Self- Adjusting Feature:
When the delay control is left at 15 seconds (for installer test), the OXC-P-1500-R and OXC-P-2MH0-R
will reset the time delay to 6 minutes automatically after remaining off for one complete hour.
Setting the Self Adjust DIP switch to ON disables the self-adjusting feature.
Temperature Compensating Circuitry:
Temperature-compensating circuitry stabilizes sensitivity at temperatures from -40°C (-40°F) to 52°C
(125°F) to avoid false activations. If the temperature is outside of this range, lights will remain on and the
LED will blink three times every five seconds.
30'
10'
0'
10'
20'
30'
20'
0'
8'
25'
11' 7' 3' 0' 3' 7' 11'
25'
SIDE VIEW
TOP VIEW
30’
20’
10’
0
10’
20’
30’
30'
10'
0'
10'
20'
30'
20'
25’
SIDE VIEW
TOP VIEW
0
30’
20’
10’
0
10’
20’
30’
30’
20’
10’
0
10’
20’
30’